Plan Review Details - Permit 03021019
Plan Review Stops For Permit 03021019
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-07-10 Cont ID  
Sent By rbrown Date 2003-07-08 Time 10:07 Rev Time 0.00
Received By rbrown Date 2003-07-08 Time 10:07 Sent To  
Notes
2003-07-08 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 --PROVISO--
 FBC 1005.7.3THE SPECIFIED SMOKE
 DETECTION SHALL BE IN ACCORDANCE NFPA 72
 AND SOUND AN ALARM IN THE MEZZANINE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-04-24 Cont ID  
Sent By lmartine Date 2003-04-24 Time 08:42 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-02-26 Cont ID  
Sent By rbrown Date 2003-02-26 Time 09:23 Rev Time 0.00
Received By rbrown Date 2003-02-26 Time 09:23 Sent To  
Notes
2003-02-26 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC 104.6.5THE DECLARED BUILDING
 PERMIT VALUATION APPEARS TO HAVE BEEN
 UNDERESTIMATED.THE VALUATION WILL BE
 INCREASED TO $9000, UNLESS A COPY OF A
 SIGNED CONTRACT IS SUBMITTED TO JUSTIFY
 A LOWER VALUATION.A NOTICE OF
 COMMENCEMENT WILL HAVE TO BE RECORDED
 AT PALM COUNTY COURTHOUSE AND THE
 PERMIT FEE DIFFERENCE WILL BE PAYABLE AT
 THIS OFFICE.
  
 2) FBC* 104.2.2THE RAISED SEAL HAS NOT
 BEEN PROPERLY APPLIED.PLEASE RECTIFY.
  
 3) FBC 307SUBMIT MATERIAL SAFETY DATA
 SHEETS, FOR THE MATERIALS/PRODUCTS USED
 IN THE OCCUPANT'S BUSINESS, TO JUSTIFY A
 CLASSIFICATION AS NON-HAZARDOUS
 OCCUPANCY.
  
 4)FBC* 106.4.3MEZZANINE DECK SAFE
 LOADING SIGN.THE PLANS SHALL BE
 AMENDED TO SHOW THE DETAILS AND WORDING
 OF THE SAFE FLOOR LOAD PLATE(S) TO BE
 AFFIXED IN A CONSPICUOUS PLACE ON THE
 MEZZANINE.
  
 5) FBC 1007.3.1THE STAIR TREADS SHALL
 BE A MINIMUM OF 11".AMEND THE NOTE ON
 SHEET S-1 AND THE STAIR SIDE ELEVATION
 ON SHEET S-2.
  
 6) FBC 1005.7.3THE EGRESS STAIRWAY
 FROM THE MEZZANINE MAY REMAIN OPEN AND
 DESCEND INTO THE FLOOR SPACE OF THE
 MAIN ROOM, ONLY IF THE SPACE BENEATH THE
 MEZZANINE IS TOTALLY OPEN AND
 UNENCUMBERED BY PARTITIONED ROOMS OR
 SPACES UNLESS THOSE PARTITIONED SPACES
 ARE PROTECTED THROUGHOUT WITH A SMOKE
 DETECTION SYSTEM.THAT SMOKE DETECTION
 SYSTEM SHALL BE IN ACCORDANCE WITH
 NFPA 72 AND SOUND AN ALARM IN THE
 MEZZANINE.
  
 7 ) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-07-01 Cont ID  
Sent By dpalmer Date 2003-07-01 Time 12:23 Rev Time 0.50
Received By dpalmer Date 2003-07-01 Time 12:22 Sent To  
Notes
2003-07-01 00:00:00*********** NOTE ******************
  
 SIGN CIRCUIT REQ`D, UNDER 600-5
 REDLINED ON PLANS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-02-21 Cont ID  
Sent By dpalmer Date 2003-02-21 Time 05:28 Rev Time 0.25
Received By dpalmer Date 2003-02-21 Time 05:28 Sent To  
Notes
2003-02-21 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SHOW/CLARIFY WHAT TYPE
 OF SANDING OR MATERIALS UNDER ART 500
 NEC.
  
 2)NOTE: PLEASE SHOW ANY EXIST OR NEW
 REQ`D EXIT AND/OR EM LTS, PLEASE ALSO
 SEE 700-12E FOR CIRCUITING.
  
 3)NOTE: TWO SPACE ARE SHOWN ON PANEL
 SCHEDULE W/ 2P 50A BRKRS? SPACES ARE
 BLANK, PLEASE CLARIFY.
  
 4)NOTE: PLEASE SEE 600-5 FOR REQ`D
 SIGN CIRCUIT.
  
 5)NOTE: PLEASE SHOW LOAD CALCULATION OF
 EXSITING AND NEW PER 220-3,220-10,220-11
 220-13 AND PLEASE SHOW ALL CONTINUOUS
 LOADS AT 125%. 230-42 215-3 ECT.
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWERS THAT MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-07-08 Cont ID  
Sent By mcarsill Date 2003-07-08 Time 12:33 Rev Time 0.00
Received By mcarsill Date 2003-07-08 Time 12:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-02-21 Cont ID  
Sent By mcarsill Date 2003-02-21 Time 11:12 Rev Time 0.00
Received By mcarsill Date 2003-02-21 Time 11:12 Sent To  
Notes
2003-02-21 00:00:001) NO EMERGENCY LIGHTS OR EXIT SIGNS
 SHOWN ON THE PLANS.
  
 2) NO INFORMATION PROVIDED CONCERNING
 FIRE EXTINGUISHERS.
  
 3) PLEASE INDICATE SIZES OF EXISTING
 DOORS.
  
 4) HOW MANY EMPLOYEE'S WILL BE WORKING
 IN THE TENANT SPACE.
  
 5) TEN INCH TREADS SHOWN ON STAIR. A
 MINIMUM OF AT LEAST ELEVEN INCH TREADS
 ARE REQUIRED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-26 Cont ID  
Sent By shernand Date 2003-06-26 Time 13:02 Rev Time 0.00
Received By shernand Date 2003-06-26 Time 13:02 Sent To  
Notes
2003-06-26 00:00:00COMM BOARD #23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-18 Cont ID  
Sent By btrobaug Date 2003-02-18 Time 17:13 Rev Time 0.00
Received By btrobaug Date 2003-02-13 Time 17:13 Sent To  
Notes
2003-02-18 00:00:00COM BOARD #4./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-07-10 Cont ID  
Sent By rbrown Date 2003-07-10 Time 10:06 Rev Time 0.00
Received By rbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-07-10 Cont ID  
Sent By rbrown Date 2003-07-10 Time 10:06 Rev Time 0.00
Received By rbrown Date   Time   Sent To  
Notes
***NONE***