2003-02-27 00:00:00 | **********CORRECTIONS************ |
| |
| 1.)PLEASE COMPLETE OWNER INFORMATION |
| ON THE PERMIT APPLICATION. |
| |
| 2.)PROVIDE A WALL SECTION DETAIL |
| FROM FOUNDATION THROUGH THE ROOF FOR THE |
| PROPOSED WALL AS PER FBC 104.3.1.1. |
| SHOW ALL DIMENSIONS.SHOW ALL PROPOSED |
| INSULATION ON THE WALL SECTION DETAIL, |
| AS WELL AS OTHER ELEMENTS INCLUDING |
| ALL ATTACHMENTS. |
| |
| 3.)PROVIDE A DETAIL FOR THE PROPOSED |
| NEW PATIO SLAB.INCLUDE A DETAIL FOR |
| BONDING OF FRESH CONCRETE TO HARDENED |
| CONCRETE AS PER FBC 1924.6.2. |
| |
| 4.)PROVIDE TWO COPIES OF THE PRODUCT |
| APPROVAL FOR THE PROPOSED 6-PANEL |
| METAL DOOR SHOWN ON THE PLAN. |
| |
| 5.)INDICATE DRYWALL ON FURRING TO |
| BE INSTALLED ON EXISTING PATIO WALLS |
| ON THE PLAN.IF DRYWALL IS BEING |
| INSTALLED ON THE CEILING, INDICATE THAT |
| ON THE WALL SECTION DETAIL. |
| |
| 6.)PROVIDE A WINDOW SCHEDULE.SHOW |
| SIZES AND LOCATIONS OF ALL EGRESS |
| WINDOWS. |
| |
| 7.)IF AIR CONDITIONING IS TO BE |
| SUPPLIED TO THE ROOM BEING ENCLOSED, |
| APPLY FOR A MECHANICAL PERMIT.THIS |
| PERMIT MAY BE APPLIED FOR SEPARATELY |
| FROM THIS BUILDING PERMIT OR MAY BE |
| SUBMITTED WITH THIS APPLICATION.FOR |
| THE MECHANICAL PERMIT YOU WOULD NEED |
| A PLAN, FORM 600C (SHORT FORM ENERGY |
| CALC) AND THE MAKE, MODEL AND BTU OF |
| THE EXISTING AHU. |
| |