Plan Review Details - Permit 03021062
Plan Review Stops For Permit 03021062
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-03-12 Cont ID  
Sent By pkrauss Date 2003-03-13 Time 14:08 Rev Time 3.00
Received By rmcdouga Date 2003-03-12 Time 11:04 Sent To  
Notes
2003-03-13 00:00:00PROVISO
  
 SUBMIT MANUFACTURER'S PRODUCT APPROVALS
 AND UL LISTING INFORMATION FOR THE ONE
 HOUR FIRE RATED GLASS BLOCK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-03-10 Cont ID  
Sent By sthyng Date 2003-03-12 Time 16:45 Rev Time 3.00
Received By rmcdouga Date 2003-03-10 Time 10:43 Sent To  
Notes
2003-03-10 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SPECIFY ON THE PLANS THAT WIRE MESH
 IN THE SLAB IS TO BE SUPPORTED AT A MAX.
 OF 3 FT OC AS REQUIRED BY FBC 1909.3.
  
 3) GLAZING WITHIN 3 FEET HORIZONTALLY OF
 A TUB OR SHOWER IS REQUIRED TO BE
 TEMPERED. THIS IS NOT CLEARLY INDICATED
 BY NOTE #9 ON SHEET 1. PLEASE CLARIFY.
  
 4) SPECIFY THE SIZE OF THE ATTIC ACCESS
 ON THE PLANS. FBC 2309.6
  
 5) SPECIFY THE LENGTH/EMBED DEPTH OF
 5/8" EXPANSION BOLTS FOR THE GARAGE DOOR
 BUCKS ON SHEET 4.
  
 6) THE REAR GABLE END ADJACENT TO THE
 VAULTED CEILING IS REQUIRED TO BE
 CONTINOUS FROM THE FLOOR TO THE CEILING
 DIAPHRAGM PER FBC 1918.3.2. PLEASE
 PROVIDE A DETAIL OF THE RAKE BEAM AT
 THIS LOCATION.
  
 7) THE SITE SPECIFIC ENGINEERING FOR THE
 NORANDEX PRODUCTS ARE REQUIRED TO HAVE
 THE EMBOSSED SEAL OF THE DESIGNER OF
 RECORD FOR THE STRUCTURE AND THE JOB
 LOCATION LISTED ON THE THE FORM. THIS IS
 REQUIRED BY THE BUILDING OFFICIAL PER
 FBC 103.7.
  
 8) THE INFORMATION LISTED ON THE ENERGY
 CALCULATION FORM IS INCORRECT. THE R-
 VALUES FOR THE EXTERIOR AND ADJACENT
 WALLS ARE REVERSED. SUBMITTED CORRECTED
 FORM.
  
 9) PROVIDE THE MANUFACTURER'S
 SPECIFICATIONS AND ANDUL LISTING
 INFORMATION FOR THE ONE HOUR FIRE RATED
 GLASS BLOCK ASSEMBLY.
  
 10) SOME OF THE OPENING SIZES ON THE
 STORM PANEL SCHEDULE DO NOT CORRESPOND
 WITH TOSE ON THE WINDOW SCHEDULE ON
 SHEET 2 OF THE PLANS. PLEASE REVISE.
  
 11) PROVIDE PRODUCT APPROVALS FOR THE
 HORIZONTAL SLIDING WINDOW WITH THE XOX
 CONFIGURATION AS SHOWN ON THE PLANS.
  
 12) THE LOMR INFORMATION LISTED ON THE
 SURVEY IS INCORRECT. PLEASE REVISE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-03-06 Cont ID  
Sent By pkrauss Date 2003-03-13 Time 14:12 Rev Time 0.25
Received By dpalmer Date 2003-03-06 Time 08:56 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-12 Cont ID  
Sent By sthyng Date 2003-03-12 Time 16:45 Rev Time 0.00
Received By sthyng Date 2003-03-12 Time 16:45 Sent To B
Notes
2003-03-12 00:00:00TO RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-18 Cont ID  
Sent By dpalmer Date 2003-02-18 Time 11:25 Rev Time 0.00
Received By dpalmer Date 2003-02-18 Time 11:25 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-03-13 Cont ID  
Sent By pkrauss Date 2003-03-13 Time 14:08 Rev Time 0.30
Received By pkrauss Date 2003-03-13 Time 14:08 Sent To E
Notes
2003-03-13 00:00:00RE-STAMP MECHANICAL PERMIT 03021107

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-03-03 Cont ID  
Sent By jleech Date 2003-03-03 Time 17:50 Rev Time 0.33
Received By jleech Date 2003-03-03 Time 17:50 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-03-03 Cont ID  
Sent By sgraham Date 2003-02-19 Time 14:18 Rev Time 0.25
Received By jleech Date 2003-03-03 Time 17:50 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-02-19 Cont ID  
Sent By dpalmer Date 2003-02-18 Time 11:25 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***