Plan Review Details - Permit 03020961
Plan Review Stops For Permit 03020961
Review Stop B BUILDING (STRUCTURAL)
Rev No 100 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 99 Status P Date 2004-06-15 Cont ID  
Sent By pkrauss Date 2004-10-25 Time 14:07 Rev Time 0.00
Received By rbrown Date 2004-06-15 Time 15:33 Sent To  
Notes
2004-06-15 00:00:00STRUCTURAL SUBMITTAL ON 6/8/04 FOR
 POUR 2, 12TH FLOOR SLAB POUR LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 98 Status P Date 2004-06-15 Cont ID  
Sent By rbrown Date 2004-06-15 Time 15:11 Rev Time 0.00
Received By rbrown Date 2004-06-15 Time 15:11 Sent To  
Notes
2004-06-15 00:00:00STRUCTURAL SUBMITTAL ON 6/8/04 FOR
 ONM&J LETTER DATED 5/27/04 ON POST-
 TENSION CABLES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 97 Status P Date 2004-06-15 Cont ID  
Sent By rbrown Date 2004-06-15 Time 15:09 Rev Time 0.00
Received By rbrown Date 2004-06-15 Time 15:09 Sent To  
Notes
2004-06-15 00:00:00STRUCTURAL SUBMITTAL ON 6/8/04 FOR
 ONM&J LETTER DATED 5/28/04 ON POST-
 TENSION CABLES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 96 Status P Date 2004-06-15 Cont ID  
Sent By rbrown Date 2004-06-15 Time 15:06 Rev Time 0.00
Received By rbrown Date 2004-06-15 Time 15:06 Sent To  
Notes
2004-06-15 00:00:00STRUCTURAL SUBMITTAL ON 6/8/04 FOR
 ONM&J LETTER DATED 6/7/04 ON POST-
 TENSION CABLES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 95 Status P Date 2004-06-15 Cont ID  
Sent By rbrown Date 2004-06-15 Time 15:01 Rev Time 0.00
Received By rbrown Date 2004-06-15 Time 15:01 Sent To  
Notes
2004-06-15 00:00:00STRUCTURAL SUBMITTAL ON 6/7/04 FOR
 2ND FLOOR WEST PARKING GARAGE SLAB POUR
 LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 94 Status P Date 2004-06-04 Cont ID  
Sent By mjacobs Date 2004-06-14 Time 14:21 Rev Time 0.00
Received By rbrown Date 2004-06-04 Time 14:12 Sent To  
Notes
2004-06-04 00:00:00STRUCTURAL SUBMITTAL ON 6/1/04 FOR
 POUR 1, 12TH FLOOR SLAB POUR LETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 93 Status P Date 2004-06-04 Cont ID  
Sent By rbrown Date 2004-06-04 Time 14:10 Rev Time 0.00
Received By rbrown Date 2004-06-04 Time 14:10 Sent To  
Notes
2004-06-04 00:00:00STRUCTURAL SUBMITTAL ON 5/26/04 FOR
 POUR 2, 11TH FLOOR SLAB POUR LETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 92 Status P Date 2004-06-04 Cont ID  
Sent By rbrown Date 2004-06-04 Time 14:07 Rev Time 0.00
Received By rbrown Date 2004-06-04 Time 14:07 Sent To  
Notes
2004-06-04 00:00:00STRUCTURAL SUBMITTAL ON 5/26/04 FOR
 ONM&J LETTER DATED 5/24/04 ON POST-
 TENSION CABLE ELONGATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 91 Status P Date 2004-06-04 Cont ID  
Sent By rbrown Date 2004-06-04 Time 10:56 Rev Time 0.00
Received By rbrown Date 2004-06-04 Time 10:56 Sent To  
Notes
2004-06-04 00:00:00STRUCTURAL SUBMITTAL ON 6/2/04 FOR CECO
 CONCRETE CONSTRUCTION LLC LEVEL 2, 3 & 4
 (WEST) SHORING PLAN SHEET S-2W.

Review Stop B BUILDING (STRUCTURAL)
Rev No 90 Status P Date 2004-05-27 Cont ID  
Sent By csiegber Date 2004-06-03 Time 08:19 Rev Time 0.00
Received By rbrown Date 2004-05-27 Time 09:51 Sent To  
Notes
2004-05-27 00:00:00STRUCTURAL SUBMITTAL ON 5/24/04 FOR
 ONM&J LETTER DATED 5/15/04 ON POST-
 TENSION CABLES FOR POUR 1, 10TH FLR SLAB

Review Stop B BUILDING (STRUCTURAL)
Rev No 89 Status P Date 2004-05-27 Cont ID  
Sent By rbrown Date 2004-05-27 Time 09:47 Rev Time 0.00
Received By rbrown Date 2004-05-27 Time 09:47 Sent To  
Notes
2004-05-27 00:00:00STRUCTURAL SUBMITTAL ON 5/24/04 FOR
 ONM&J LETTER DATED 5/20/04 ON POST-
 TENSION CABLES FOR POUR 2, 10TH FLR SLAB

Review Stop B BUILDING (STRUCTURAL)
Rev No 88 Status P Date 2004-05-27 Cont ID  
Sent By rbrown Date 2004-05-27 Time 09:44 Rev Time 0.00
Received By rbrown Date 2004-05-27 Time 09:44 Sent To  
Notes
2004-05-27 00:00:00STRUCTURAL SUBMITTAL ON 5/24/04 FOR
 ONM&J LETTER DATED 5/11/04 ON POST-
 TENSION CABLES FOR POUR 2, 9TH FLR SLAB

Review Stop B BUILDING (STRUCTURAL)
Rev No 87 Status P Date 2004-05-27 Cont ID  
Sent By rbrown Date 2004-05-27 Time 09:41 Rev Time 0.00
Received By rbrown Date 2004-05-27 Time 09:41 Sent To  
Notes
2004-05-27 00:00:00STRUCTURAL SUBMITTAL ON 5/24/04 FOR
 ONM&J LETTER DATED 5/5/04 ON POST
 TENSION CABLES FOR POUR 1, 9TH FLR SLAB

Review Stop B BUILDING (STRUCTURAL)
Rev No 86 Status P Date 2004-05-27 Cont ID  
Sent By rbrown Date 2004-05-27 Time 08:20 Rev Time 0.00
Received By rbrown Date 2004-05-27 Time 08:20 Sent To  
Notes
2004-05-27 00:00:00STRUCTURAL SUBMITTAL ON 5/24/04 FOR
 CECO CONCRETE CONSTRUCTION L.L.C. ROOF
 LEVEL SHORING PLAN S-8.

Review Stop B BUILDING (STRUCTURAL)
Rev No 85 Status P Date 2004-05-24 Cont ID  
Sent By alange Date 2004-05-26 Time 10:03 Rev Time 0.00
Received By rbrown Date 2004-05-24 Time 11:20 Sent To  
Notes
2004-05-24 00:00:00STRUCTURAL SUBMITTAL ON 5/21/04 FOR
 POUR 1, 11TH FLOOR SLAB POUR LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 84 Status P Date 2004-05-27 Cont ID  
Sent By rbrown Date 2004-05-24 Time 09:16 Rev Time 0.00
Received By rbrown Date 2004-05-24 Time 09:16 Sent To  
Notes
2004-05-27 00:00:00O.K.
 SHEETS RE-SIGNED BY TOLLIVER FRAZIER P.E
 AS REQUIRED.
2004-05-24 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 STRUCTURAL SUBMITTAL ON 5/20/04 FOR
 ONM&J SKETCHES SSK77 TO SSK82.
  
 61G15-23.002FL. ADMIN. CODE.THE
 SUBMITTED COPIES OF THE ABOVE SHEETS ALL
 HAVE PHOTOCOPIED SIGNATURES.RE-SUBMIT
 THE SHEETS WITH THE WET SIGNATURE OF
 TOLLIVER FRAZIER, P.E. AS THE ENGINEER
 OF RECORD. (471.025 F.S.)

Review Stop B BUILDING (STRUCTURAL)
Rev No 83 Status P Date 2004-05-20 Cont ID  
Sent By csiegber Date 2004-05-21 Time 08:46 Rev Time 0.00
Received By rbrown Date 2004-05-20 Time 10:08 Sent To  
Notes
2004-05-20 00:00:00STRUCTURAL SUBMITTAL ON 5/17/04 FOR
 POUR #2, 10TH FLOOR SLAB POUR LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 82 Status P Date 2004-05-20 Cont ID  
Sent By rbrown Date 2004-05-20 Time 10:05 Rev Time 0.00
Received By rbrown Date 2004-05-20 Time 10:05 Sent To  
Notes
2004-05-20 00:00:00STRUCTURAL SUBMITTAL ON 5/12/04 FOR
 POUR 1, 10TH FLOOR SLAB POUR LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 81 Status P Date 2004-05-07 Cont ID  
Sent By csiegber Date 2004-05-17 Time 11:12 Rev Time 0.00
Received By rbrown Date 2004-05-07 Time 09:44 Sent To  
Notes
2004-05-07 00:00:00STRUCTURAL SUBMITTAL ON 5/5/04 FOR
 POUR 2, 9TH FLOOR EAST/WEST POUR LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 80 Status P Date 2004-05-07 Cont ID  
Sent By rbrown Date 2004-05-07 Time 09:43 Rev Time 0.00
Received By rbrown Date 2004-05-07 Time 09:43 Sent To  
Notes
2004-05-07 00:00:00STRUCTURAL SUBMITTAL ON 4/29/04 FOR
 ONM&J LETTER, DATED 4/22/04,
 RE: POUR 1 - 8TH FLOOR POST-TENSION SLAB

Review Stop B BUILDING (STRUCTURAL)
Rev No 79 Status P Date 2004-05-07 Cont ID  
Sent By rbrown Date 2004-05-07 Time 09:39 Rev Time 0.00
Received By rbrown Date 2004-05-07 Time 09:39 Sent To  
Notes
2004-05-07 00:00:00STRUCTURAL SUBMITTAL ON 4/29/04 FOR
 ONM&J LETTER, DATED 4/27/04,
 RE: 5TH FLOOR EASTERN POOL SLOPING DECK

Review Stop B BUILDING (STRUCTURAL)
Rev No 78 Status P Date 2004-05-07 Cont ID  
Sent By rbrown Date 2004-05-07 Time 09:37 Rev Time 0.00
Received By rbrown Date 2004-05-07 Time 09:37 Sent To  
Notes
2004-05-07 00:00:00STRUCTURAL SUBMITTAL ON 4/29/04 FOR
 ONM&J LETTER, DATED 4/29/04,
 RE: POUR 2 - 8TH FLOOR POST-TENSION SLAB

Review Stop B BUILDING (STRUCTURAL)
Rev No 77 Status P Date 2004-05-07 Cont ID  
Sent By rbrown Date 2004-05-07 Time 09:34 Rev Time 0.00
Received By rbrown Date 2004-05-07 Time 09:34 Sent To  
Notes
2004-05-07 00:00:00STRUCTURAL SUBMITTAL ON 4/29/04 FOR
 ONM&J LETTER, DATED 4/19/04,
 RE: POUR 2 - 7TH FLOOR POST-TENSION SLAB

Review Stop B BUILDING (STRUCTURAL)
Rev No 76 Status P Date 2004-05-07 Cont ID  
Sent By rbrown Date 2004-05-07 Time 09:31 Rev Time 0.00
Received By rbrown Date 2004-05-07 Time 09:31 Sent To  
Notes
2004-05-07 00:00:00STRUCTURAL SUBMITTAL ON 4/29/04 FOR
 POUR 1, 9TH FLOOR POUR LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 75 Status P Date 2004-04-26 Cont ID  
Sent By csiegber Date 2004-05-05 Time 16:40 Rev Time 0.00
Received By rbrown Date 2004-04-26 Time 13:55 Sent To  
Notes
2004-04-26 00:00:00STRUCTURAL SUBMITTAL ON 4/26/04 FOR
 POUR 2, 8TH FLOOR POUR LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 74 Status P Date 2004-04-23 Cont ID  
Sent By csiegber Date 2004-04-26 Time 13:11 Rev Time 0.00
Received By rbrown Date 2004-04-23 Time 15:45 Sent To  
Notes
2004-04-23 00:00:00STRUCTURAL SUBMITTAL ON 4/12/04 FOR
 SKYLINE STEEL METAL PAN STAIR SHOP
 DRAWINGS - STAIR #1 AND STAIR #2

Review Stop B BUILDING (STRUCTURAL)
Rev No 73 Status P Date 2004-04-23 Cont ID  
Sent By rbrown Date 2004-04-23 Time 14:24 Rev Time 0.00
Received By rbrown Date 2004-04-23 Time 14:24 Sent To  
Notes
2004-04-23 00:00:00STRUCTURAL SUBMITTAL ON 4/20/04 FOR
 PTE STRAND CO 5TH FLOOR POST-TENSION
 SLAB PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 72 Status P Date 2004-04-23 Cont ID  
Sent By rbrown Date 2004-04-23 Time 13:48 Rev Time 0.00
Received By rbrown Date 2004-04-23 Time 13:48 Sent To  
Notes
2004-04-23 00:00:00STRUCTURAL SUBMITTAL ON 4/20/04 FOR
 ONM&J SHEETS SSK 75A, 75B AND 75C

Review Stop B BUILDING (STRUCTURAL)
Rev No 71 Status P Date 2004-04-23 Cont ID  
Sent By rbrown Date 2004-04-23 Time 12:03 Rev Time 0.00
Received By rbrown Date 2004-04-23 Time 12:03 Sent To  
Notes
2004-04-23 00:00:00STRUCTURAL SUBMITTAL ON 4/20/04 FOR
 ONM&J LETTER, DATED 4/14/04,
 RE: POUR 1 - 7TH FLOOR POST-TENSION SLAB

Review Stop B BUILDING (STRUCTURAL)
Rev No 70 Status P Date 2004-04-23 Cont ID  
Sent By rbrown Date 2004-04-23 Time 11:40 Rev Time 0.00
Received By rbrown Date 2004-04-23 Time 11:40 Sent To  
Notes
2004-04-23 00:00:00STRUCTURAL SUBMITTAL ON 4/22/04 FOR
 5TH FLOOR LOWER EAST POOL POUR LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 69 Status P Date 2004-04-23 Cont ID  
Sent By rbrown Date 2004-04-23 Time 11:29 Rev Time 0.00
Received By rbrown Date 2004-04-23 Time 11:29 Sent To  
Notes
2004-04-23 00:00:00STRUCTURAL SUBMITTAL ON 4/20/04 FOR
 POUR 1, 8TH FLOOR POUR LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 68 Status P Date 2004-04-15 Cont ID  
Sent By alange Date 2004-04-22 Time 12:01 Rev Time 0.50
Received By shill Date 2004-04-15 Time 13:03 Sent To  
Notes
2004-04-15 00:00:00SHORING & RESHORING LETTERS POUR 2,LVL 7
 PREPARED BY WEITZ, ONM&J (JEFF BALLARD,
 PE) DATED 4/14/04, CAPRI (OSVALDO
 AREVALO, PE) DATED 4/14/04.

Review Stop B BUILDING (STRUCTURAL)
Rev No 67 Status P Date 2004-04-12 Cont ID  
Sent By csiegber Date 2004-04-14 Time 10:20 Rev Time 0.00
Received By rbrown Date 2004-04-12 Time 13:45 Sent To  
Notes
2004-04-12 00:00:00STRUCTURAL SUBMITTAL ON 4/1/04 FOR PTE
 STRAND CO. INC. 2ND FLOOR WEST AND 3RD
 FLOOR WEST POST-TENSION SLAB PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 66 Status P Date 2004-04-12 Cont ID  
Sent By rbrown Date 2004-04-12 Time 11:13 Rev Time 0.00
Received By rbrown Date 2004-04-12 Time 11:13 Sent To  
Notes
2004-04-12 00:00:00STRUCTURAL SUBMITTAL ON 4/8/04 FOR
 ONM&J LETTER, DATED 3/31/04,
 RE: POUR 1 - 6TH FLOOR POST-TENSION SLAB

Review Stop B BUILDING (STRUCTURAL)
Rev No 65 Status P Date 2004-04-12 Cont ID  
Sent By rbrown Date 2004-04-12 Time 10:21 Rev Time 0.00
Received By rbrown Date 2004-04-12 Time 10:20 Sent To  
Notes
2004-04-12 00:00:00STRUCTURAL SUBMITTAL ON 4/8/04 FOR
 ONM&J LETTER, DATED 4/6/04,
 RE: POUR 2 - 6TH FLOOR POST-TENSION SLAB

Review Stop B BUILDING (STRUCTURAL)
Rev No 64 Status P Date 2004-04-12 Cont ID  
Sent By rbrown Date 2004-04-12 Time 10:05 Rev Time 0.00
Received By rbrown Date 2004-04-12 Time 10:05 Sent To  
Notes
2004-04-12 00:00:00STRUCTURAL SUBMITTAL ON 4/12/04 FOR
 POUR 1, 7TH FLOOR POUR LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 63 Status P Date 2004-04-09 Cont ID  
Sent By rbrown Date 2004-04-09 Time 17:22 Rev Time 0.00
Received By rbrown Date 2004-04-09 Time 17:22 Sent To  
Notes
2004-04-09 00:00:00STRUCTURAL SUBMITTAL ON 4/8/04 FOR ONM&J
 LETTER, DATED 3/17/04, RE: POUR 1 -
 5TH FLOOR POST-TENSION SLAB

Review Stop B BUILDING (STRUCTURAL)
Rev No 62 Status P Date 2004-04-09 Cont ID  
Sent By rbrown Date 2004-04-09 Time 16:59 Rev Time 0.00
Received By rbrown Date 2004-04-09 Time 16:59 Sent To  
Notes
2004-04-09 00:00:00STRUCTURAL SUBMITTAL ON 4/1/04 FOR
 POUR 2, 6TH FLOOR POUR LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 61 Status P Date 2004-04-09 Cont ID  
Sent By rbrown Date 2004-04-09 Time 16:51 Rev Time 0.00
Received By rbrown Date 2004-04-09 Time 16:51 Sent To  
Notes
2004-04-09 00:00:00STRUCTURAL SUBMITTAL ON 4/1/04 FOR CECO
 CONSTRUCTION, 5TH FLOOR SHORING PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 60 Status F Date 2004-04-09 Cont ID  
Sent By rbrown Date 2004-04-09 Time 16:27 Rev Time 0.00
Received By rbrown Date 2004-04-09 Time 16:27 Sent To  
Notes
2004-04-23 00:00:00RESUBMITTED ON 4/20/04 WITH THE REQUIRED
 SIGNATURE.SEE 4/23/04 REVIEW NOTES.
2004-04-09 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 STRUCTURAL REVISION SUBMITTED 4/9/04 FOR
 SKETCH SHEETS SSK 75A, 75B AND 75C.
  
 471.025 F.S.ENGINEER'S SEAL/SIGNATURE.
 THE SUBMITTED COPIES OF THESE SHEETS DO
 NOT BEAR THE ORIGINAL (WET) SIGNATURE OF
 THE ENGINEER.AN ORIGINAL SIGNATURE IS
 REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 59 Status P Date 2004-04-09 Cont ID  
Sent By rbrown Date 2004-04-09 Time 16:25 Rev Time 0.00
Received By rbrown Date 2004-04-09 Time 16:25 Sent To  
Notes
2004-04-09 00:00:00STRUCTURAL REVISION SUBMITTED 4/1/04 FOR
 SKETCH SHEETS SSK 69, 74 AND 75

Review Stop B BUILDING (STRUCTURAL)
Rev No 58 Status P Date 2004-04-07 Cont ID  
Sent By csiegber Date 2004-04-08 Time 14:22 Rev Time 0.00
Received By rbrown Date 2004-04-07 Time 15:07 Sent To  
Notes
2004-04-07 00:00:00SUBMITTAL ON 4/6/04 FOR REVISED CONCRETE
 MIX DESIGN (5000PSI) FOR ELEVATED SLABS,

Review Stop B BUILDING (STRUCTURAL)
Rev No 57 Status P Date 2004-03-25 Cont ID  
Sent By csiegber Date 2004-04-06 Time 08:50 Rev Time 0.00
Received By rbrown Date 2004-03-25 Time 12:14 Sent To  
Notes
2004-03-25 00:00:00STRUCTURAL SUBMITTAL ON 3/22/04 FOR
 PTE STRAND CO 5TH FLR EAST POST-TENSION
 SLAB DRAWING

Review Stop B BUILDING (STRUCTURAL)
Rev No 56 Status P Date 2004-03-25 Cont ID  
Sent By rbrown Date 2004-03-25 Time 11:56 Rev Time 0.00
Received By rbrown Date 2004-03-25 Time 11:56 Sent To  
Notes
2004-03-25 00:00:00STRUCTURAL SUBMITTAL ON 3/15/04 FOR
 ONM&J SKETCHES SSK 70, 71 AND 72

Review Stop B BUILDING (STRUCTURAL)
Rev No 55 Status P Date 2004-03-25 Cont ID  
Sent By rbrown Date 2004-03-25 Time 11:52 Rev Time 0.00
Received By rbrown Date 2004-03-25 Time 11:52 Sent To  
Notes
2004-03-25 00:00:00STRUCTURAL SUBMITTAL ON 3/5/04 FOR
 ONM&J SKETCHES SSK 59-68

Review Stop B BUILDING (STRUCTURAL)
Rev No 54 Status P Date 2004-03-25 Cont ID  
Sent By rbrown Date 2004-03-25 Time 10:07 Rev Time 0.00
Received By rbrown Date 2004-03-25 Time 10:07 Sent To  
Notes
2004-03-25 00:00:00STRUCTURAL SUBMITTAL ON 3/3/04 FOR CECO
 5TH FLOOR SHORING PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 53 Status P Date 2004-03-25 Cont ID  
Sent By rbrown Date 2004-03-25 Time 10:03 Rev Time 0.00
Received By rbrown Date 2004-03-25 Time 10:03 Sent To  
Notes
2004-03-25 00:00:00STRUCTURAL SUBMITTAL ON 3/3/04 FOR CECO
 4TH FLOOR SHORING PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 52 Status F Date 2004-03-25 Cont ID  
Sent By rbrown Date 2004-03-25 Time 09:46 Rev Time 0.00
Received By rbrown Date 2004-03-25 Time 09:46 Sent To  
Notes
2004-03-25 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 STRUCTURAL SUBMITTAL ON 3/3/04 FOR
 PTE STRAND CO 4TH FLOOR POST-TENSION
 SLAB CABLE FIELD ADJUSTMENT LETTER.
  
 THE ENGINEER OF RECORD SHALL REVIEW AND
 STAMP OR PROVIDE A SIGNED AND SEALED
 COVER LETTER MAKING SPECIFIC REFERENCE
 TO THE FIELD ADJUSTMENT LETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 51 Status P Date 2004-03-25 Cont ID  
Sent By rbrown Date 2004-03-25 Time 09:23 Rev Time 0.00
Received By rbrown Date 2004-03-25 Time 13:44 Sent To  
Notes
2004-03-25 00:00:00STRUCTURAL SUBMITTAL ON 3/2/04 FOR
 PTE STRAND CO 5TH FLR EAST POST-TENSION
 SLAB DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 50 Status F Date 2004-03-25 Cont ID  
Sent By rbrown Date 2004-03-25 Time 09:21 Rev Time 0.00
Received By rbrown Date 2004-03-25 Time 09:21 Sent To  
Notes
2004-03-25 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 STRUCTURAL SUBMITTAL ON 3/2/04 FOR
 PTE STRAND CO POST-TENSION SLAB CABLE
 FIELD ADJUSTMENT LETTER.
  
 THE ENGINEER OF RECORD SHALL REVIEW AND
 STAMP OR PROVIDE A SIGNED AND SEALED
 COVER LETTER MAKING SPECIFIC REFERENCE
 TO THE FIELD ADJUSTMENT LETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 49 Status F Date 2004-03-25 Cont ID  
Sent By rbrown Date 2004-03-25 Time 09:12 Rev Time 0.00
Received By rbrown Date 2004-03-25 Time 09:12 Sent To  
Notes
2004-03-25 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 STRUCTURAL SUBMITTAL ON 3/2/04 FOR
 PTE STRAND CO 4TH FLOOR POST-TENSION
 SLAB CABLE FIELD ADJUSTMENT LETTER.
  
 THE ENGINEER OF RECORD SHALL REVIEW AND
 STAMP OR PROVIDE A SIGNED AND SEALED
 COVER LETTER MAKING SPECIFIC REFERENCE
 TO THE FIELD ADJUSTMENT LETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 48 Status P Date 2004-03-24 Cont ID  
Sent By rbrown Date 2004-03-24 Time 18:09 Rev Time 0.00
Received By rbrown Date 2004-03-24 Time 18:09 Sent To  
Notes
2004-03-24 00:00:00STRUCTURAL SUBMITTAL ON 3/18/04 FOR
 POUR 2, 5TH FLOOR POUR LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 47 Status P Date 2004-03-24 Cont ID  
Sent By rbrown Date 2004-03-24 Time 18:07 Rev Time 0.00
Received By rbrown Date 2004-03-24 Time 18:07 Sent To  
Notes
2004-03-24 00:00:00STRUCTURAL SUBMITTAL ON 3/18/04 FOR
 PTE STRAND CO STRESSING OPERATION LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 46 Status P Date 2004-03-24 Cont ID  
Sent By rbrown Date 2004-03-24 Time 18:06 Rev Time 0.00
Received By rbrown Date 2004-03-24 Time 18:04 Sent To  
Notes
2004-03-24 00:00:00STRUCTURAL SUBMITTAL ON MM/DD/YY FOR
 ONM&J POUR 2 & 3, 4TH FLOOR POST-TENSION
 LETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 45 Status P Date 2004-03-24 Cont ID  
Sent By rbrown Date 2004-03-24 Time 18:03 Rev Time 0.00
Received By rbrown Date 2004-03-24 Time 18:03 Sent To  
Notes
2004-03-24 00:00:00STRUCTURAL SUBMITTAL ON 3/9/04 FOR
 ONM&J POUR 1, 4TH FLOOR POST-TENSION
 LETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 44 Status P Date 2004-03-24 Cont ID  
Sent By rbrown Date 2004-03-24 Time 18:02 Rev Time 0.00
Received By rbrown Date 2004-03-24 Time 18:02 Sent To  
Notes
2004-03-24 00:00:00STRUCTURAL SUBMITTAL ON 3/9/04 FOR
 ONM&J POUR 2, 3RD FLOOR POST-TENSION
 LETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 43 Status P Date 2004-03-24 Cont ID  
Sent By rbrown Date 2004-03-24 Time 17:58 Rev Time 0.00
Received By rbrown Date 2004-03-24 Time 17:58 Sent To  
Notes
2004-03-24 00:00:00STRUCTURAL SUBMITTAL ON 3/9/04 FOR
 ONM&J POUR 3, 2ND FLOOR POST-TENSION
 LETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 42 Status P Date 2004-03-24 Cont ID  
Sent By rbrown Date 2004-03-24 Time 17:57 Rev Time 0.00
Received By rbrown Date 2004-03-24 Time 17:57 Sent To  
Notes
2004-03-24 00:00:00STRUCTURAL SUBMITTAL ON 3/4/04 FOR
 POUR 3, 4TH FLOOR EAST POUR LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 41 Status P Date 2004-03-24 Cont ID  
Sent By rbrown Date 2004-03-24 Time 17:44 Rev Time 0.00
Received By rbrown Date 2004-03-24 Time 17:44 Sent To  
Notes
2004-03-24 00:00:00STRUCTURAL SUBMITTAL ON 3/1/04 FOR
 POUR 2, 4TH FLOOR EAST POUR LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 40 Status P Date 2004-03-24 Cont ID  
Sent By rbrown Date 2004-03-24 Time 15:34 Rev Time 0.00
Received By rbrown Date 2004-03-24 Time 15:34 Sent To  
Notes
2004-03-24 00:00:00STRUCTURAL SUBMITTAL ON 3/18/03 FOR PTE
 STRAND CO. 6TH TO 17TH FLR POST-TENSION
 SHOP DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 39 Status P Date 2004-03-24 Cont ID  
Sent By rbrown Date 2004-03-24 Time 15:32 Rev Time 0.00
Received By rbrown Date 2004-03-24 Time 15:32 Sent To  
Notes
2004-03-24 00:00:00STRUCTURAL SUBMITTAL ON 3/15/03 FOR CECO
 6TH LEVEL SHORING DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 38 Status P Date 2004-03-09 Cont ID  
Sent By csiegber Date 2004-03-23 Time 08:57 Rev Time 0.00
Received By rbrown Date 2004-03-09 Time 15:57 Sent To  
Notes
2004-03-09 00:00:00STRUCTURAL SUBMITTAL ON 3/9/04 FOR PTE
 STRAND AND CO. 5TH FLOOR POST-TENSION
 SLAB PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 37 Status P Date 2004-02-27 Cont ID  
Sent By csiegber Date 2004-03-05 Time 14:43 Rev Time 0.00
Received By rbrown Date 2004-02-27 Time 16:38 Sent To  
Notes
2004-02-27 00:00:00STRUCTURAL REVISION SUBMITTED 2/10/04
 FOR ONM&J REVISED PLAN SHEETS

Review Stop B BUILDING (STRUCTURAL)
Rev No 36 Status P Date 2004-02-27 Cont ID  
Sent By rbrown Date 2004-02-27 Time 13:54 Rev Time 0.00
Received By rbrown Date 2004-02-27 Time 13:54 Sent To  
Notes
2004-02-27 00:00:00STRUCTURAL REVISION SUBMITTED 2/17/04
 FOR ONM&J SHEETS SSK-53 TO SSK-57

Review Stop B BUILDING (STRUCTURAL)
Rev No 35 Status P Date 2004-02-27 Cont ID  
Sent By rbrown Date 2004-02-27 Time 13:25 Rev Time 0.00
Received By rbrown Date 2004-02-27 Time 13:25 Sent To  
Notes
2004-02-27 00:00:00STRUCTURAL SUBMITTAL ON 2/5/04 FOR PTE
 STRAND CO. 4TH FLOOR POST-TENSION SLAB
 PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 34 Status P Date 2004-02-27 Cont ID  
Sent By rbrown Date 2004-02-27 Time 13:20 Rev Time 0.00
Received By rbrown Date 2004-02-27 Time 13:20 Sent To  
Notes
2004-02-27 00:00:00STRUCTURAL SUBMITTAL ON 2/5/04 FOR
 ONM&J LETTER DATED 1/18/04 ON AUGER-
 CAST PILES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 33 Status P Date 2004-02-23 Cont ID  
Sent By rbrown Date 2004-02-23 Time 14:57 Rev Time 0.00
Received By rbrown Date 2004-02-23 Time 14:56 Sent To  
Notes
2004-02-23 00:00:00STRUCTURAL SUBMITTAL ON 2-23-04 FOR
 LEVEL 2, 3, AND 4 RESHORING AND FORMWORK

Review Stop B BUILDING (STRUCTURAL)
Rev No 32 Status P Date 2004-02-23 Cont ID  
Sent By rbrown Date 2004-02-23 Time 11:54 Rev Time 0.00
Received By rbrown Date 2004-02-23 Time 11:54 Sent To  
Notes
2004-02-23 00:00:00STRUCTURAL SUBMITTAL ON 2/20/04 FOR
 FOURTH FLOOR POST-TENSION SHOP DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 31 Status P Date 2004-02-10 Cont ID  
Sent By csiegber Date 2004-02-20 Time 12:13 Rev Time 0.00
Received By rbrown Date 2004-02-10 Time 13:44 Sent To  
Notes
2004-02-10 00:00:00STRUCTURAL SUBMITTAL ON 2/10/04 FOR
 ONM&J SKETCHES SSK44-SSK52.

Review Stop B BUILDING (STRUCTURAL)
Rev No 30 Status P Date 2004-02-10 Cont ID  
Sent By rbrown Date 2004-02-10 Time 13:43 Rev Time 0.00
Received By rbrown Date 2004-02-10 Time 13:43 Sent To  
Notes
2004-02-10 00:00:00STRUCTURAL SUBMITTAL ON 2/6/04 FOR PTE
 THIRD FLOOR POST-TENSION SHOP DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 29 Status P Date 2004-01-29 Cont ID  
Sent By csiegber Date 2004-02-06 Time 09:50 Rev Time 0.00
Received By rbrown Date 2004-01-29 Time 11:55 Sent To  
Notes
2004-01-29 00:00:00STRUCTURAL SUBMITTAL ON 1-28-04 FOR
 LEVEL 3 FORMWORK/SHORING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 28 Status F Date 2004-01-29 Cont ID  
Sent By rbrown Date 2004-01-29 Time 11:38 Rev Time 0.00
Received By rbrown Date 2004-01-29 Time 11:38 Sent To  
Notes
2004-01-29 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 SUBMITTAL 1/21/04 FOR POST TENSION SLAB
 PLAN AND CALCS
  
 1) NO ONM&J LETTER WAS ATTACHED TO PLAN
 SHEET 7R.NOTE ALSO, THE ONM&J REVIEW
 LETTERS ATTACHED TO PLAN SHEETS PT7 AND
 PT8 DO NOT HAVE AN ORIGINAL SIGNATURE,
 ARE NOT SEALED AND DO NOT MAKE SPECIFIC
 REFERENCE TO THE PLAN SHEET(S).
 ALTERNATIVELY, SHOP DRAWINGS SHALL BE
 REVIEWED AND STAMPED BY THE ENGINEER OF
 RECORD BEFORE SUBMITTAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 27 Status P Date 2004-01-29 Cont ID  
Sent By rbrown Date 2004-01-29 Time 11:36 Rev Time 0.00
Received By rbrown Date 2004-01-29 Time 11:36 Sent To  
Notes
2004-01-29 00:00:00STRUCTURAL SUBMITTAL ON 1/21/04 FOR
 ONM&J LETTER DATED 1/7/04 ON AUGER-CAST
 PILES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 26 Status P Date 2004-01-29 Cont ID  
Sent By rbrown Date 2004-01-29 Time 11:35 Rev Time 0.00
Received By rbrown Date 2004-01-29 Time 11:35 Sent To  
Notes
2004-01-29 00:00:00STRUCTURAL SUBMITTAL ON 1/21/04 FOR
 ONM&J LETTER DATED 12/23/03 ON AUGER-
 CAST PILES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 25 Status P Date 2004-01-29 Cont ID  
Sent By rbrown Date 2004-01-29 Time 11:27 Rev Time 0.00
Received By rbrown Date 2004-01-29 Time 11:27 Sent To  
Notes
2004-01-29 00:00:00STRUCTURAL SUBMITTAL ON 1/21/2004 FOR
 ONM&J LETTER DATED 12/17/03 ON AUGER-
 CAST PILES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 24 Status P Date 2004-01-13 Cont ID  
Sent By csiegber Date 2004-01-28 Time 16:41 Rev Time 0.00
Received By rbrown Date 2004-01-13 Time 13:43 Sent To  
Notes
2004-01-13 00:00:00STRUCTURAL SUBMITTAL ON 1/9/04 FOR PTE
 SECOND FLOOR POST-TENSION SHOP DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 23 Status P Date 2004-01-06 Cont ID  
Sent By csiegber Date 2004-01-12 Time 10:24 Rev Time 0.00
Received By rbrown Date 2004-01-06 Time 13:53 Sent To  
Notes
2004-01-06 00:00:00STRUCTURAL SUBMITTAL ON 12/30/03 FOR
 ONM&J LETTER DATED 12/2/03 ABOUT AUGER-
 CAST PILE AS-BUILT LOCATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 22 Status P Date 2004-01-06 Cont ID  
Sent By rbrown Date 2004-01-06 Time 13:49 Rev Time 0.00
Received By rbrown Date 2004-01-06 Time 13:49 Sent To  
Notes
2004-01-06 00:00:00STRUCTURAL SUBMITTAL ON 12/30/03 FOR
 CECO CONCRETE CONSTRUCT, LLC LETTER
 DATED 12/29/03 ABOUT SHORING FOR POUR 1
 OF LEVEL 2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 21 Status P Date 2004-01-06 Cont ID  
Sent By rbrown Date 2004-01-06 Time 13:46 Rev Time 0.00
Received By rbrown Date 2004-01-06 Time 13:46 Sent To  
Notes
2004-01-06 00:00:00STRUCTURAL SUBMITTAL ON 12/12/03 FOR
 ONM&J LETTER DATED 11/26/03 ABOUT AUGER-
 CAST PILE AS-BUILT LOCATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 20 Status P Date 2004-01-06 Cont ID  
Sent By rbrown Date 2004-01-06 Time 13:39 Rev Time 0.00
Received By rbrown Date 2004-01-06 Time 13:39 Sent To  
Notes
2004-01-06 00:00:00STRUCTURAL SUBMITTAL ON 12/12/03 FOR
 ONM&J LETTER DATED 12/2/03 ABOUT AUGER-
 CAST PILE AS-BUILT LOCATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status P Date 2004-01-08 Cont ID  
Sent By rbrown Date 2004-01-06 Time 11:51 Rev Time 0.00
Received By rbrown Date 2004-01-06 Time 11:51 Sent To  
Notes
2004-01-08 00:00:00******PASSED*******
 REQUIRED ENGINEER'S DETAILS ADDED TO
 PLAN SHEETS.
2004-01-06 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 SUBMITTAL ON 12/12/03 FOR THIRD FLOOR -
 EAST POST-TENSIONED SLAB PLANS.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) 61G15-23.002(2)FL. ADMIN. CODE.
 SHEET PT-1 HAS BEEN STAMPED WITH THE
 NAME, ADDRESS AND LICENSE NUMBER OF
 MIAN ABDUL HAMID, P.E. BUT ALL SHEETS
 ARE ACTUALLY SIGNED AND SEALED BY SANJAY
 ROY P.E.ALL SHEETS SHOULD INCLUDE
 SANJAY ROY'S PRINTED NAME AND LICENSE
 NUMBER, AND EITHER HIS ADDRESS OR THE
 CERTIFICATE OF AUTHORIZATION NUMBER FOR
 PTE STRAND CO., INC.ALTERNATIVELY ALL
 SHEETS SHALL BE STAMPED WITH MIAN ABDUL
 HAMID'S DETAILS (LIKE SHEET PT-1) AND
 SIGNED AND SEALED BY HIM.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status P Date 2003-12-17 Cont ID  
Sent By csiegber Date 2003-12-30 Time 11:38 Rev Time 0.00
Received By rbrown Date 2003-12-17 Time 16:53 Sent To  
Notes
2003-12-17 00:00:00SUBMITTAL ON 12/17/03 FOR LEVEL 2
 FORMWORK PLAN

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status P Date 2003-12-08 Cont ID  
Sent By rbrown Date 2003-12-08 Time 08:57 Rev Time 0.00
Received By rbrown Date 2003-12-08 Time 08:57 Sent To  
Notes
2003-12-08 00:00:00STRUCTURAL SUBMITTAL 12/5/03 FOR
 SKETCHES SSK22-SSK43

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status P Date 2003-12-02 Cont ID  
Sent By csiegber Date 2003-12-05 Time 09:50 Rev Time 0.00
Received By rbrown Date 2003-12-02 Time 11:27 Sent To  
Notes
2003-12-02 00:00:00STRUCTURAL SUBMITTAL ON 11/20/03 FOR
 ONM&J LETTER ON AUGERCAST PILE LOCATIONS
 AND LOG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status P Date 2003-11-20 Cont ID  
Sent By rbrown Date 2003-11-20 Time 09:47 Rev Time 0.00
Received By rbrown Date 2003-11-20 Time 09:47 Sent To  
Notes
2003-11-20 00:00:00STRUCTURAL SUBMITTAL ON 11/13/03 FOR
 ONM&J LETTER DATED 11/10/03 ABOUT PILE
 CAP POURS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status F Date 2003-11-20 Cont ID  
Sent By rbrown Date 2003-11-20 Time 09:35 Rev Time 0.00
Received By rbrown Date 2003-11-20 Time 09:35 Sent To  
Notes
2003-11-20 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 STRUCTURAL SUBMITTAL ON 11/18/03 FOR
 ARDAMAN & ASSOCIATES LETTER, DATED
 10/30/03, ABOUT PILE CAP B5-16.
  
 1) THE SUBMITTED COPIES OF THE LETTER
 DO NOT HAVE THE RAISED SEAL OR WET
 SIGNATURE OF THE ENGINEER (PETER G.
 ANDERSON, P.E.).SIGN AND SEAL BEFORE
 RE-SUBMITTING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status P Date 2003-11-19 Cont ID  
Sent By rbrown Date 2003-11-19 Time 16:59 Rev Time 0.00
Received By rbrown Date 2003-11-19 Time 16:59 Sent To  
Notes
2003-11-19 00:00:00STRUCTURAL SUBMITTAL ON 11/6/03 FOR
 SKETCHES SSK8 TO SSK20

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2003-10-21 Cont ID  
Sent By csiegber Date 2003-11-18 Time 10:06 Rev Time 0.00
Received By rbrown Date 2003-10-21 Time 08:52 Sent To  
Notes
2003-10-21 00:00:00STRUCTURAL SUBMITTAL 10/16/03 FOR
 SKETCHES SSK-1 TO SSK-7

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2003-10-21 Cont ID  
Sent By rbrown Date 2003-10-21 Time 08:47 Rev Time 0.00
Received By rbrown Date 2003-10-21 Time 08:47 Sent To  
Notes
2003-10-21 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 SUBMITTAL 10/14/03 FOR 1ST LIFT COLUMN
 REINFORCEMENT.
  
 --PROVISO--
 COMPLY WITH THE ENGINEER OF RECORD'S
 COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2003-10-21 Cont ID  
Sent By rbrown Date 2003-10-21 Time 08:40 Rev Time 0.00
Received By rbrown Date 2003-10-21 Time 08:40 Sent To  
Notes
2003-10-21 00:00:00SUBMITTAL 10/14/03 FOR MASONRY UNIT
 GROUT AND LINTELS

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2003-10-21 Cont ID  
Sent By rbrown Date 2003-10-21 Time 08:33 Rev Time 0.00
Received By rbrown Date 2003-10-21 Time 08:33 Sent To  
Notes
2003-10-21 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 SUBMITTAL 10/14/03 FOR PILE CAP, GRADE
 BEAM AND COLUMN DOWEL REINFORCEMENT SHOP
 DRAWINGS.
  
 --PROVISO--
 COMPLY WITH THE ENGINEER OF RECORD'S
 COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2003-10-20 Cont ID  
Sent By rbrown Date 2003-10-20 Time 16:35 Rev Time 0.00
Received By rbrown Date 2003-10-20 Time 16:35 Sent To  
Notes
2003-10-20 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 SUBMITTAL 10/14/03 FOR SHEAR WALL AND
 CONC. WALL DOWEL REBAR SHOP DRAWINGS.
  
 --PROVISO--
 COMPLY WITH THE ENGINEER OF RECORD'S
 COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2003-10-20 Cont ID  
Sent By rbrown Date 2003-10-20 Time 16:15 Rev Time 0.00
Received By rbrown Date 2003-10-20 Time 16:14 Sent To  
Notes
2003-10-20 00:00:00SUBMITTAL 10/14/03 FOR AUGER PILE GROUT
 MIX DESIGN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2003-11-20 Cont ID  
Sent By csiegber Date 2003-10-16 Time 16:38 Rev Time 0.00
Received By rbrown Date 2003-10-10 Time 10:45 Sent To  
Notes
2003-11-20 00:00:00PASSED AS PER PREVIOUS NOTE
2003-10-21 00:00:00CAN ACCEPT A SIGNED AND SEALED LETTER
 FROM THE ENGINEER OF RECORD.
2003-10-10 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 SUBMITTAL 10/8/03 FOR POST TENSION SLAB
 SHOP DRAWINGS:
  
 1) ALL STRUCTURAL SHOP DRAWINGS SHALL BE
 REVIEWED AND STAMPED BY THE ENGINEER OF
 RECORD BEFORE SUBMITTAL.THIS IS STILL
 REQUIRED EVENTHOUGH THE ENGINEER OF
 RECORD MAY HAVE ATTACHED A COMMENT/
 REVIEW LETTER TO THE SHOP DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2003-10-09 Cont ID  
Sent By rbrown Date 2003-10-09 Time 19:52 Rev Time 0.00
Received By rbrown Date 2003-10-09 Time 19:52 Sent To  
Notes
2003-10-09 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 SUBMITTAL ON 10/8/03 FOR CONCRETE MIX
 DESIGN.
  
 --PROVISO--
 THE RINKER MATERIALS COVERING LETTER AND
 EACH MIX DESIGN LETTER ALL REFER TO
 ACI 318-99.FLORIDA BUILDING CODE 2001
 (WITH 2003 REVISIONS) REFERS TO
 ACI 318-02.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-09-23 Cont ID  
Sent By csiegber Date 2003-10-08 Time 11:54 Rev Time 0.00
Received By rbrown Date 2003-09-23 Time 09:23 Sent To  
Notes
2003-09-23 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 9/23/03 SUBMITTAL FOR AUGERCAST PILING.
  
 --PROVISO--
 FBC 1903.8.2SHEET 1 OF CONTINENTAL
 FLORIDA MATERIALS INC REFERS TO
 ACI 318-99.FLORIDA BUILDING CODE 2001
 (WITH 2003 REVISIONS) REFERENCES
 ACI 318-02.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-08-04 Cont ID  
Sent By csiegber Date 2003-09-22 Time 15:24 Rev Time 0.00
Received By rbrown Date 2003-07-24 Time 09:05 Sent To  
Notes
2003-07-24 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 --PROVISO--
 DRAWING SHEET 1 OF THE SUBMITTED BESAM
 ALUM SLIDING GLASS DOOR PRODUCT APPROVAL
 NOA# 00-0728.01 SHOWS A MAXIMUM ROUGH
 OPENING HEIGHT OF 92-1/4".THIS IS LESS
 THAN 8'-0" DOOR HEIGHT STATED FOR DOOR
 L1-02B ON DOOR SCHEDULE SHEET A8.1.01A.
 THE DIMENSIONS OF THE PROPOSED DOOR
 SHALL BE WITHIN THE SCOPE OF THE
 SUBMITTED PRODUCT APPROVAL.
  
  
 NOTE:
 CONDOMINIUM V APARTMENTS.IF THE
 DWELLING UNITS ARE TO BE SOLD AS
 CONDOMINIUMS, NO CERTIFICATE OF
 OCCUPANCY CAN BE ISSUED UNTIL A
 'DECLARATION OF CONDOMINIUM' HAS BEEN
 SUBMITTED TO THE STATE FOR APPROVAL, AND
 THEN RECORDED WITH THE CLERK OF THE
 COUNTY COURT.A RECORDED COPY SHALL BE
 SUBMITTED TO THE CITY FOR RECORDS,
 ADDRESSING PURPOSES, AND NOTIFICATION OF
 PALM BEACH COUNTY PROPERTY APPRAISER'S
 OFFICE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-05-14 Cont ID  
Sent By rbrown Date 2003-05-14 Time 13:45 Rev Time 0.00
Received By rbrown Date 2003-04-16 Time 13:57 Sent To  
Notes
2003-04-16 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 3/7/03:
  
 8) FBC* 104.2.1DOOR SCHEDULE.THE
 SUBMITTAL OF LEGIBLE COPIES IS NOTED.
 DOOR SCHEDULE SHEET, A8.1.01A:
 -TENANT DOOR 6B1-1 IS NOT SHOWN AS FIRE-
 RATED. SHOULD BE 20 MIN. AMEND SCHEDULE
 DOOR SCHEDULE SHEET, A8.1.01B:
 -STORAGE ROOM DOOR L1-17A IS NOT SHOWN
 RATED. SHOULD BE 1-1/2 HR. AMEND THE
 SCHEDULE.ALSO, THE DOOR REF. IS NOT
 SHOWN ON SHEET A1.2.01A. ADD REFERENCES
 -STORAGE ROOM DOOR 2.04A IS NOT SHOWN AS
 RATED. SHOULD BE 1-1/2 HR. AMEND SCHED.
 -STORAGE ROOM DOOR 3.04A IS NOT SHOWN AS
 RATED. SHOULD BE 1-1/2 HR. AMEND SCHED.
 -POOL EQUIPMENT ROOM DOOR 4.04A SHOULD
 BE LABELLED 4.01A TO MATCH PLAN SHEET
 A1.2.04A.ALSO, IT IS NOT SHOWN AS
 RATED. SHOULD BE 1-1/2 HR. AMEND SCHED.
 CHECK DOOR SCHEDULE SHEETS A8.1.01A AND
 A8.1.01B TO ENSURE THAT ALL DOORS ARE
 SHOWN AS FIRE-RATED WHERE REQUIRED, AS
 THIS REVIEW IS NOT EXHAUSTIVE.
  
 11) INCORRECT REFERENCE TO BUILDING
 OCCUPANCY GROUP 'R4' (RESIDENTIAL CARE/
 ASSISTED LIVING).SHEET G3 STILL REFERS
 TO OCCUPANCY GROUP 'R4', UNDER THE
 HEADING 'CODE DATA'.AMEND THE PLAN.
  
 12) FBC 412.10.1 SPRINKLER DESIGN
 PARAMETERS.THIS COMMENT HAS NOT BEEN
 PROPERLY ADDRESSED.SHEET LS0.01
 'GENERAL INFORMATION' STILL REFERS TO
 FBC 412.1.10.THIS SHOULD BE CORRECTED
 TO READ FBC 412.10.1
  
 13) INFORMATIVE: FBC TABLE 600THE
 ADDITION OF THE TABLE 600 INFORMATION TO
 SHEET LS1.02 IS NOTED.CODE REFERENCES
 AND FOOTNOTE REFERENCES PERTAINING TO
 CONSTRUCTION TYPES II, III AND IV HAVE
 BEEN INADVERTENTLY INTERSPERSED WITH THE
 TYPE I INFORMATION.THE CORRECTIONS
 HAVE BEEN RED-LINED ON ONE (NOT ALL) OF
 THE SUBMITTED COPIES.
  
 14) SHEET A1.2.02A.STAIR #1 IS MIS-
 LABELLED AS STAIR #2.CONTRARY TO THE
 SUBMITTED COMMENT RESPONSE MEMO, THIS
 COMMENT HAS NOT BEEN ADDRESSED.
  
 15) FBC 1005.6.5SMOKEPROOF ENCLOSURE.
 THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.SHEET A1.2.01 SHOWS WALL
 TYPE B11 (WHICH IS ONLY ONE-HOUR RATED)
 ON TWO OF THE WALLS SEPARATING SERVICE
 CORRIDOR 1-10 AND RESTROOM 1-01.AMEND
 THE PLANS TO SHOW 2-HOUR FIRE-RATED
 WALLS.
  
 18) FBC TABLE 704.1SHEET 1.01.
 SEPARATION.THIS COMMENT HAS NOT BEEN
 PROPERLY ADDRESSED.THE PLAN DOES NOT
 SHOW THE REQUIRED ONE-HOUR FIRE-RATED
 SEPARATION BETWEEN THE FUTURE RETAIL
 (AND THE FUTURE OFFICE) OCCUPANCY AND
 THE ADJACENT CORRIDOR.AMEND THE PLAN.
  
 20) FBC 704.1THIS COMMENT HAS NOT BEEN
 PROPERLY ADDRESSED.SHEET LS1.02 STILL
 DOES NOT SHOW ANY FIRE-RATING FOR THE
 WALLS BETWEEN THE VEHICLE RAMP (ALSO THE
 ACCESSIBLE PARKING SPACE OPPOSITE) AND
 THE 'VOID' ABOVE THE FIRST FLOOR
 RECEPTION, MAIL ROOM AND STORAGE ROOM.
  
 21) FBC TABLE 1003.1SHEET LS1.05.THE
 SUBMITTED RESPONSE IS NOTED. SUBTRACTION
 OF THE BAR AREA TO CALCULATE THE FOOR
 AREA IS ACCEPTABLE, BUT THE 5'
 'CIRCULATION PATH' SHALL NOT BE EXCLUDED
 FROM THE FLOOR AREA CALCULATION.AMEND
 THE CALCULATION.
  
 23) FBC 1005.6.2STAIR #1 AND ADJACENT
 SHAFTS AND ELEVATORS.THIS COMMENT HAS
 NOT BEEN PROPERLY ADDRESSED.SHEETS
 LS1.05 AND LS1.06 STILL SHOW ONLY ONE-
 HOUR FIRE SEPARATION BETWEEN THE EXIT
 ACCESS CORRIDOR AND THE STAIRWAY/SHAFT/
 ELEVATOR.AMEND THE PLANS TO SHOW THE
 REQUIRED 2-HOUR SEPARATION.
  
 25) FBC 301.2OCCUPANT LOAD TABLE,
 SHEET LS1.06.THIS COMMENT HAS NOT BEEN
 PROPERLY ADDRESSED.THE REVISED AREA OF
 'RESIDENTIAL' OCCUPANCY IS STATED AS
 16544 GSF.IT IS ACTUALLY IN EXCESS OF
 18000 GSF FOR EACH OF THE TYPICAL FLOORS
 AMEND THE TABLE.
  
 26) FBC TABLE 705.1.2THIS COMMENT HAS
 NOT BEEN ADDRESSED.SHEET LS1.06 STILL
 SHOWS NO FIRE-RATING FOR THE WALLS
 BETWEEN STAIR #1 AND THE ADJACENT SHAFTS
 OR FOR WALLS BETWEEN INDIVIDUAL SHAFTS.
 ALSO, THE WALL BETWEEN STAIR #2 LOBBY
 AND THE ADJACENT ELEVATOR LOBBY
 (FBC 412.6.1) IS NOT SHOWN AS FIRE-RATED
 AMEND THE PLANS.
  
 31) THE SUBMITTED MODIFIED BITUMEN ROOF
 SYSTEM PRODUCT APPROVAL NOA# 02-0605.04
 STATES A MAX.DESIGN PRESSURE OF
 -112.5 PSF WHICH IS LESS THAN THE
 -140 PSF PEAK NEGATIVE PRESSURE STATED
 ON SHEET S-21.ALSO, THE SYSTEM THAT
 ACHIEVES -112.5 PSF IS FOR APPLICATION
 TO STEEL DECK AND THEREFOR NOT
 APPLICABLE TO THE PROPOSED CONCRETE ROOF
 DECKS.SUBMIT AN ALTERNATIVE PRODUCT
 APPROVAL.BEFORE SUBMITTAL, THE
 ALTERNATIVE PRODUCT APPROVAL SHALL BE
 REVIEWED BY THE ENGINEER-OF-RECORD AND
 THE PROPOSED ASSEMBLY/SYSTEM SHALL BE
 CIRCLED ON EACH COPY.
  
 32) FBC 1606.1.4SUBMIT PRODUCT
 APPROVALS FOR THE WINDOWS AND EXTERIOR
 DOORS.
  
 34) FBC 13-103.0ENERGY CODE COMPLIANCE
 FORMS.THE PROJECT INFORMATION HAS NOT
 BEEN ENTERED PROPERLY.THE ARCHITECT'S
 REGISTRATION NUMBER SHALL BE ENTERED ON
 SHEET 2 OF THE FORMS.
  
 35) FBC 411.2.3PARKING GARAGE BARRIER.
 AN IMPACT GUARDRAIL NOTE HAS BEEN ADDED
 TO SHEET A1.1.02 (LEVEL 2 PARKING PLAN),
 UNDER 'GENERAL NOTES'.ALL OF THE
 'GENERAL NOTES' EXCEPT THE IMPACT
 GUARDRAIL NOTE, HAVE BEEN REPEATED ON
 SHEET A1.1.03 AND 04 (LEVEL 3 PARKING
 AND LEVEL 4 PARKING PLAN).SHEETS S-3
 THRU S-8 STILL DO NOT SHOW ANY VEHICULAR
 IMPACT BARRIER DETAILS FOR THE WALLS AT
 THE END OF THE PERIMETER PARKING SPACES.
 PROVIDE IMPACT GUARDRAIL/WALL DETAILS.
  
 36) FBC 1608.2GUARDRAIL STRENGTH.
 THIS COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.THE AMENDED NOTES ON
 SHEET A6.1.05, 06 AND 07 DO NOT STATE
 THE REQUIREMENT FOR THE GUARDRAIL
 SYSTEMS TO BE DESIGNED AND CONSTRUCTED
 FOR A CONCENTRATED LOAD OF 200 LB
 APPLIED AT ANY POINT AND IN ANY
 DIRECTION AT THE TOP OF THE GUARDRAIL.
 ADD THIS REQUIREMENT TO THE NOTES.
 ALL OF THE GUARDRAIL NOTES SHALL BE
 ADDED TO SHEET A7.1.05 'RAILING DETAILS'
  
 37) FBC 1608.2.1HANDRAIL STRENGTH.
 THIS COMMENT HAS NOT BEEN ADDRESSED.
 CONTRARY TO THE SUBMITTED COMMENT
 RESPONSE MEMO, SHEET A6.1.08, DETAIL 5
 STILL REFERS TO SFBC (SOUTH FLORIDA
 BUILDING CODE) FOR HANDRAIL STRENGTH
 REQUIREMENTS.THAT CODE IS NOT
 APPLICABLE.THE RELEVANT CODE
 REQUIREMENTS ARE IN FLORIDA BUILDING
 CODE (2001) FBC 1608.2.1.AMEND THE
 PLAN.
  
 42) FBC 11-4.13.6MANEUVERING
 CLEARANCES AT DOORS.THIS COMMENT HAS
 NOT BEEN ADDRESSED. THE SUBMITTED
 COMMENT RESPONSE MEMO REFERS TO 'SHEETS
 A1.105A AND A1.105B'.THESE SHEETS
 NUMBERS ARE NOT PART OF THE SUBMITTED
 PLANS SETS.THE COMMENT RESPONSE MEMO
 SHOULD REFER TO SHEETS A1.2.05A AND
 A1.2.05B.THESE PLANS DO NOT GIVE ANY
 DIMENSIONS FOR THE LOCATIONS IN QUESTION
 AMEND THE PLANS TO PROVIDE/CONFIRM THE
 REQUIRED 12" CLEARANCE BETWEEN THE DOOR
 FRAME AND THE ADJACENT WALL ON THE PUSH
 SIDE OF MEN'S RESTROOM DOOR 5-06 IF THE
 DOOR HAS BOTH A CLOSER AND A LATCH.
 ALSO AMEND THE PLANS TO PROVIDE/CONFIRM
 THE REQUIRED 18" CLEARANCE BETWEEN THE
 LEADING EDGE OF THE DOOR AND THE
 ADJACENT WALL ON THE PULL SIDE OF THE
 WOMEN'S RESTROOM DOOR 5-08.
 NOTE: ENSURE THAT THE REQUIRED CLEARANCE
 IS ALSO PROVIDED AT THE DOORS FROM
 CORRIDOR 5-11 TO THE EAST POOL DECK AND
 TO THE WEST POOL DECK.
  
 THE FOLLOWING ARE ADDITIONAL COMMENTS
 ARISING FROM REVIEW OF THE REVISED
 PLANS AND APPLICATION FOR PERMIT:
  
 46) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 47) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, THE PLANS STAMPED BY THEM
 AND A COPY OF THE RECEIPT SUBMITTED TO
 THE CITY OF WEST PALM BEACH DEPARTMENT
 OF CONSTRUCTION SERVICES BEFORE A
 BUILDING PERMIT CAN BE ISSUED.
  
 48) THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES THE BOUNDARY LINES BETWEEN
 FOUR DIFFERENT LOTS.SUBMIT A COPY OF A
 RECORDED UNITIVE TITLE DOCUMENT SO THAT
 FBC TABLE 600 BOUNDARY LINE REQUIREMENTS
 MAY BE DEEMED NOT APPLICABLE.
  
 49) CONDOMINIUM V APARTMENTS.IF THE
 DWELLING UNITS ARE TO BE SOLD AS
 CONDOMINIUMS, NO CERTIFICATE OF
 OCCUPANCY CAN BE ISSUED UNTIL A
 'DECLARATION OF CONDOMINIUM' HAS BEEN
 SUBMITTED TO THE STATE FOR APPROVAL, AND
 THEN RECORDED WITH THE CLERK OF THE
 COUNTY COURT.A RECORDED COPY SHALL BE
 SUBMITTED TO THE CITY FOR RECORDS,
 ADDRESSING PURPOSES, AND NOTIFICATION OF
 PALM BEACH COUNTY PROPERTY APPRAISER'S
 OFFICE.
  
 50) FBC TABLE 600SHEET A1.1.01.THE
 ADDITION OF THE 'FIRE RESISTANCE RATING
 CALCULATIONS' TABLE IS NOTED.FOR THE
 WEST ELEVATION OF THE PODIUM, THE TABLE
 STATES THAT THE PERMITTED PERCENTAGE OF
 UNPROTECTED OPENINGS IS 40%.AS THE
 DISTANCE TO THE PROPERTY LINE IS BETWEEN
 10 FT AND 20 FT (ACTUALLY 16'-6") THE
 PERMITTED PERCENTAGE OF OPENINGS, FROM
 TABLE 600, IS 20%.AMEND THE FIRE
 RESISTANCE RATING CALCULATION TABLE.IT
 IS, ANY CASE, NOTED THAT THE PERCENTAGE
 OF UNPROTECTED OPENINGS IN THE PODIUM
 WEST ELEVATION IS 18% AND SO DOES NOT
 EXCEED THAT PERMITTED.
  
 51) FBC 11-4.9.4SHEET A6.1.08.AT THE
 TOP OF THE PARKING LOT STAIR, THE
 HANDRAILS SHALL EXTEND HORIZONTALLY AT
 LEAST 12" BEYOND THE TOP RISER.AT THE
 BOTTOM OF THE STAIR, HANDRAILS SHALL
 CONTINUE TO SLOPE, BEYOND THE BOTTOM
 RISER FOR A DISTANCE EQUAL TO THE WIDTH
 OF ONE RISER AND THEN EXTEND
 HORIZONTALLY FOR A FURTHER 12 INCHES.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-03-12 Cont ID  
Sent By rbrown Date 2003-03-07 Time 16:10 Rev Time 0.00
Received By rbrown Date 2003-03-07 Time 16:10 Sent To  
Notes
2003-03-07 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) VALUATION.FROM PUBLISHED SBCCI
 VALUATION DATA, THE CONSTRUCTION COST
 FOR APARTMENTS IN TYPE I CONSTRUCTION IS
 $84/SQFT PLUS $1.75/SQFT (SPRINKLERED).
 AT 413,370 SQFT THE CORRECT VALUATION IS
 $35,446,478.THE $17,770,333 VALUE
 STATED ON THE PLANS IS UNDERESTIMATED.
 IT IS NOTED THAT THE CURRENT APPLICATION
 IS FOR PLAN REVIEW ONLY, BUT THE VALUE
 SHALL BE AMENDED BEFORE APPLYING FOR A
 PERMIT.
  
 2) FBC* 105.13.1SPECIAL INSPECTOR.A
 STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED PRIOR TO THE ISSUANCE OF A
 BUILDING PERMIT FOR THE CONSTRUCTION OF
 A THRESHOLD BUILDING.A THRESHOLD
 BUILDING IS ANY BUILDING WHICH IS
 GREATER THAN THREE STORIES OR 50 FEET IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY
 OCCUPANCY WITH 5,000 SQFT AREA AND
 GREATER THAN 500 OCCUPANTS.
  
 3) FBC* 104.1.1A SEPARATE SWIMMING
 POOL PERMIT APPLICATION IS REQUIRED,
 SHOWING COMPLIANCE WITH FBC 424.1
  
 4) FBC* 104.1.1A SEPARATE PERMIT
 APPLICATION IS REQUIRED FOR THE FABRIC
 AWNINGS.
  
 5) FBC* 104.2.2THE ARCHITECTURAL PLANS
 ARE NOT PROPERLY SEALED.
  
 6) FBC* 104.2.4THE SURVEY DRAWING IS
 NOT SIGNED AND SEALED.
  
 7) FBC* 104.2.1.3SHEET A1.1.01THE
 USE OF TAPED-ON NOTES WILL NOT BE
 APPROPRIATE FOR PERMITTING PURPOSES.
  
 8) FBC* 104.2.1DOOR SCHEDULE AND
 INTERIOR FINISH SCHEDULE.SHEETS
 A8.1.01A, 01B, 03A AND 03B CANNOT BE
 READ.SUBMIT LEGIBLE COPIES.
  
 9) SHEET S-15.'CODES AND STANDARDS'
 NOTE 2A REFERS TO FLORIDA BUILDING CODE
 2000.AMEND TO FLORIDA BUILDING CODE
 2001.
  
 10) SHEET A6.1.09 NOTES 1 THRU 9 REFER
 TO STANDARD BUILDING CODE 1997.AMEND
 THEM TO REFER TO CHAPTERS 11 AND 30 OF
 FLORIDA BUIDING CODE 2001.
  
 11) LIFE SAFETY FLOOR PLANS, SHEETS
 LS1.01, 02, 05 AND 06 ALL INCORRECTLY
 STATE, UNDER 'GENERAL NOTES' THAT THE
 BUILDING OCCUPANCY GROUP IS 'R4'
 (RESIDENTIAL CARE/ASSISTED LIVING) AND
 'H' (HAZARDOUS).ONE OF THE THREE
 SUBMITTED COPIES OF SHEET LS1.01 ONLY
 HAS BEEN RED-LINED TO CORRECT THIS.ALL
 OF THE LIFE SAFETY FLOOR PLAN SHEETS
 SHALL BE AMENDED.NOTE:THE RED-LINE
 ALSO INCLUDES CORRECTIONS TO THE
 'MINIMUM INTERIOR FINISH CLASSIFICATION'
 TABLE.ALSO, NOTES ABOVE THE 'LEGEND'
 ON SHEETS LS1.05, 06 AGAIN STATE AN
 OCCUPANCY TYPE 'H' (AND AN OCCUPANCY
 LOAD OF ONLY 503 PEOPLE).AMEND SHEETS
 LS1.05 AND 06.
  
 12) FBC 412.10.1SPRINKLER DESIGN
 PARAMETERS.SHEET LS0.01 'GENERAL INFO'
 REFERS TO FBC 412.1.10, AMEND THIS TO
 READ FBC 412.10.1.ALSO, SPRINKLER
 SYSTEM DESIGN SHALL BE AS PER NFPA13,
 REMOVE ALL REFERENCES TO NFPA13R.
  
 13) FBC TABLE 600THE PLANS SHALL STATE
 THE REQUIRED FIRE RESISTANCE RATING FOR
 THE BEAMS, COLUMNS AND WALLS.
  
 14) SHEET A1.2.02A.STAIR #1 IS MIS-
 LABELLED AS STAIR #2.
  
 15) FBC 1005.6.5SMOKEPROOF ENCLOSURE.
 STAIR #1 DISCHARGES AT LEVEL 1 VIA
 SERVICE CORRIDOR 1-10 WHICH IS SHOWN
 WITH 1-HOUR RATED WALLS.AMEND THE
 PLANS TO SHOW 2-HOUR FIRE-RATED WALLS.
  
 16) FBC 412.11(4) FIRE DAMPER RESISTANCE
 RATING.SHEEET LS0.01 SHOWS THE FIRE
 DAMPER 'FIRE RESISTANCE RATING' AS 'N/A'
 THAT IS NOT CORRECT FOR ANY DAMPERS
 REQUIRED TO MAINTAIN THE FIRE RESISTANCE
 OF THE FLOORS.AMEND THE ITEM
 'SEPARATION FLOOR-TO-FLOOR' TO READ
 'SEPARATION FLOOR-TO-FLOOR (INCLUDING
 FIRE DAMPERS)
  
 17) FBC 1005.6.2EXIT DOOR FIRE
 RESISTANCE.THE DOORS INTO STAIRS 1 & 2
 SHALL HAVE A FIRE RESISTANCE RATING OF
 1 1/2 HOURS.AMEND SHEET LS0.01 WHERE
 THE TWELFTH NOTE UNDER'GENERAL
 INFORMATION' STATES THAT 1-HOUR RATED
 DOORS AND FRAMES WILL BE PROVIDED.
  
 18) FBC TABLE 704.1SHEETS LS1.01 & 02
 SEPARATION.THE PLAN DOES NOT SHOW THE
 REQUIRED ONE-HOUR FIRE RESISTANT
 SEPARATION BETWEEN THE PARKING GARAGE
 AND THE A/C ROOM (AND THE STORAGE ROOM
 FOR SHEET LS1.01 ONLY) OR THE REQUIRED
 ONE-HOUR SEPARATION BETWEEN THE FUTURE
 RETAIL AND THE FUTURE OFFICE OCCUPANCY
 AND THE ADJACENT CORRIDOR.AMEND THE
 PLANS.
  
 19) FBC 1004.1.2SHEET LS1.01, GUEST
 PARKING EGRESS.ANNOTATE THE PLANS TO
 SHOW HOW THE PROPOSED GATE ARRANGEMENT
 WILL ENABLE EGRESS IN ACCORDANCE WITH
 FBC 1012.
  
 20) FBC 704.1SHEET LS1.02THE WALLS
 SURROUNDING THE VOIDS DESCRIBED ON THE
 PLAN AS 'OPEN TO BELOW', SHALL HAVE THE
 SAME FIRE-RATING AS SHOWN FOR THOSE SAME
 AREAS ON SHEET LS1.01 (THE FLOOR BELOW)
 TO MAINTAIN SEPARATION.
  
 21) FBC TABLE 1003.1SHEET LS1.05.ON
 WHAT BASIS HAS THE STATED 600 NET SQFT
 AREA, FOR THE PARTY ROOM, BEEN
 CALCULATED (SEE FBC 202 FOR DEFINITION
 OF 'AREA, NET FLOOR').SUBMIT DETAILS
 TO SUPPORT THE CALCULATED NET AREA, OR
 AMEND THE STATED OCCUPANT LOAD.
  
 22) FBC 1004.1.2SHEET LS1.05, PARTY
 ROOM.SEPARATION BETWEEN THE EXIT DOORS
 SHALL BE 1/3 OF THE OVERALL DIAGONAL OF
 THE ROOM.AMEND THE PLANS.
  
 23) FBC 1005.6.2SHEETS LS1.05 AND
 LS1.06 SHOW ONLY 1-HOUR FIRE SEPARATION
 BETWEEN THE EXIT ACCESS CORRIDOR AND THE
 STAIRWAY/SHAFTS/ELEVATOR.AMEND THE
 PLANS TO SHOW THE REQUIRED 2-HOUR
 SEPARATION.
  
 24) FBC 704.1SHEET LS1.06.THE
 REQUIRED 1-HOUR SEPARATION BETWEEN
 UNIT C-1 AND B-2B IS NOT SHOWN.AMEND
 THE PLANS.
  
 25) INFORMATIVE: FBC 301.2OCCUPANT
 LOAD TABLE, SHEET LS1.06.THE AREA OF
 'RESIDENTIAL' OCCUPANCY HAS BEEN UNDER-
 STATED BY APPROX 50% (TABLE STATES ONLY
 8986 GSF).ALSO, THE AREA RATE PER
 OCCUPANT USED TO CALCULATE THE "TOTAL"
 NUMBER OF PEOPLE STATED IN THE TABLE IS
 APPROX 50% OF THE STATED 200 GSF PER
 PERSON.THESE TWO ERRORS CANCEL OUT SO
 THAT THE CALCULATED TOTAL NUMBER OF
 PERSONS IS CORRECT.AMEND THE TABLE TO
 SHOW THE CORRECT AREA ALLOCATED TO
 RESIDENTIAL OCCUPANCY.
  
 26) FBC TABLE 705.1.2SHEET LS1.06. THE
 STAIRWAY, SHAFT, ELEVATOR LOBBY AND
 ELEVATOR HOISTWAY WALLS ARE NOT SHOWN AS
 FIRE-RATED.AMEND THE PLANS.
  
 27) FBC TABLE 1005.6.2 THE COMMENT ABOVE
 ALSO APPLIES TO STAIR #2 ON SHEET LS1.05
  
 28) FBC 1007.6.2 STAIR #2. SHEET A6.1.06
 THE WIDTH OF THE STAIR SHALL NOT
 DECREASE IN THE DIRECTION OF EXIT TRAVEL
 AMEND THE DIMENSIONS ON PLANS 3 AND 4 TO
 ENSURE THAT THE STAIR FLIGHT WIDTHS ARE
 NOT GREATER THAN THAT ON PLANS 1 AND 2.
  
 29) FBC 1012.4SLIDING DOOR DETAILS,
 SHEET A7.1.01.THIS DOOR MUST COMPLY
 WITH THE REQUIREMENTS FOR HORIZONTAL
 SLIDING DOORS IN A MEANS OF EGRESS,
 INCLUDING, BUT NOT LIMITED TO, BEING
 OPENABLE BY A FORCE APPLIED
 PERPENDICULAR TO THE DOOR.AMEND THE
 PLANS TO SPECIFY EACH OF THE
 REQUIREMENTS.
  
 30) FBC 3003.4.1ELEVATORS, STRETCHER
 REQUIREMENTS.ADD A NOTE TO
 SHEET A6.1.09 TO ENSURE/CONFIRM THAT A
 76"LONG X 24"WIDE AMBULANCE STRETCHER
 CAN BE ACCOMMODATED IN THE HORIZONTAL
 POSITION IN ONE OF THE ELEVATORS
 (PRESUMABLY ELEVATOR #3).IDENTIFY THE
 ELEVATOR AS 'ACCESSIBLE ELEVATOR'.
  
 31) SUBMIT A PRODUCT APPROVAL FOR THE
 ROOFING.
  
 32) FBC 1606.1.4PROTECTION OF OPENINGS
 ALTHOUGH NOTE (1) ON SHT A8.1.02 STATES
 THAT THE DOORS AND WINDOWS WILL BE UNDER
 A SEPARATE PERMIT, THE PLANS SHALL STATE
 WHETHER THE WINDOWS WITHIN 60 FT HEIGHT
 ABOVE GRADE ARE TO HAVE IMPACT RESISTANT
 GLAZING OR IMPACT PROTECTION. IF NEITHER
 OF THESE IS PROVIDED, THEN THE WINDOWS
 SHALL BE ASSUMED TO BE OPENINGS AND THE
 BUILDING EVALUATED AS AN 'OPEN' OR
 'PARTIALLY ENCLOSED' BUILDING IN
 ACCORDANCE WITH FBC 1606.1.4.1
  
 33) FBC 2405.2ALL INTERIOR OR EXTERIOR
 GLAZING IN A 'HAZARDOUS LOCATION' IS
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).ANNOTATE THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 34) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS
  
 35) FBC 411.2.3PARKING GARAGE.
 SHEETS S-3 THRU S-8, PARKING FRAMING
 PLANS, DO NOT CALL UP STRUCTURAL CROSS-
 SECTIONAL DETAILS FOR DETAIL 1 ON SHEETS
 A1.1.02.THOSE SHEETS DO INCORRECTLY
 REFERENCE NON-EXISTENT DETAILS ON SHEET
 S-19.PROVIDE VEHICULAR IMPACT WALL
 DETAILS WITH APPROPRIATE REFERENCES ON
 THE PLANS.
  
 36) FBC 1608.2GUARDRAIL STRENGTH.THE
 NOTES ON SHEET A6.1.05,06 AND 07 GIVE
 AN INCOMPLETE AND INCORRECT STRENGTH
 SPECIFICATION FOR THE GUARDRAILS AND
 HANDRAILS.AMEND THE PLANS TO SPECIFY
 THE CONCENTRATED, LINEAR AND COMBINED
 LOADS TO BE RESISTED BY THE GUARDRAILS
 AND HANDRAILS.ALSO, THE NOTES ON
 SHEET A6.1.05 ARE NOT COMPLETE.
  
 37) FBC 1608.2.1HANDRAIL STRENGTH.
 SHEET A6.1.08, DETAIL 5 REFERS TO SFBC
 (SOUTH FLORIDA BUILDING CODE) FOR
 HANDRAIL STRENGTH REQUIREMENTS.THE
 RELEVANT CODE REQUIREMENTS ARE FLORIDA
 BUILDING CODE (2001) FBC 1608.2.1
  
 38) FBC 424.1.3.1.2POOL WET DECKS.
 THE POOL WET DECKS SHALL BE UNIFORMLY
 SLOPED AT A MAXIMUM OF 2%, MINIMUM OF
 4%, AWAY FROM THE POOL OR TO DECK DRAINS
 TO PREVENT STANDING WATER.ANNOTATE THE
 PLANS TO DEMONSTRATE COMPLIANCE.
  
 39) SHEET A7.1.17.THE TITLES FOR
 DETAILS 1 THRU' 11 SHOW THAT THEY SHOULD
 BE ON SHEET A8.1.07. ALSO, SHEET A4.1.03
 (AND A4.1.08) REFERENCES DETAIL
 1/A7.1.17 FOR SECTION THROUGH THE WEST
 POOL.IT SHOULD, INSTEAD, REFERENCE
 DETAIL 1/A4.1.10.
  
 40) FBC 11-4.6THE ACCESSIBLE PARKING
 SPACE MARKINGS ARE NOT AS PER FLORIDA
 BUILDING COMMISSION RECOMMENDED PARKING
 SPACE DESIGN (COPY ATTACHED).
  
 41) FBC 11-4.2.9DETECTABLE WARNINGS.
 SHEET G3 REFERS TO 'DETACHABLE WARNINGS'
 ONE OF THE SUBMITTED COPIES HAS BEEN
 RED-LINED TO CORRECT THIS TO READ
 'DETECTABLE WARNINGS'.AMEND THE PLAN.
  
 42) FBC 11-4.13.6MANEUVERING
 CLEARANCES AT DOORS.AMEND THE PLANS TO
 PROVIDE/CONFIRM THE REQUIRED 12"
 CLEARANCE BETWEEN THE DOOR FRAME AND THE
 ADJACENT WALL ON THE PUSH SIDE OF MEN'S
 RESTROOM DOOR 5-06 IF THE DOOR HAS BOTH
 A CLOSER AND A LATCH.ALSO AMEND THE
 PLANS TO PROVIDE/CONFIRM THE REQUIRED
 MIN. 18" CLEARANCE BETWEEN THE LEADING
 EDGE OF THE DOOR AND THE ADJACENT WALL
 ON THE PULL SIDE OF THE WOMEN'S RESTROOM
 DOOR 5-08.NOTE:ENSURE, THAT THE
 REQUIRED CLEARANCE IS ALSO PROVIDED AT
 THE DOORS FROM CORRIDOR 5-11 TO THE EAST
 POOL DECK AND THE WEST POOL DECK.
  
 43) FBC 11-4.8.2THE RAMP IN CORRIDOR
 1-08 IS NOT LONG ENOUGH TO ACHIEVE THE
 REQUIRED 12" LEVEL CHANGE WITHOUT
 EXCEEDING THE MAXIMUM GRADIENT OF
 1 IN 12.AMEND THE PLANS.
  
 44) FBC 11-4.8.5(5)NORTH WEST RAMP
 SECTION, SHEET A6.1.04A.THE HANDRAIL
 HEIGHT IS SHOWN AS 3'-6".AMEND TO READ
 BETWEEN 34" AND 38".ALSO THE SECTION
 SHOULD BE AMENDED TO SHOW A MIN' 2" CURB
 AT THE EDGE OF THE RAMP.
  
 45) FBC 11-4.8.5(2)EAST RAMP SECTION,
 SHEET A6.1.04B.THE HANDRAIL EXTENSION
 IS SHOWN AS 1'-1".AMEND TO AT LEAST
 18" EXTENSION BEYOND THE SLOPED SEGMENT
 AT BOTH THE TOP AND BOTTOM OF THE RAMP.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 94 Status P Date 2005-08-11 Cont ID  
Sent By rbrown Date 2005-08-11 Time 08:01 Rev Time 0.00
Received By rbrown Date 2005-08-11 Time 08:01 Sent To  
Notes
2005-08-11 00:00:00STRUCTURAL REVISION SUBMITTED ON 7/29/05
 FOR PAC UNIT #2 ACCESS PLATFORM SKETCHES

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 93 Status P Date 2005-07-14 Cont ID  
Sent By rbrown Date 2005-07-14 Time 15:21 Rev Time 0.00
Received By rbrown Date 2005-07-14 Time 15:21 Sent To  
Notes
2005-07-14 00:00:00ARCTITECTURAL REVISION SUBMITTED 6/23/05
 FOR ACCESSIBLE PARKING SPACE AND
 GUARDRAIL ADJACENT GRID 10.6

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 92 Status P Date 2005-06-20 Cont ID  
Sent By rbrown Date 2005-06-20 Time 15:47 Rev Time 0.00
Received By rbrown Date 2005-06-20 Time 15:47 Sent To  
Notes
2005-06-20 00:00:00STRUCTURAL SUBMITTAL ON 5/31/05 FOR
 ALUMINUM RAILING DESIGN CALCS.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 91 Status P Date 2005-06-20 Cont ID  
Sent By rbrown Date 2005-06-20 Time 15:48 Rev Time 0.00
Received By rbrown Date 2005-06-20 Time 15:48 Sent To  
Notes
2005-06-20 00:00:00STRUCTURAL SUBMITTAL ON 5/25/05 FOR
 ALUMINUM VERTICAL LOUVER DESIGN CALCS.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 90 Status P Date 2005-06-20 Cont ID  
Sent By rbrown Date 2005-06-20 Time 15:49 Rev Time 0.00
Received By rbrown Date 2005-06-20 Time 15:49 Sent To  
Notes
2005-06-20 00:00:00STRUCTURAL SUBMITTAL ON 5/23/05 FOR
 17TH FLOOR SLIDING GLASS DOOR CALCS.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 89 Status P Date 2005-06-20 Cont ID  
Sent By rbrown Date 2005-06-20 Time 15:51 Rev Time 0.00
Received By rbrown Date 2005-06-20 Time 15:51 Sent To  
Notes
2005-06-20 00:00:00STRUCTURAL SUBMITTAL FOR GLASS POOL
 GUARDRAIL ENGINEERING.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 88 Status P Date 2005-06-20 Cont ID  
Sent By rbrown Date 2005-06-20 Time 15:44 Rev Time 0.00
Received By rbrown Date 2005-06-20 Time 15:43 Sent To  
Notes
2005-06-20 00:00:00STRUCTURAL SUBMITTAL ON 5/10/05 FOR
 REMEDIAL WORK TO R.C. ALUM. 3060 HP
 STOREFRONT AT GROUND FLOOR.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 87 Status P Date 2005-06-20 Cont ID  
Sent By rbrown Date 2005-06-20 Time 15:31 Rev Time 0.00
Received By rbrown Date 2005-06-20 Time 15:31 Sent To  
Notes
2005-06-20 00:00:00STRUCTURAL SUBMITTAL ON 5/10/05 FOR
 REMEDIAL WORK AT STAIR #2.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 86 Status P Date 2005-05-20 Cont ID  
Sent By rbrown Date 2005-05-20 Time 16:41 Rev Time 0.00
Received By rbrown Date 2005-05-20 Time 16:41 Sent To  
Notes
2005-05-20 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 STRUCTURAL SUBMITTAL 5/20/05 FOR
 ALUMINUM BALCONY GUARDRAIL DESIGN
 CALCULATIONS.
  
 --PROVISO--
 A COPY OF CALCULATION SHEET 2, MARKED
 WITH NECESSARY CORRECTIONS, IS ATTACHED.
 PLEASE CORRECT AND RE-SUBMIT THE
 CALCULATIONS, OR CALL TO DISCUSS IF THIS
 COMMENT IS CONSIDERED INCORRECT.IT IS
 NOT ANTICIPATED THAT THE CHANGES WILL
 AFFECT THE SPECIFIED GUARDRAIL
 CONFIGURATION/SIZES SO THE DRAWING HAS
 BEEN STAMPED AS 'REVIEWED FOR CODE
 COMPLIANCE'.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 85 Status P Date 2005-05-04 Cont ID  
Sent By rbrown Date 2005-05-04 Time 11:38 Rev Time 0.00
Received By rbrown Date 2005-05-04 Time 11:38 Sent To  
Notes
2005-05-04 00:00:00ARCHITECTURAL SUBMITTAL ON 4/28/05 FOR
 EGGCRATE LOUVER DESIGN CALCULATIONS.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 84 Status P Date 2005-05-04 Cont ID  
Sent By rbrown Date 2005-05-04 Time 11:19 Rev Time 0.00
Received By rbrown Date 2005-05-04 Time 11:19 Sent To  
Notes
2005-05-04 00:00:00ARCHITECTURAL SUBMITTAL ON 4/28/05 FOR
 DECORATIVE LOUVER CALCULATIONS.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 83 Status P Date 2005-05-04 Cont ID  
Sent By rbrown Date 2005-05-04 Time 10:58 Rev Time 0.00
Received By rbrown Date 2005-05-04 Time 10:58 Sent To  
Notes
2005-05-04 00:00:00STRUCTURAL SUBMITTAL ON 4/28/05 FOR
 LETTER ON EMBEDMENT AND EDGE DISTANCE
 FOR ALUMINUM RAILING DESIGN.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 82 Status P Date 2005-05-04 Cont ID  
Sent By rbrown Date 2005-05-04 Time 10:46 Rev Time 0.00
Received By rbrown Date 2005-05-04 Time 10:46 Sent To  
Notes
2005-05-04 00:00:00STRUCTURAL SUBMITTAL ON 4/28/04 FOR
 ALUMINUM STAIR RAILING DESIGN CALCS

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 81 Status P Date 2005-05-04 Cont ID  
Sent By rbrown Date 2005-05-04 Time 09:49 Rev Time 0.00
Received By rbrown Date 2005-05-04 Time 09:49 Sent To  
Notes
2005-05-04 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 ARCHITECTURAL SUBMITTAL ON 4/28/05 FOR
 5TH AND 6TH FLOOR SERIES 345 FIXED
 WINDOW.
  
 - PROVISO -
 WINDOW AND INSTALLATION MUST BE IN
 ACCORDANCE WITH THE SUBMITTED PRODUCT
 APPROVAL.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 80 Status P Date 2005-04-27 Cont ID  
Sent By rbrown Date 2005-04-27 Time 15:36 Rev Time 0.00
Received By rbrown Date 2005-04-27 Time 15:36 Sent To  
Notes
2005-04-27 00:00:00REVISION RE-SUBMITTED ON 4/18/05
 (ORIGINALLY SUBMITTED ON 4/1/05) FOR
 SECTION THROUGH DEMISING WALL IN C-3
 UNIT KITCHEN

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 79 Status P Date 2005-04-19 Cont ID  
Sent By rbrown Date 2005-04-19 Time 11:43 Rev Time 0.00
Received By rbrown Date 2005-04-19 Time 11:43 Sent To  
Notes
2005-04-19 00:00:00STRUCTURAL REVISION SUBMITTED ON 4/19/05
 FOR CU-1 PLATFORM STEEL SKETCHES 1 TO 4
 (REVISED 4/14/05).

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 78 Status P Date 2005-04-19 Cont ID  
Sent By rbrown Date 2005-04-19 Time 11:35 Rev Time 0.00
Received By rbrown Date 2005-04-19 Time 11:35 Sent To  
Notes
2005-04-19 00:00:00ARCHITECTURAL REVISION RE-SUBMITTED ON
 4/14/05 ( ORIGINALLY SUBMITTED ON
 2/1/05) FOR SHEETS A1.1.01 AND A1.1.03

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 77 Status F Date 2005-04-08 Cont ID  
Sent By rbrown Date 2005-04-08 Time 09:25 Rev Time 0.00
Received By rbrown Date 2005-04-08 Time 09:25 Sent To  
Notes
2005-04-08 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 REVISION SUBMITTED ON 4/1/05 FOR SECTION
 THROUGH DEMISING WALL IN C-3 UNIT
 KITCHEN
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC 701.2FIRE RESISTANCE.THE
 PROPOSED WALL TYPE SHALL BE SHOWN TO
 HAVE PERFORMED SATISFACTORILY WHEN
 TESTED TO THE REQUIREMENTS OF ASTM E 119
 IT IS NOTED THAT THE SUBMITTED SHEETS
 MAKE REFERENCE TO TEST NUMBER U OF C
 7-31-62(UNIVERSITY OF CALIFORNIA).
 SUBMIT A COPY OF THE TEST REPORT OR
 OTHER DOCUMENTATION TO SHOW COMPLIANCE
 WITH ASTM E 119.
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]
  

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 76 Status P Date 2005-04-07 Cont ID  
Sent By rbrown Date 2005-04-07 Time 16:11 Rev Time 0.00
Received By rbrown Date 2005-04-07 Time 16:10 Sent To  
Notes
2005-04-07 00:00:00STRUCTURAL REVISION RE-SUBMITTED ON
 4/7/05 (ORIGINALLY SUBMITTED ON 3/22/05)
 FOR CU-1 PLATFORM STEEL SKETCHES 1 TO 4.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 75 Status P Date 2005-03-31 Cont ID  
Sent By rbrown Date 2005-03-31 Time 09:59 Rev Time 0.00
Received By rbrown Date 2005-03-31 Time 09:59 Sent To  
Notes
2005-03-31 00:00:00ARCHITECTURAL REVISION SUBMITTED ON
 2/1/05 FOR SHEETS A1.1.06A, A1.3.06,
 A1.3.07, A1.5.916/917 AND A1.5.1116/1117

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 74 Status F Date 2005-03-31 Cont ID  
Sent By rbrown Date 2005-03-31 Time 09:59 Rev Time 0.00
Received By rbrown Date 2005-03-30 Time 19:08 Sent To  
Notes
2005-03-30 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 ARCHITECTURAL REVISION SUBMITTED ON
 2/1/05 FOR SHEETS A1.1.01 AND A1.1.03
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC* 104.2.1 SHEET A1.1.01 REVISIONS.
 THE SUBMITTED REVISION #5 SHEET IS
 MISSING 'GENERAL NOTES 7 TO 11' WHICH
 WERE INCLUDED UNDER REVISIONS 1 TO 4, IS
 THIS INTENTIONAL?IF IT IS INTENTIONAL,
 A FIRE AND PLUMBING REVIEW WILL BE
 NECESSARY BECAUSE OMITTING THOSE GENERAL
 NOTES WILL AFFECT THEIR REVIEWS.PLEASE
 CLARIFY THE EXTENT OF THE PROPOSED
 REVISIONS TO THIS SHEET.
  
 2) SHEET A1.1.03THE PARKING TABLE HAS
 NOT BEEN REVISED TO REFLECT THE
 REDUCTION IN THE NUMBER OF PARKING
 SPACES.THE PLANS SHOWED 97 PARKING
 SPACES NUMBERED 301 TO 397. THE PROPOSED
 REVISION WILL OMIT 'REGULAR' PARKING
 SPACES 367 AND 368 LEAVING A TOTAL OF 95
 SPACES (0F WHICH 72 ARE 'REGULAR'.
 AMEND THE PARKING TABLE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]
  

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 73 Status P Date 2005-03-30 Cont ID  
Sent By rbrown Date 2005-03-30 Time 18:05 Rev Time 0.00
Received By rbrown Date 2005-03-30 Time 18:05 Sent To  
Notes
2005-03-30 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 REVISION SUBMITTED FOR DOOR L1-01A,
 L1-01B, L1-01C, L1-13A, L1-13B, L1-28A,
 L1-30B, L1-31B, L1-33, R02 & R04 PRODUCT
 APPROVAL.
  
 --PROVISO--
 DOORS L1-13A, L1-13B, L1-28A, L1-30B,
 L1-31B ARE ALSO REQUIRED TO BE FIRE
 DOORS PER DOOR SCHEDULE SHEET A8.1.01A.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 72 Status F Date 2005-03-30 Cont ID  
Sent By rbrown Date 2005-03-30 Time 16:38 Rev Time 0.00
Received By rbrown Date 2005-03-30 Time 16:38 Sent To  
Notes
2005-03-30 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 ARCHITECTURAL REVISION SUBMITTED 3/22/05
 FOR DOOR L1-29A PRODUCT APPROVAL.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) THE DOOR SCHEDULE SHEET A8.1.01A
 SHOWS DOOR L1-29A AS A PAIR OF 3'X 8'
 GLAZED STOREFRONT DOORS.THE SUBMITTED
 TOTAL DOOR OUTSWING STEEL COMMERCIAL
 DOOR PRODUCT APPROVAL NOA# 03-0822.01
 ONLY COVERS DOORS WITH A MAXIMUM HEIGHT
 OF 7'-1" AND DOES NOT COVER GLAZED
 DOORS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]
  
  
  

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 71 Status F Date 2005-03-30 Cont ID  
Sent By rbrown Date 2005-03-30 Time 15:23 Rev Time 0.00
Received By rbrown Date 2005-03-30 Time 15:23 Sent To  
Notes
2005-03-30 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 STRUCTURAL REVISION SUBMITTED ON 3/22/05
 FOR CU-1 PLATFORM STEEL SKETCHES 1 TO 4.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) 61G15-23.002(1)FL. ADMIN. CODE.
 ONLY SHEET 1 OF 4 BEARS THE SIGNATURE
 AND SEAL OF THE ENGINEER.EACH COPY OF
 EVERY SHEET SUBMITTED BY THE ENGINEER
 FOR PUBLIC RECORD, SHALL BEAR THE
 ORIGINAL SIGNATURE AND RAISED SEAL OF
 THE ENGINEER. (471.025 F.S.)
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]
  
  
  

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 70 Status P Date 2005-03-30 Cont ID  
Sent By rbrown Date 2005-03-30 Time 15:22 Rev Time 0.00
Received By rbrown Date 2005-03-23 Time 14:17 Sent To  
Notes
2005-03-23 00:00:00ARCHITECTURAL REVISION SUBMITTED 3/23/05
 FOR SHEET LS1.05 REVISIONS TO PARTY ROOM
 AND FITNESS CENTER.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 69 Status P Date 2005-03-22 Cont ID  
Sent By rbrown Date 2005-03-22 Time 12:09 Rev Time 0.00
Received By rbrown Date 2005-03-22 Time 12:09 Sent To  
Notes
2005-03-22 00:00:00ARCHITECTURAL REVISION SUBMITTED ON
 3/2/05 FOR SHEET A2.1.05A, LEVEL 5
 REFLECTED CEILING PLAN

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 68 Status P Date 2005-03-22 Cont ID  
Sent By rbrown Date 2005-03-22 Time 11:58 Rev Time 0.00
Received By rbrown Date 2005-03-22 Time 11:58 Sent To  
Notes
2005-03-22 00:00:00SUBMITTAL ON 2/22/05 FOR ADTEK LIGHT
 GAGE STEEL CANOPY STRUCTURE FRAMING
 SKETCHES AND CALCULATION.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 67 Status P Date 2005-03-22 Cont ID  
Sent By rbrown Date 2005-03-22 Time 11:08 Rev Time 0.00
Received By rbrown Date 2005-03-22 Time 11:08 Sent To  
Notes
2005-03-22 00:00:00STRUCTURAL SUBMITTAL 2/22/05 (ORIGINALLY
 SUBMITTED 2/8/05) FOR ALUMINUM BALCONY
 GUARDRAIL DESIGN CALCULATIONS.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 66 Status P Date 2005-03-22 Cont ID  
Sent By rbrown Date 2005-03-22 Time 10:48 Rev Time 0.00
Received By rbrown Date 2005-03-22 Time 10:48 Sent To  
Notes
2005-03-22 00:00:00SUBMITTAL ON 2/22/05 FOR SITE SPECIFIC
 ENGINEERING TO JUSTIFY PRODUCT APPROVALS
 FOR STEEL DOORS AND LOUVERED STEEL
 DOORS.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 65 Status P Date 2005-02-15 Cont ID  
Sent By rbrown Date 2005-02-15 Time 09:26 Rev Time 0.00
Received By rbrown Date 2005-02-15 Time 09:26 Sent To  
Notes
2005-02-15 00:00:00FLAT ROOFING PRODUCT APPROVAL REVISION
 SUBMITTED ON 1/20/05 (AND RE-SUBMITTED
 ON 2/11/05) FOR ELEVATOR MACHINE ROOM
 ROOF.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 64 Status F Date 2005-02-10 Cont ID  
Sent By rbrown Date 2005-02-10 Time 12:18 Rev Time 0.00
Received By rbrown Date 2005-02-10 Time 12:06 Sent To  
Notes
2005-02-10 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 STRUCTURAL SUBMITTAL 2/8/05 FOR ALUMINUM
 BALCONY GUARDRAIL DESIGN CALCULATIONS.
  
 1) THE ONM&J REVIEW LETTER ATTACHED TO
 EACH SET OF THE WHITE ALUMINUM
 FABRICATION, INC DOCUMENTS IS A COPY AND
 DOES NOT HAVE AN ORIGINAL (WET)
 SIGNATURE OR RAISED SEAL, FROM THE
 ENGINEER OF RECORD.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 63 Status P Date 2005-02-10 Cont ID  
Sent By rbrown Date 2005-02-10 Time 11:04 Rev Time 0.00
Received By rbrown Date 2005-02-10 Time 11:04 Sent To  
Notes
2005-02-10 00:00:00ARCHITECTURAL SUBMITTAL ON 2/8/05 FOR
 RFI CLARIFICATION OF STAIR HEADROOM
 HEIGHT REQUIREMENT.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 62 Status F Date 2005-02-04 Cont ID  
Sent By rbrown Date 2005-02-04 Time 16:15 Rev Time 0.00
Received By rbrown Date 2005-02-04 Time 16:15 Sent To Z
Notes
2005-02-04 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 ARCHITECTURAL REVISION SUBMITTED ON
 2/1/05 FOR SHEETS A1.1.01, A1.1.03 AND
 A2.1.05A
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC* 104.2.1 SHEET A1.1.01
 REVISIONS.
 REVISION #5 IS DESCRIBED AS "PARKING
 REVISION" BUT THERE ARE NUMEROUS NOTES
 MISSING WHEN COMPARED TO REVISION
 #4(E.G. NOTES THAT WERE PRINTED AROUND
 THE OUTSIDE OF THE NORTH, EAST, SOUTH
 AND WEST PROPERTY LINES), IS THIS
 INTENTIONAL?CLARIFY THE EXTENT OF THE
 PROPOSED REVISIONS TO THIS SHEET.
  
 2) SHEET A1.1.03THE PARKING TABLE HAS
 NOT BEEN REVISED TO REFLECT THE
 REDUCTION IN THE NUMBER OF PARKING
 SPACES.THE PROPOSED REVISION WILL OMIT
 PARKING SPACES 367 AND 368.THE REVISED
 PLANS HAVE BEEN ROUTED TO THE ZONING
 PLAN REVIEWER FOR RECORD/REVIEW.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 61 Status F Date 2005-02-04 Cont ID  
Sent By rbrown Date 2005-02-04 Time 14:55 Rev Time 0.00
Received By rbrown Date 2005-02-04 Time 14:55 Sent To  
Notes
2005-02-04 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 ARCHITECTURAL REVISION SUBMITTED ON
 1-20/05 FOR SHEETS A1.3.02, A1.3.05 AND
 A1.3.07
  
 FAIR HOUSING ACT (FHA) - REQUIREMENT 7,
 PART B - USABLE BATHROOMS.
 THE PROPOSED REVISION PROVIDES A SINGLE
 SPECIFICATION B BATHROOM INSTEAD OF TWO
 SPECIFICATION A BATHROOMS.THIS IS
 PERMITTED BY FHA, ONLY IF THE PROPOSED
 BATHROOM LAYOUT MEETS THE ALL OF THE
 REQUIREMENTS FOR A SPECIFICATION B
 BATHROOM.THE FHA SPECIFICATION B
 LAYOUTS ON THE REVISED SHEETS MUST HAVE
 A BATHTUB WITH A PARALLEL APPROACH AND A
 30"X 48" CLEAR FLOOR SPACE WHICH IS
 FLUSH WITH THE CONTROL WALL SURFACE.
 AMEND THE PLANS TO SHOW AT WHICH END OF
 THE BATHTUB THE CONTROLS ARE LOCATED TO
 DEMONSTRATE COMPLIANCE.IF THE BATHROOM
 DOES NOT MEET SPECIFICATION B
 REQUIREMENTS THEN EACH BATHROOM IN THE
 UNIT MUST MEET SPECIFICATION A
 REQUIREMENTS.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 60 Status F Date 2005-02-04 Cont ID  
Sent By rbrown Date 2005-02-04 Time 13:20 Rev Time 0.00
Received By rbrown Date 2005-02-04 Time 13:20 Sent To  
Notes
2005-02-04 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FLAT ROOFING PRODUCT APPROVAL REVISION
 SUBMITTED ON 1/20/05 FOR ELEVATOR
 MACHINE ROOM ROOF.
  
 FROM THE WIND LOAD PRESSURE SUMMARY
 SHEETS S-22 AND S-23, THE DESIGN WIND
 NEGATIVE PRESSURE ON THE THE ELEVATOR
 MACHINE ROOM ROOF IS UP TO -100 PSF.
 THE SUBMITTED GAF PRODUCT APPROVAL NOA#
 04-0611.01 COVERS SYSTEMS WITH MAXIMUM
 DESIGN PRESSURES RANGING FROM -52.5 PSF
 TO -242.5 PSF.WHICH SYSTEM IS
 PROPOSED?
 THE PRODUCT APPROVAL SHEETS SHALL BE
 MARKED, AS APPROPRIATE, TO IDENTIFY
 WHICH SYSTEM IS TO BE USED.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 59 Status P Date 2005-02-03 Cont ID  
Sent By rbrown Date 2005-02-03 Time 16:20 Rev Time 0.00
Received By rbrown Date 2005-02-03 Time 16:20 Sent To  
Notes
2005-02-03 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 ARCHITECTURAL REVISION SUBMITTED ON
 1/20/05 FOR STAIR #2 EXIT DISCHARGE
 DOOR
 S1-2A PRODUCT APPROVAL.
  
 --PROVISO--
 TO MEET THE REQUIRED -80 PSF DESIGN
 PRESSURE FOR THIS BUILDING THE DOOR
 TYPE
 MUST BE THE 'REINFORCED PANEL TRIPLE
 FLIPPER PLUS TOP/BOTTOM STIFFENER' (SEE
 DESIGN PRESSURE TABLE ON PRODUCT
 APPROVAL NOA# 03-0822.01, DRAWING SHEET
 1 OF 9).

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 58 Status P Date 2004-12-22 Cont ID  
Sent By rbrown Date 2004-12-22 Time 14:59 Rev Time 0.00
Received By rbrown Date 2004-12-22 Time 14:59 Sent To  
Notes
2004-12-22 00:00:00SUBMITTAL ON 12/21/04 FOR ADTEK LIGHT
 GAGE STEEL ROOF STRUCTURE FRAMING
 SKETCHES AND CALCULATION.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 57 Status P Date 2004-12-22 Cont ID  
Sent By rbrown Date 2004-12-22 Time 14:57 Rev Time 0.00
Received By rbrown Date 2004-12-22 Time 14:57 Sent To  
Notes
2004-12-22 00:00:00SUBMITTAL ON 12/21/04 FOR WILKINSON
 TRASH CHUTE SHOP DRAWING.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 56 Status P Date 2004-12-14 Cont ID  
Sent By rbrown Date 2004-12-14 Time 17:22 Rev Time 0.00
Received By rbrown Date 2004-12-14 Time 17:22 Sent To  
Notes
2004-12-14 00:00:00STRUCTURAL SUBMITTAL ON 12/14/04 FOR
 ONM&J SKETCHES S1 TO S4
  
 --PROVISO--
 THE HEIGHT OF MECHANICAL EQUIPMENT SHALL
 COMPLY WITH FBC TABLE 1511.7
 REQUIREMENTS FOR CLEARANCE ABOVE THE
 ROOF COVERING.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 55 Status F Date 2004-12-14 Cont ID  
Sent By rbrown Date 2004-12-14 Time 15:02 Rev Time 0.00
Received By rbrown Date 2004-12-14 Time 15:02 Sent To  
Notes
2004-12-14 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 ALTERNATIVE PRODUCT APPROVAL SUBMITTED
 ON 12/14/04 FOR DOOR S1-2A, FIRST FLOOR
 STAIR 2 EXIT DISCHARGE DOOR TO
 EXTERIOR.
  
 1) THE PRODUCT APPROVAL WAS BROUGHT IN
 AS A SUBMITTAL FOR ZERO FEE.IT IS IN
 FACT A REVISION AND A REVISION FEE OF
 $60 IS DUE.
  
 2) FBC 1606.1WIND PRESSURES ON DOOR
 S1-2A.SHEET S-22, WIND TUNNEL
 ANALYSIS
 RESULTS, SHOWS A PEAK NEGATIVE PRESSURE
 OF -80 PSF, FOR THIS LOCATION ON THE
 BUILDING.THIS EXCEEDS THE -70 PSF
 DESIGN PRESSURE RATING GIVEN IN THE
 SUBMITTED INGERSOLL-RAND COMMERCIAL
 STEEL DOOR PRODUCT APPROVAL NOA#
 02-712.01 AND IS THUS OUTSIDE THE SCOPE
 OF THE PRODUCT APPROVAL.THIS DOOR HAS
 NOT BEEN DEMONSTRATED AS SUITABLE FOR
 USE IN THIS LOCATION.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 54 Status P Date 2004-11-15 Cont ID  
Sent By rbrown Date 2004-11-15 Time 11:45 Rev Time 0.00
Received By rbrown Date 2004-11-15 Time 11:44 Sent To  
Notes
2004-11-15 00:00:00STRUCTURAL REVISION SUBMITTED ON
 11/15/04 WITH PRODUCT APPROVALS FOR
 STAIR #1 AND #2 INSWING DOORS AT LEVELS
 2 TO 4 AND STAIR #2 OUTSWING DOOR AT
 LEVEL 1

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 53 Status P Date 2004-11-03 Cont ID  
Sent By rbrown Date 2004-11-03 Time 15:54 Rev Time 0.00
Received By rbrown Date 2004-11-03 Time 15:54 Sent To  
Notes
2004-11-03 00:00:00STRUCTURAL SUBMITTAL ON 11/1/04 FOR 5TH
 FLOOR WEST POOL DECK SLAB POUR LETTERS.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 52 Status P Date 2004-11-03 Cont ID  
Sent By rbrown Date 2004-11-03 Time 14:37 Rev Time 0.00
Received By rbrown Date 2004-11-03 Time 14:37 Sent To  
Notes
2004-11-03 00:00:00STRUCTURAL SUBMITTAL ON 10/20/04 FOR
 ONM&J SKETCH SSK-96.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 51 Status P Date 2004-11-03 Cont ID  
Sent By rbrown Date 2004-11-03 Time 14:27 Rev Time 0.00
Received By rbrown Date 2004-11-03 Time 14:27 Sent To  
Notes
2004-11-03 00:00:00STRUCTURAL SUBMITTAL ON 10/20/04 FOR 5TH
 FLOOR EAST POOL DECK SLAB POUR LETTERS.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 50 Status P Date 2004-11-03 Cont ID  
Sent By rbrown Date 2004-11-03 Time 14:17 Rev Time 0.00
Received By rbrown Date 2004-11-03 Time 14:17 Sent To  
Notes
2004-11-03 00:00:00SUBMITTAL ON 9/24/04 FOR COOLING TOWER
 ANCHORAGE CALCS AND SHOP DRAWINGS.SEE
 MECHANICAL REVIEW DATED 10/25/04.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 49 Status P Date 2004-11-03 Cont ID  
Sent By rbrown Date 2004-11-03 Time 13:47 Rev Time 0.00
Received By rbrown Date 2004-11-03 Time 13:47 Sent To  
Notes
2004-11-03 00:00:00SUBMITTAL ON 9/24/04 FOR MODIFIED
 BITUMEN ROOF SYSTEM PRODUCT DETAILS.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 48 Status P Date 2004-11-02 Cont ID  
Sent By rbrown Date 2004-11-02 Time 14:38 Rev Time 0.00
Received By rbrown Date 2004-11-02 Time 14:38 Sent To  
Notes
2004-11-02 00:00:00STRUCTURAL SUBMITTAL ON 9/24/04 FOR
 WHITE ALUMINUM FABRICATION, INC.
 GUARDRAIL DETAILS/CALC.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 47 Status F Date 2004-10-15 Cont ID  
Sent By rbrown Date 2004-10-15 Time 16:35 Rev Time 0.00
Received By rbrown Date 2004-10-15 Time 16:35 Sent To  
Notes
2004-10-15 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 REVISION SUBMITTED 10/12/04 FOR
 ARCHITECTURAL SHEETS LS1.01, 02, 05, 06
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC 412.6.2SHEET LS1.02, THE MAIN
 ELEVATOR LOBBY IS NOW SHOWN WITH AN
 ADDITIONAL DOOR LEADING TO THE TENANT
 STORAGE.OPENINGS IN THE ELEVATOR LOBBY
 SHALL BE LIMITED TO THOSE REQUIRED FOR
 ACCESS TO THE ELEVATORS.AMEND THE PLAN
 ALSO, THE REVISIONS ARE NOT CLOUDED.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 46 Status P Date 2004-10-15 Cont ID  
Sent By rbrown Date 2004-10-15 Time 16:31 Rev Time 0.00
Received By rbrown Date 2004-10-15 Time 16:31 Sent To  
Notes
2004-10-15 00:00:00STRUCTURAL SUBMITTAL ON 10/12/04 FOR
 WALKER CANVAS AWNINGS, INC SHOP DRAWINGS
 1 AND 2

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 45 Status P Date 2004-10-15 Cont ID  
Sent By rbrown Date 2004-10-15 Time 16:24 Rev Time 0.00
Received By rbrown Date 2004-10-15 Time 16:24 Sent To  
Notes
2004-10-15 00:00:00STRUCTURAL REVISION SUBMITTED ON 10/7/04
 FOR ONM&J SKETCHES SSK 85, TEF 4,10,16,
 SF-1, SF-2 AND RFI 537

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 44 Status P Date 2004-10-15 Cont ID  
Sent By rbrown Date 2004-10-15 Time 16:22 Rev Time 0.00
Received By rbrown Date 2004-10-15 Time 16:22 Sent To  
Notes
2004-10-15 00:00:00STRUCTURAL SUBMITTAL ON 10/7/04 FOR
 ONM&J LETTER DATED 9/30/04 ON HANDRAIL/
 GRAB-BAR TESTING.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 43 Status P Date 2004-10-15 Cont ID  
Sent By rbrown Date 2004-10-15 Time 16:20 Rev Time 0.00
Received By rbrown Date 2004-10-15 Time 16:20 Sent To  
Notes
2004-10-15 00:00:00STRUCTURAL SUBMITTAL ON 10/1/04 FOR
 POUR 1, 5TH FLOOR WEST POOL DECK SLAB
 POUR LETTERS

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 42 Status P Date 2004-10-15 Cont ID  
Sent By rbrown Date 2004-10-15 Time 16:18 Rev Time 0.00
Received By rbrown Date 2004-10-15 Time 16:17 Sent To  
Notes
2004-10-15 00:00:00SUBMITTAL ON 9/29/02 FOR WEITZ CO LETTER
 DATED 9/24/04 ON DRYWALL DAMAGE/REPLACE-
 MENT

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 41 Status P Date 2004-09-21 Cont ID  
Sent By rbrown Date 2004-09-21 Time 14:13 Rev Time 0.00
Received By rbrown Date 2004-09-21 Time 14:13 Sent To  
Notes
2004-09-21 00:00:00STRUCTURAL SUBMITTAL ON 9/20/04 FOR EAST
 5TH FLOOR AMENITIES POOL SLAB POUR
 LETTERS.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 40 Status P Date 2004-09-21 Cont ID  
Sent By rbrown Date 2004-09-21 Time 14:11 Rev Time 0.00
Received By rbrown Date 2004-09-21 Time 14:11 Sent To  
Notes
2004-09-21 00:00:00STRUCTURAL REVISION SUBMITTED ON 9/15/04
 FOR ONM&J SKETCHES SSK-83, 89A AND 94

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 39 Status P Date 2004-09-21 Cont ID  
Sent By rbrown Date 2004-09-21 Time 13:18 Rev Time 0.00
Received By rbrown Date 2004-09-21 Time 13:18 Sent To  
Notes
2004-09-21 00:00:00REVISION SUBMITTED 9/15/04 FOR 3000 PSI
 MASONRY GROUT MIX DESIGN.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 38 Status F Date 2004-09-21 Cont ID  
Sent By rbrown Date 2004-09-21 Time 13:07 Rev Time 0.00
Received By rbrown Date 2004-09-21 Time 13:07 Sent To  
Notes
2004-09-21 00:00:00STRUCTURAL REVISION SUBMITTED ON 9/15/04
 FOR PTE STRAND CO ROOF SLAB POST-TENSION
 SLAB SKECTES AND CALCULATIONS.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 37 Status P Date 2004-09-21 Cont ID  
Sent By rbrown Date 2004-09-21 Time 13:04 Rev Time 0.00
Received By rbrown Date 2004-09-21 Time 13:04 Sent To  
Notes
2004-09-21 00:00:00STRUCTURAL REVISION SUBMITTED ON 9/15/04
 FOR PTE STRAND CO. 5TH FLR WEST POST-
 TENSION SHOP DRAWINGS.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 36 Status P Date 2004-09-21 Cont ID  
Sent By rbrown Date 2004-09-21 Time 11:40 Rev Time 0.00
Received By rbrown Date 2004-09-21 Time 11:40 Sent To  
Notes
2004-09-21 00:00:00STRUCTURAL REVISION SUBMITTED ON 9/1/04
 FOR ONM&J LETTER, DATED 7/15/04, RE: 2ND
 3RD, 4TH FLOOR WEST POST-TENSION SLABS

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 35 Status P Date 2004-09-21 Cont ID  
Sent By rbrown Date 2004-09-21 Time 11:37 Rev Time 0.00
Received By rbrown Date 2004-09-21 Time 11:37 Sent To  
Notes
2004-09-21 00:00:00STRUCTURAL REVISION SUBMITTED ON 8/25/04
 FOR ONM&J SKETCHES SSK-21,58,73,76,84,87

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 34 Status P Date 2004-09-21 Cont ID  
Sent By rbrown Date 2004-09-21 Time 11:32 Rev Time 0.00
Received By rbrown Date 2004-09-21 Time 11:31 Sent To  
Notes
2004-09-21 00:00:00STRUCTURAL SUBMITTAL ON 8/23/04 FOR
 POUR 2, WEST GARAGE ROOF POUR LETTERS

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 33 Status F Date 2004-09-21 Cont ID  
Sent By rbrown Date 2004-09-21 Time 10:15 Rev Time 0.00
Received By rbrown Date 2004-09-21 Time 10:15 Sent To  
Notes
2004-09-21 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 REVISION SUBMITTED 8/23/04 FOR DOORS
 L1-23A THROUGH L1-27A LOUVERED DOOR
 PRODUCT APPROVALS.
  
 1) THE PRODUCT APPROVAL WAS BROUGHT IN
 AS A SUBMITTAL.IT IS A REVISION AND
 THE APPROPRIATE FEE IS $60.
  
 2) DESIGN WIND PRESSURES.DRAWING SHEET
 1 OF THE SUBMITTED INGERSOLL-RAND
 LOUVERED DOOR PRODUCT APPROVAL NOA#
 03-0327.02 STATES THAT THE DESIGN
 PRESSURE RATING IS +60 PSF / -60 PSF.
 THE PEAK POSITIVE AND NEGATIVE PRESSURES
 FROM STRUCTURAL PLAN SHEETS S-22 AND
 S-23 ARE +70 PSF AND -70 PSF.SUBMIT
 A PRODUCT APPROVAL FOR DOORS WITH A
 DESIGN PRESSURE RATING THAT EXCEEDS THE
 PEAK POSITIVE AND NEGATIVE PRESSURES.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 32 Status P Date 2004-08-19 Cont ID  
Sent By rbrown Date 2004-08-19 Time 10:50 Rev Time 0.00
Received By rbrown Date 2004-08-19 Time 10:50 Sent To  
Notes
2004-08-19 00:00:00STRUCTURAL SUBMITTAL ON 8/17/04 FOR
 ONM&J LETTER, DATED 8/12/04,
 RE: POUR 1 - ROOF LVL POST-TENSION SLAB

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 31 Status P Date 2004-08-19 Cont ID  
Sent By rbrown Date 2004-08-19 Time 10:41 Rev Time 0.00
Received By rbrown Date 2004-08-19 Time 10:41 Sent To  
Notes
2004-08-19 00:00:00STRUCTURAL SUBMITTAL ON 8/17/04 FOR
 ROOF LEVEL SLAB (EAST SIDE) REVISED
 SHORING SKETCHES 1 TO 4.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 30 Status P Date 2004-08-12 Cont ID  
Sent By rbrown Date 2004-08-12 Time 14:14 Rev Time 0.00
Received By rbrown Date 2004-08-12 Time 14:14 Sent To  
Notes
2004-08-12 00:00:00STRUCTURAL SUBMITTAL ON 8/12/04 FOR
 POUR 2, ROOF SLAB POUR LETTERS

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 29 Status P Date 2004-08-12 Cont ID  
Sent By rbrown Date 2004-08-12 Time 13:38 Rev Time 0.00
Received By rbrown Date 2004-08-12 Time 13:38 Sent To  
Notes
2004-08-12 00:00:00STRUCTURAL SUBMITTAL ON 8/12/04 FOR
 BROMLEY COOK CLARIFICATION LETTERS,
 DATED 7/29/04, RE: GROUT UNDER SLIDING
 DOOR TRACKS AND BUILDING OUT OF WINDOW/
 DOOR OPENINGS.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 28 Status P Date 2004-08-12 Cont ID  
Sent By rbrown Date 2004-08-12 Time 13:35 Rev Time 0.00
Received By rbrown Date 2004-08-12 Time 13:35 Sent To  
Notes
2004-08-12 00:00:00STRUCTURAL SUBMITTAL ON 8/11/04 FOR
 ONM&J LETTER, DATED 8/3/04,
 RE: POUR 2, 17TH FLOOR POST-TENSION SLAB

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 27 Status P Date 2004-08-05 Cont ID  
Sent By rbrown Date 2004-08-05 Time 15:27 Rev Time 0.00
Received By rbrown Date 2004-08-05 Time 15:27 Sent To  
Notes
2004-08-05 00:00:00STRUCTURAL SUBMITTAL ON 8/5/04 FOR
 POUR 1, ROOF SLAB POUR LETTERS

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 26 Status P Date 2004-08-05 Cont ID  
Sent By rbrown Date 2004-08-05 Time 15:24 Rev Time 0.00
Received By rbrown Date 2004-08-05 Time 15:24 Sent To  
Notes
2004-08-05 00:00:00STRUCTURAL SUBMITTAL ON 8/2/04 FOR
 ONM&J LETTER, DATED 8/4/04,
 RE: POUR 1, 17TH FLOOR POST-TENSION SLAB

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 25 Status P Date 2004-07-29 Cont ID  
Sent By rbrown Date 2004-07-29 Time 10:07 Rev Time 0.00
Received By rbrown Date 2004-07-29 Time 10:07 Sent To  
Notes
2004-07-29 00:00:00STRUCTURAL SUBMITTAL ON 7/28/04 FOR 4TH
 FLOOR WEST PARKING SLAB POUR LETTERS

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 24 Status P Date 2004-07-29 Cont ID  
Sent By rbrown Date 2004-07-29 Time 10:05 Rev Time 0.00
Received By rbrown Date 2004-07-29 Time 10:05 Sent To  
Notes
2004-07-29 00:00:00STRUCTURAL SUBMITTAL ON 7/27/04 FOR
 POUR 2, 17TH FLOOR SLAB, POUR LETTERS

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 23 Status P Date 2004-07-29 Cont ID  
Sent By rbrown Date 2004-07-29 Time 09:58 Rev Time 0.00
Received By rbrown Date 2004-07-29 Time 09:58 Sent To  
Notes
2004-07-29 00:00:00STRUCTURAL SUBMITTAL ON 7/22/04 FOR
 PRO-BEL WINDOW CLEANING SAFETY SYSTEM
 DRAWING NO 1.01

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 22 Status P Date 2004-07-29 Cont ID  
Sent By rbrown Date 2004-07-29 Time 09:55 Rev Time 0.00
Received By rbrown Date 2004-07-29 Time 09:55 Sent To  
Notes
2004-07-29 00:00:00STRUCTURAL SUBMITTAL ON 7/20/04 FOR
 JENKINS & CHARLAND LETTER DATED 7/14/04
 ON STAIR FRAMING

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 21 Status P Date 2004-07-29 Cont ID  
Sent By rbrown Date 2004-07-29 Time 09:49 Rev Time 0.00
Received By rbrown Date 2004-07-29 Time 09:49 Sent To  
Notes
2004-07-29 00:00:00STRUCTURAL SUBMITTAL ON 7/20/04 FOR
 ONM&J LETTER, DATED 7/16/04,
 RE: POUR 2, 16TH FLOOR POST-TENSION SLAB

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 20 Status P Date 2004-07-28 Cont ID  
Sent By rbrown Date 2004-07-29 Time 09:46 Rev Time 0.00
Received By rbrown Date 2004-07-28 Time 09:48 Sent To  
Notes
2004-07-29 00:00:00STRUCTURAL SUBMITTAL ON 7/20/04 FOR
 POUR 1, 17TH FLOOR SLAB, POUR LETTERS

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 19 Status P Date 2004-07-21 Cont ID  
Sent By rbrown Date 2004-07-21 Time 17:20 Rev Time 0.00
Received By rbrown Date 2004-07-21 Time 17:20 Sent To  
Notes
2004-07-21 00:00:00STRUCTURAL SUBMITTAL ON 7/12/04 FOR
 POUR 2, 16TH FLOOR POUR LETTERS

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 18 Status P Date 2004-07-21 Cont ID  
Sent By rbrown Date 2004-07-21 Time 17:19 Rev Time 0.00
Received By rbrown Date 2004-07-21 Time 17:18 Sent To  
Notes
2004-07-21 00:00:00STRUCTURAL SUBMITTAL ON 7/14/04 FOR
 ONM&J LETTER, DATED 7/13/04,
 RE: POUR 1, 16TH FLOOR POST-TENSION SLAB

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 17 Status P Date 2004-07-21 Cont ID  
Sent By rbrown Date 2004-07-21 Time 17:17 Rev Time 0.00
Received By rbrown Date 2004-07-21 Time 17:17 Sent To  
Notes
2004-07-21 00:00:00STRUCTURAL SUBMITTAL ON 7/14/04 FOR
 ONM&J LETTER, DATED 7/7/04,
 RE: POUR 2, 15TH FLOOR POST-TENSION SLAB

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 16 Status P Date 2004-07-21 Cont ID  
Sent By rbrown Date 2004-07-21 Time 17:16 Rev Time 0.00
Received By rbrown Date 2004-07-21 Time 17:16 Sent To  
Notes
2004-07-21 00:00:00STRUCTURAL SUBMITTAL ON 7/14/04 FOR
 ONM&J LETTER, DATED 7/1/04,
 RE: 3RD FLOOR POST-TENSION SLAB

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 15 Status P Date 2004-07-21 Cont ID  
Sent By rbrown Date 2004-07-21 Time 17:13 Rev Time 0.00
Received By rbrown Date 2004-07-21 Time 17:13 Sent To  
Notes
2004-07-21 00:00:00STRUCTURAL SUBMITTAL ON 7/14/04 FOR
 ONM&J SKETCHES FOR MECH/PLUMBING EQUIP
 STANDS.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 14 Status P Date 2004-07-09 Cont ID  
Sent By rbrown Date 2004-07-09 Time 12:03 Rev Time 0.00
Received By rbrown Date 2004-07-09 Time 12:02 Sent To  
Notes
2004-07-09 00:00:00STRUCTURAL SUBMITTAL ON 6/30/04 FOR
 POUR 1, 16TH FLOOR POUR LETTERS

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 13 Status P Date 2004-07-09 Cont ID  
Sent By rbrown Date 2004-07-09 Time 12:01 Rev Time 0.00
Received By rbrown Date 2004-07-09 Time 12:01 Sent To  
Notes
2004-07-09 00:00:00STRUCTURAL SUBMITTAL ON 6/30/04 FOR
 POUR 2, 15TH FLOOR POUR LETTERS

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2004-07-09 Cont ID  
Sent By rbrown Date 2004-07-09 Time 11:59 Rev Time 0.00
Received By rbrown Date 2004-07-09 Time 11:59 Sent To  
Notes
2004-07-09 00:00:00STRUCTURAL SUBMITTAL ON 6/30/04 FOR
 ONM&J LETTER, DATED 6/29/04,
 RE: POUR 1, 15TH FLOOR POST-TENSION SLAB

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2004-07-09 Cont ID  
Sent By rbrown Date 2004-07-09 Time 11:57 Rev Time 0.00
Received By rbrown Date 2004-07-09 Time 11:57 Sent To  
Notes
2004-07-09 00:00:00STRUCTURAL SUBMITTAL ON 6/30/04 FOR
 ONM&J LETTER, DATED 6/23/04,
 RE: POUR 2, 14TH FLOOR POST-TENSION SLAB

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2004-07-09 Cont ID  
Sent By rbrown Date 2004-07-09 Time 11:55 Rev Time 0.00
Received By rbrown Date 2004-07-09 Time 11:55 Sent To  
Notes
2004-07-09 00:00:00STRUCTURAL SUBMITTAL ON 6/30/04 FOR
 ONM&J LETTER, DATED 6/15/04,
 RE: 2ND FLOOR POST-TENSION SLAB

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2004-06-29 Cont ID  
Sent By rbrown Date 2004-06-29 Time 11:05 Rev Time 0.00
Received By rbrown Date 2004-06-29 Time 11:05 Sent To  
Notes
2004-06-29 00:00:00STRUCTURAL SUBMITTAL ON 6/28/04 FOR
 3RD FLOOR SLAB WEST POUR LETTERS

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2004-06-29 Cont ID  
Sent By rbrown Date 2004-06-29 Time 11:01 Rev Time 0.00
Received By rbrown Date 2004-06-29 Time 11:01 Sent To  
Notes
2004-06-29 00:00:00STRUCTURAL SUBMITTAL ON 6/24/04 FOR
 POUR 1, 15TH FLOOR POUR LETTERS

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2004-06-29 Cont ID  
Sent By rbrown Date 2004-06-29 Time 10:56 Rev Time 0.00
Received By rbrown Date 2004-06-29 Time 10:56 Sent To  
Notes
2004-06-29 00:00:00STRUCTURAL SUBMITTAL ON 6/24/04 FOR
 PTE STRAND ROOF LEVEL POST-TENSION SLAB
 PLANS

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-06-21 Cont ID  
Sent By rbrown Date 2004-06-21 Time 13:59 Rev Time 0.00
Received By rbrown Date 2004-06-21 Time 13:59 Sent To  
Notes
2004-06-21 00:00:00STRUCTURAL SUBMITTAL ON 6/18/04 FOR
 POUR 2, 14TH FLOOR POUR LETTERS

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-06-17 Cont ID  
Sent By rbrown Date 2004-06-17 Time 13:30 Rev Time 0.00
Received By rbrown Date 2004-06-17 Time 13:29 Sent To  
Notes
2004-06-17 00:00:00STRUCTURAL SUBMITTAL ON 6/16/04 FOR
 RINKER CONCRETE MIX DESIGN LETTER DATED
 6/2/04.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-06-17 Cont ID  
Sent By rbrown Date 2004-06-17 Time 13:19 Rev Time 0.00
Received By rbrown Date 2004-06-17 Time 13:19 Sent To  
Notes
2004-06-17 00:00:00STRUCTURAL SUBMITTAL ON 6/16/04 FOR
 ONM&J LETTER DATED 6/10/04 ON POST-
 TENSION CABLES.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-06-15 Cont ID  
Sent By rbrown Date 2004-06-15 Time 16:15 Rev Time 0.00
Received By rbrown Date 2004-06-15 Time 16:15 Sent To  
Notes
2004-06-15 00:00:00STRUCTURAL SUBMITTAL ON 6/14/04 FOR
 POUR 1, 14TH FLOOR SLAB POUR LETTERS.

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-06-15 Cont ID  
Sent By rbrown Date 2004-06-15 Time 16:07 Rev Time 0.00
Received By rbrown Date 2004-06-15 Time 16:07 Sent To  
Notes
2004-06-15 00:00:00STRUCTURAL SUBMITTAL ON 6/10/04 FOR
 ONM&J SKETCH SHEETS SSK 85 AND SSK 86

Review Stop B1 BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-06-15 Cont ID  
Sent By rbrown Date 2004-06-15 Time 15:45 Rev Time 0.00
Received By rbrown Date 2004-06-15 Time 15:44 Sent To  
Notes
2004-06-15 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 STRUCTURAL SUBMITTAL ON 6/10/04 FOR
 PTE STRAND CO,INC. POST-TENSION DRAWINGS
 - 5TH FLOOR WEST POST-TENSION SLAB.
  
 --PROVISO--
 COMPLY WITH THE ENGINEER OF RECORD'S
 COMMENTS.ADDRESS THE COMMENTS IN ONM&J
 LETTER DATED 6/1/04.

Review Stop E ELECTRICAL
Rev No 21 Status P Date 2005-06-15 Cont ID  
Sent By dpalmer Date 2005-06-15 Time 11:48 Rev Time 0.30
Received By dpalmer Date 2005-06-15 Time 11:48 Sent To  
Notes
2005-06-15 00:00:00REVISION FOR COOKING RANGE CONNECTIONS,
 ETC FOR PANELS WITHIN SIGHT.

Review Stop E ELECTRICAL
Rev No 20 Status P Date 2005-05-19 Cont ID  
Sent By dpalmer Date 2005-05-19 Time 06:46 Rev Time 0.50
Received By dpalmer Date 2005-05-19 Time 06:46 Sent To  
Notes
2005-05-19 00:00:00REV TO REMOVE JP UNIT PH 1/18 FROM PLANS
 UNDER MAIN BLDG ELEC. THIS IS UNDER A
 SEPARATE PERMIT.
  
 REV'S FOR 6,6.1,6.2
 REV'S ON 4- 81/2X11'S.

Review Stop E ELECTRICAL
Rev No 19 Status F Date 2005-04-18 Cont ID  
Sent By dpalmer Date 2005-04-18 Time 15:37 Rev Time 0.20
Received By dpalmer Date 2005-04-18 Time 15:37 Sent To  
Notes
2005-04-18 00:00:00****** UNSAT ******
  
 1)NOTE: PLEASE SEE DETAIL FOR COOKING
 DOES NOT SHOW A DISC MEANS AS REQUIRED.
 422.31
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 18 Status P Date 2005-04-18 Cont ID  
Sent By dpalmer Date 2005-04-18 Time 14:24 Rev Time 0.50
Received By dpalmer Date 2005-04-18 Time 14:24 Sent To  
Notes
2005-04-18 00:00:00REV FOR PARKING LEVEL 1 .

Review Stop E ELECTRICAL
Rev No 17 Status P Date 2005-04-18 Cont ID  
Sent By dpalmer Date 2005-04-18 Time 13:25 Rev Time 0.30
Received By dpalmer Date 2005-04-18 Time 13:24 Sent To  
Notes
2005-04-18 00:00:00REVISION FOR RECEPTS ON CATV/TELE RM
 ONLY.

Review Stop E ELECTRICAL
Rev No 16 Status P Date 2005-03-10 Cont ID  
Sent By dpalmer Date 2005-03-10 Time 16:49 Rev Time 0.25
Received By dpalmer Date 2005-03-10 Time 16:48 Sent To  
Notes
2005-03-10 00:00:00REV FOR PARTY RM LIGHTING LAYOUT ONLY.

Review Stop E ELECTRICAL
Rev No 15 Status N Date 2005-02-08 Cont ID  
Sent By dpalmer Date 2005-02-08 Time 08:59 Rev Time 0.00
Received By dpalmer Date 2005-02-08 Time 08:59 Sent To  
Notes
2005-02-08 00:00:00NO REVIEW DONE, PLANS SUBMITTED DO NOT
 CORRELATE WITH JOBSITE WORK PER DAN
 KEMPA ELECTRICAL INSPECTOR.

Review Stop E ELECTRICAL
Rev No 14 Status N Date 2004-12-29 Cont ID  
Sent By dpalmer Date 2004-12-29 Time 10:55 Rev Time 0.25
Received By dpalmer Date 2004-12-29 Time 10:55 Sent To  
Notes
2004-12-29 00:00:00LTR FOR GROUNDING OF TRANSFORMER SENT TO
 JAKE FOR REVIEW.
 LTR ADDRESSED TO THE CHEIF ELECTRICAL
 INSPEC.
  
 250.30

Review Stop E ELECTRICAL
Rev No 13 Status P Date 2004-12-14 Cont ID  
Sent By dpalmer Date 2004-12-14 Time 09:12 Rev Time 0.33
Received By dpalmer Date 2004-12-14 Time 09:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 12 Status P Date 2004-10-08 Cont ID  
Sent By dpalmer Date 2004-10-08 Time 07:48 Rev Time 0.33
Received By dpalmer Date 2004-10-08 Time 07:48 Sent To FIRE
Notes
2004-10-08 00:00:00REV FOE E-1 AND E-12 ONLY

Review Stop E ELECTRICAL
Rev No 11 Status F Date 2004-10-06 Cont ID  
Sent By dpalmer Date 2004-10-06 Time 18:50 Rev Time 0.25
Received By dpalmer Date 2004-10-06 Time 18:50 Sent To  
Notes
2004-10-06 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE NOTES FROM REVIEW #10
 FOR REQUIRED DISCONNECTING MEANS OF
 COOKING EQUIPMENT. SEE DETAIL #2.
 422.30-33
  
 2)NOTE: PLEASE SEE RECEPT IN CLOTHES
 CLOSET. PLEASE SEE CLEARENCE MUST BE
 MAINTAINED FOR ANY TRANSFORMER(S) ETC
 BEING PLUGGED INTO RECEPT. RECEPT MAY BE
 PLACED OVER DOOR.
 110.26/
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2004-09-21 Cont ID  
Sent By dpalmer Date 2004-09-21 Time 10:23 Rev Time 0.25
Received By dpalmer Date 2004-09-21 Time 10:23 Sent To  
Notes
2004-09-21 00:00:00PHOTOMETRICS ONLY.

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2004-09-21 Cont ID  
Sent By dpalmer Date 2004-09-21 Time 08:11 Rev Time 1.00
Received By dpalmer Date 2004-09-21 Time 08:10 Sent To  
Notes
2004-09-21 00:00:00******** UNSAT ***********
  
 PLEASE SEE REVISIONS FOR SHEETS :
 E-1,5,8,E-8A-CU, E-9A-CU, E9-10.
  
 PLEASE SEE COMMENTS/REDLINESFROM PREV-
 -IOUS REVIEWS.
  
 1)NOTE: PLEASE SEE "DETAIL #2" FOR
 COOKING EQUIPMENT. THIS SHOWS BOTH UNITS
 BEING CONNECTED TO A "J-BOX" WITH NO
 DISCONNECTING MEANS. PLEASE SEE SOME
 UNITS PANEL IS W/IN SITE, YET SOME ARE
 NOT. PLEASE SEE 422.30,31,33 ETC FOR
 REQUIRED MEANS OF DICONNECT.
  
 2)NOTE: PLEASE ALSO SEE SAME "DETAIL #2"
 WHICH DOES NOT INDICATE ANY NEUTRAL
 CONDUCTOR AS REQUIRED UNDER 250.140.
  
 3)NOTE: PLEASE SEE REVISION FOR RFI-323,
 WHICH HAS INCLUDED LTS AND SD'S ON ARC-
 -FAULT PROTECTED BRKRS.THIS IS OK, HOW-
 -EVER, NOTE FOR ARC FAULT PROTECTION
 "**" ONLY INDICATES RECEPTS. THIS APPEAR
 -S TO JUST BE A NOTE THAT HAS NOT BEEN
 REVISED YET?
  
 4)NOTE: PLEASE SEE RESPONSE LETTER FROM
 FES DATED AUGUST 20, 2004 FROM MARVIN
 SANCHEZ. NOTE(RESPONSE) # 4 MENTIONS BLD
 DEPARTMENT COMMENTS: DINING RM RECEPTS
 HAS BEEN CHANGED TO ARC FAULT PROTECTION
 ??? PLEASE VERIFY COMMENT AND/OR WHERE/
 WHY THIS CHANGE WAS MADE. DINING RM
 RECEPTS ARE NOT REQUIRED TO BE ARC FAULT
 PROTECTED, UNLESS SO DESIRED.
  
 PLEASE SEE OTHER COMMENTS FROM OTHER
 REVIEWERS WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2004-09-21 Cont ID  
Sent By dpalmer Date 2004-09-21 Time 08:06 Rev Time 0.25
Received By dpalmer Date 2004-09-21 Time 07:27 Sent To  
Notes
2004-09-21 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE LETTER FOR CONNECTION
 OF ELEVATOR TRANSFORMERS TO BLDG STEEL.
 PLEASE SEE TITLE BLOCK ON SIGNED AND
 SEALED LETTER IS REQUIRED TO HAVE ALL
 LICENSE #'S AS SET FORTH IN FAC 61G15-23
 .002.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2004-07-27 Cont ID  
Sent By dpalmer Date 2004-07-27 Time 13:09 Rev Time 0.33
Received By dpalmer Date 2004-07-27 Time 13:09 Sent To  
Notes
2004-07-27 00:00:00REV FOR COMBO UNITS ONLY. 9TH AND 11TH
 FLRS.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2004-07-19 Cont ID  
Sent By dpalmer Date 2004-07-19 Time 19:05 Rev Time 1.50
Received By dpalmer Date 2004-07-19 Time 18:33 Sent To  
Notes
2004-07-19 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE SEE PREVIOUS NOTES.
 PLEASE SEE SHEET E-13, THIS SHEETS HAS
 NOT BEEN CORRECTED??
  
 PLEASE SEE REVISIONS NOW MADE
 TO OTHER SHEETS SINCE LAST REVIEW AND
 NEW COMMENTS HAVE BEEN GENERATED.
  
 1)NOTE: PLEASE SEE DEATIL FOR KITCHEN
 COOKING EQUIPMENT. PLEASE SEE 250.140
 FOR RANGES TEC.
 # OF CONDUCTORS?
 PLEASE ALSO SEE SPECS ON EQUIPMENT AND
 MEANS OF DISC THAT MAY BE REQUIRED.
 SHOWN TO J-BOX WITH NO MEANS OF DISC?
 NOT ALL PANELS ARE W/IN "SIGHT" OF UNITS
 ??
  
 2)NOTE: PLEASE SEE E-8A-CU SHOWS DINING
 RM W/ GEN RECEPT CIRCUIT? PLEASE SEE
 210.52B-3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2004-05-25 Cont ID  
Sent By dpalmer Date 2004-05-25 Time 10:08 Rev Time 4.00
Received By dpalmer Date 2004-05-24 Time 11:44 Sent To  
Notes
2004-05-25 00:00:00**** UNSAT ******
  
 1)NOTE: PLEASE CORRELATE ALL REVISIONS
 AS NOTED ON TITLE BLOCK WITH PLANS.
 SOME SHOWN AS BLANK?
 SOME WHERE REVISION # IS ON PLAN BUT NOT
 LISTED ON REV/TITLE BLOCK.?
  
 2)NOTE: PLEASE SHOW ALL LARGEST MOTORS
 AT 125%.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-07-31 Cont ID  
Sent By dpalmer Date 2003-07-31 Time 06:34 Rev Time 1.25
Received By dpalmer Date 2003-07-31 Time 06:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-07-22 Cont ID  
Sent By dpalmer Date 2003-07-22 Time 14:26 Rev Time 2.00
Received By dpalmer Date 2003-07-22 Time 14:25 Sent To  
Notes
2003-07-22 00:00:00*********** UNSAT ************
  
 1)NOTE: PLEASE NOTE, I AM UNABLE TO A
 COMPLETE PLAN REVIEW AT THIS TIME.
 THE SETS OS PLANS ARE NOT COMPLETE AND
 ARE MISSING E-13 WHICH IS MOST OF THE
 COMMENTS FORM OTHERS REVIEWS.
  
 PLEASE SUBMIT COMPLETE SETS FOR REVIEW.
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
 PLEASE ALSO HAVE NEW SHEETS SIGNED ,
 DATED AND SEALED PER FS 471.025
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-05-01 Cont ID  
Sent By dpalmer Date 2003-05-01 Time 06:55 Rev Time 5.00
Received By dpalmer Date 2003-05-01 Time 06:55 Sent To  
Notes
2003-05-01 00:00:00********* UNSAT **********
  
 1)NOTE: PLEASE SEE E-1, THERE ARE FEEDER
 /CONDUIT NOTES FOR MAINS 1 ETC. NOTES
 MENTION SEE "NOTE 7&9?ON WHICH PAGE
 WOULD THIS BE?
  
 2)NOTE: PLEASE SEE RISER DIAGRAM AND
 E-1. E-1 SEEMS TO SHOW MAIN #2 AS BUS
 STAB AND RISER SHOWS CONDUIT/FEEDERS?
 PLEASE CORRELAT/CLARIFY.
  
 3)NOTE: PLEASE SEE E-1, SHOWS MULTIPLE
 LINES COMING FROM HDP, RISER ONLY SHOWS
 2LINES COMING OUT AND GOING UP TO ROOF.?
 CONDUITS THAT APPEAR TO COME FROM XDP
 ON RISER DIAGRAM SEEM TO BE SHOWN COMING
 FROM HDP ON E-1? PLEASE CORRELATE. PANEL
 HB? ETC
 4)NOTE: PLEASE SEE E-13, IT APPEARS TO
 SHOW FEEDERS FOR MAIN 3 COMING OVERHEAD.
 PLEASE NOTE, AS PER LOCAL AMENDMENTS,
 NO MORE THAN 8' OF UNPROTECTED CONDUCTOR
 -S ARE PERMITTED INTO BLDG. PLEASE SHOW
 AS EITHER UNDERGROUND OR COMPLETE CONCR-
 -ETE ENCASEMENT. 230-70 LOCAL AMEND.
  
 5)NOTE: PLEASE CLARIFY FIXTURE TYPE FOR
 ELEVATOR EQUIPMENT ROOM AND OTHER ROOMS
 THAT REQUIRE EMERGENCY LIGHTING REQ`D TO
 MEET 700-16? SOME OTHER LOCATIONS SHOW
 ROOMS AND TYPE OF FIXTURES REFERENCE
 BACK TO FIXTURE SCHEDULE.FIX SCH, DETAIL
 -S DUAL BALLAST/BULBS.
  
 6)NOTE: PLEASE SEE E-8, SHOWS RECEPT
 ADDED TO SERVE KITCHEN COUNTER PENINSUL-
 -AR. HOWEVER SHOWN ON LIVING ROOM CIR-
 -CUIT? PLEASE SEE 210-11,210-52 220-16
 ETC. MUST BE ON W/SMALL APPLAIANCE."A-3"
 PLEASE ALSO CLARIFY HOW THE CIRCUIT #`S
 ARE SHOWN AS THE SAME W/ AN A&B?
  
 7)NOTE: PLEASE NOTE, OCP FOR FIRE PUMP
 TO BE PER 695-4B-1 ALSO SEE NOTE 12
  
 8)NOTE: PLEASE CLARIFY SIZE OF MAIN 4OF4
 FEEDS 1000A PANEL AC ON ROOF.
  
 9)NOTE: PLEASE CORRELATE FEEDERS NOTED
 ON BOTTOM OF LOAD CALCS FOR UNITS ON
 E-8,9,10 WITH RISER DIAGRAM. RISER SHOWS
 3-#1'S ETC AND FEEDERS NOTED AT #2'S?
  
 10)NOTE: PLEASE CLARIFY HOW POWER IS
 TRANSFERED OVER FROM FPL TO GENERATOR
 FOR FIRE PUMP? PLEASE ALSO SEE RISER
 DIAGRAM, SHOWS POWER FROM FPL TO EM MAIN
 AND THEN TO X-FER SWITCH, WHICH IS FINE,
 HOWEVER, SHOWS POWER COMING FROM
 GENERATOR TO EM MAIN? PLEASE CLARIFY HOW
 THE POWER WOULD BE TRANSFERED AT THIS
 LOCATION. HOW WOULD THIS KEEP POWER
 BEING ON EQUIPMENT AT THE SAME TIME
 FROM TWO DIFFERENT SOURCES W/OUT GOING
 THROUGH TRANSFER SWITCH?
  
 11)NOTE: PLEASE SEE NOTE/WIRE/CONDUIT
 ON RISER DIAGRAM FOR FROM 1000A BRKR
 ON GENERATOR.
  
 12)NOTE: PLEASE SHOW/CLARIFY MEANS OF
 DISC REQ`D FOR FIRE PUMP. PLEASE NOTE,
 SHOW A MANUAL MEANS REQ`D, 225-31
 230-76, 230-79, FOR DISC MEANS.
 PLEASE CLARIFY IF THERE WILL BE A MANUAL
 MEANS OF DISC AND/OR TRANSFER SWITCH
 LOCATED WITH/ON SERVICE ENTRANCE RATED
 EQUIPMENT/CONTROLLER FOR FIRE PUMP.
  
 13)NOTE: PLEASE SEE GENERATOR NOTES,
 NOTES MENTION A 600A AND 400A BRKR ON
 GENERATOR AND ELECTRICAL RISER DIAGRAM
 EQUIPMENT NOTES, MENTION 500A AND 1000A
 OCP.? PLEASE CORRELATE.
  
  
 PLEASE NOTE, A RESPONSE LETTER FROM
 ELECTRICAL ENGINEER WILL HELP WITH
 CLARIFICATIONS OF SOME COMMENTS ETC.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL. IF A MEETING ON PHONE OR
 IN PERSON IS NEEDED, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-03-03 Cont ID  
Sent By dpalmer Date 2003-03-03 Time 06:05 Rev Time 6.00
Received By dpalmer Date 2003-03-03 Time 05:54 Sent To  
Notes
2003-03-03 00:00:00********** UNSAT ******************
  
 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 THAT WILL AFFECT ELECTRICAL DRAWINGS.
  
 2)NOTE: PLEASE PROVIDE CIRCUITING ON
 ALL SHEETS. EACH PARKING LEVEL AND OTHER
 SHEETS MISSING CIRCUIT #`S.
  
 3)NOTE: PLEASE CLARIFY TWO DIFFERENT
 POOL EQUIPMENT ROOMS?E-4 PLEASE CALRIFY
 IF THERE IS MORE THANONE POOL?
  
 4)NOTE: PLEASE CLARIFY EM LTS FOR
 BATHS LEVEL 5 AMENITIES.
  
 5)NOTE: PLEASE NOTE ON E-8, SD`S TO BE
 5' FROM RA'S PER MANFACT. SPECS
  
 6)NOTE: PLEASE SEEMASTER BATHS, GFI'S
 3'MIN FROM SINK. 210-52D
  
 7)NOTE: PLEASE SEE MISSING PENINSULAR
 RECEPTS ON VARIOUS UNITS. 210-52-C-3,4
  
 8)NOTE: PLEASE COMPLETE PANEL SCHEULES,
 SHOWN AS BLANKS STARTING ON E-12??
  
 9)NOTE: PLEASE COMPLETE RISER DIAGRAM
 FOR A COMPLETE REVIEW TO BE PERFORMED.
 PLEASE NOTE, THERE MAY BE OTHER COMMENTS
 TO FOLLOW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2005-06-24 Cont ID  
Sent By mamini Date 2005-06-24 Time 09:50 Rev Time 0.50
Received By mamini Date 2005-06-24 Time 09:50 Sent To B
Notes
2005-06-24 00:00:00PASSED:
  
 1. THE TWO SHEETS, CIVIL' REVISIONS THAT
 WERE BROUGHT IN UNDER THIS PERMIT
 FILED WITH UTILITY PERMIT # 03040815.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2003-04-14 Cont ID  
Sent By mamini Date 2003-04-14 Time 09:38 Rev Time 1.00
Received By mamini Date 2003-04-14 Time 09:38 Sent To  
Notes
2003-04-14 00:00:00PASSED:
 1. SEE PERMIT # 03040815 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2003-02-21 Cont ID  
Sent By mamini Date 2003-02-21 Time 10:14 Rev Time 3.00
Received By mamini Date 2003-02-21 Time 10:14 Sent To  
Notes
2003-02-21 00:00:00FAILED :
 1. PLEASE NOTE THAT A SEPARATE PERMIT
 APPLICATION AND FEES FOR THE UNDERGROUND
 UTILITIES AND SITE WORKS AT THE TIME OF
 ACTUAL PERMITTING WILL BE REQUIRED.
 2. FIVE (5) PLANTERS ALONG N. FLAGLER DR
 MUST BE MOVED TO THE BACK OF CURB AND
 GUTTER, PER PLANNING DEPARTMENT.
 3. PLEASE PROVIDE A SANITARY MANHOLE
 ON LATERAL PRIOR TO CONNECTION TO 8"
 SANITARY, ON THE PROPERTY, PER UTILITY
 DEPARTMENT.
 4. PLEASE COORDINATE WITH MECHANICAL
 ENGINEER REGARDING THE FIRE LINE SIZE.
 5. PLEASE SHOW THE WIDTH FOR THE
 PARALLEL PARKINGS ALONG SOUTH LAKESIDE
 COURT, MIN. OF 8' IS REQUIRED.
 6. GREASE / WATER SEPARATOR FOR THE
 PROPOSED RESTAURANTS MAY BE REQUIRED,
 PLEASE CINTACT MR. RODNEY COMPO AT
 837-4051 EXT. 4074 FOR THIS REQUIREMENTS
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 15 Status P Date 2005-06-01 Cont ID  
Sent By mwennerg Date 2005-06-01 Time 13:42 Rev Time 0.00
Received By mwennerg Date 2005-06-01 Time 13:42 Sent To  
Notes
2005-06-01 00:00:00REVISION DATED 5/6/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 14 Status P Date 2005-04-20 Cont ID  
Sent By mwennerg Date 2005-04-20 Time 14:46 Rev Time 0.00
Received By mwennerg Date 2005-04-20 Time 14:46 Sent To  
Notes
2005-04-20 00:00:00REVISION DATED- 3/30/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 13 Status P Date 2005-02-28 Cont ID  
Sent By nmccray Date 2005-02-28 Time 14:39 Rev Time 0.00
Received By nmccray Date 2005-02-28 Time 14:39 Sent To B
Notes
2005-02-28 00:00:00SMOKE BOMB SUDMITTAL 02-25-05
 SENT TO R BROWN

Review Stop FIRE FIRE DEPARTMENT
Rev No 12 Status P Date 2004-11-22 Cont ID  
Sent By nmccray Date 2004-11-22 Time 13:36 Rev Time 0.00
Received By nmccray Date 2004-11-22 Time 13:35 Sent To  
Notes
2004-11-22 00:00:00REVISION DATED 10-27-04

Review Stop FIRE FIRE DEPARTMENT
Rev No 11 Status P Date 2004-10-18 Cont ID  
Sent By nmccray Date 2004-10-18 Time 11:14 Rev Time 0.00
Received By nmccray Date 2004-10-18 Time 11:14 Sent To  
Notes
2004-10-18 00:00:00REVISION DATED 9-23-04 E-1 & E-12

Review Stop FIRE FIRE DEPARTMENT
Rev No 10 Status P Date 2004-10-13 Cont ID  
Sent By mcarsill Date 2004-10-13 Time 17:23 Rev Time 0.00
Received By mcarsill Date 2004-10-13 Time 17:22 Sent To  
Notes
2004-10-13 00:00:001) SEPARATE PLANS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER REMODEL.
  
 2) A FIRE SPRINKLER HEAD IS REQUIRED
 IN THE O2 CLOSET.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 9 Status F Date 2004-09-22 Cont ID  
Sent By nmccray Date 2004-09-22 Time 10:54 Rev Time 0.00
Received By nmccray Date 2004-09-22 Time 10:54 Sent To  
Notes
2004-09-22 00:00:00***********DENIED***********************
 THESE REVISIONS ALSO NEED TO BE
 SUBMITTED WITH THE FIRE SPRINKLER SHOP
 DRAWINGS PERMITTED UNDER 04070258
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status P Date 2004-08-13 Cont ID  
Sent By mcarsill Date 2004-08-13 Time 14:07 Rev Time 0.00
Received By mcarsill Date 2004-08-13 Time 14:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2004-07-30 Cont ID  
Sent By mcarsill Date 2004-07-30 Time 10:25 Rev Time 0.00
Received By mcarsill Date 2004-07-30 Time 10:25 Sent To  
Notes
2004-07-30 00:00:001) TWO FIRE DEPARTMENT CONNECTIONS ARE
 REQUIRED. TWO 2 1/2 INCH CONNECTIONS
 ARE REQUIRED AT BOTH LOCATIONS.
  
 2) ARE THE PRESSURE REGULATING
 DEVICES PLANNED FOR USE SET IN THE
 FIELD OR THE FACTORY. PLEASE ADVISE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2004-06-15 Cont ID  
Sent By nmccray Date 2004-06-15 Time 11:53 Rev Time 0.00
Received By nmccray Date 2004-06-15 Time 11:53 Sent To  
Notes
2004-06-15 00:00:00SMOKE CONTROL PANEL LAY OUT OK 6-15-04

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2004-05-26 Cont ID  
Sent By mcarsill Date 2004-05-26 Time 16:15 Rev Time 0.00
Received By mcarsill Date 2004-05-26 Time 16:15 Sent To  
Notes
2004-05-26 00:00:001) SINCE THE BUILDING IS A HIGH-RISE
 BUILDING, TWO FIRE DEPARTMENT
 CONNECTIONS ARE REQUIRED.
  
 2) SEVERAL PAGES WERE INSERTED
 UPSIDE DOWN IN PLANS PACKET.
  
 3) NO NON-APPROVED EQUIPMENT OR DEVICES
 ARE ALLOWED IN THE STAIRTOWERS.
  
 4) DUCT SMOKE DETECTORS WHEN ACTIVATED
 SHALL CAUSE THE FIRE ALARM SYSTEM
 TO ACTIVATE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2003-08-07 Cont ID  
Sent By nmccray Date 2003-08-07 Time 09:13 Rev Time 0.00
Received By nmccray Date 2003-08-07 Time 08:55 Sent To  
Notes
2003-08-07 00:00:00*************PROVISO********************
 1) OS&Y VALVES ARE TO BE EQUIPPED WITH
 TAMPER SWITCHES.
  
 2) THE FIRE HYDRANT CLEAR ZONE ON L-5 IS
 IS NOT CORRECT. IT ALSO USES THE WRONG
 CODE.
  
 3) THE KNOX-BOX IS TO BE INSTALLED ON
 THE OUTSIDE OF THE BUILDING.
  
 4) PRESSURE REDUCING VALES NOTED ON
 SP-12. PLEASE PROVIDE FURTHER DETAILS.
 IT IS PREFERRED THAT THEY NOT BE USED.
  
 5) AUTOMATIC DOOR RELEASE DIAGRAM.
 PLEASE SEE NFPA 101, SECTION 7.2.1.5.2.
  
 6) VARIOUS CONDUITS NOTED IN STAIR # 2.
  
 NOTES FOR MIKE CARSILLO, CAPTAIN
 805-6722 OR 835-2910
  
 NATE MCCRAY, CAPTAIN

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2003-07-11 Cont ID  
Sent By mcarsill Date 2003-07-11 Time 07:48 Rev Time 0.00
Received By mcarsill Date 2003-07-11 Time 07:48 Sent To  
Notes
2003-07-11 00:00:001) OS&Y VALVES ARE TO BE EQUIPPED WITH
 TAMPER SWITCHES.
  
 2) THE FIRE HYDRANT CLEAR ZONE ON L-5
 IS NOT CORRECT. IT ALSO USES THE WRONG
 CODE.
  
 3) THE KNOX-BOX IS TO BE INSTALLED
 ON THE OUTSIDE OF THE BUILDING.
  
 4) AN EXIT SIGN IS MISSING NEAR THE
 DOOR LEADING FROM THE PARKING GARAGE
 AND CORRIDOR ON THE GARAGE SIDE. DEAD
 ENDS SHALL NOT EXCEED 50 FEET.
  
 5) THE WEST POOL AREA DOOR LEADING
 INTO THE CORRIDOR SWINGS IN THE WRONG
 DIRECTION. DOOR SHOULD SWING IN THE
 DIRECTION OF EXIT TRAVEL. PLEASE
 REVISE AS NECESSARY.
  
 6) EXIT DOOR LEADING FROM EAST POOL
 DECK APPEARS TO SWING IN THE WRONG
 DIRECTION.
  
 7) PRESSURE REDUCING VALVES NOTED ON
 SP-12. PLEASE PROVIDE FURTHER DETAILS.
 IT IS PREFERRED THAT THEY NOT BE USED.
  
 8) AUTOMATIC DOOR RELEASE DIAGRAM.
 PLEASE SEE NFPA 101, SECTION 7.2.1.5.2.
  
 9) VARIOUS CONDUITS NOTED IN STAIR # 2.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2003-05-16 Cont ID  
Sent By mcarsill Date 2003-05-16 Time 15:00 Rev Time 0.00
Received By mcarsill Date 2003-05-16 Time 15:00 Sent To  
Notes
2003-05-16 00:00:001) THE ONE FDC NOTED NEAR THE SOUTHEAST
 CORNER IS FACING THE WRONG DIRECTION.
 IT SHOULD EITHER FACE 15TH STREET OR
 NORTH FLAGLER DRIVE. THE CURRENT
 ARRANGEMENT WILL CAUSE THE HOSE TO KINK
 AND THUS REDUCE ITS EFFECTIVENESS.
  
 2) WHAT PREVENTS A SINGLE FIRE INCIDENT
 IN THE PARTY ROOM FROM BLOCKING BOTH
 EXITS.
  
 3) A SIGN IS REQUIRED AT ELEVATOR # 3
 INDICATING IT IS STRETCHER USEABLE.
  
 4) THE SECURITY FEATURES PLANNED FOR THE
 GARAGE STILL SEEM TO LEAVE THIS WRITER
 CONFUSED WITH REGARDS TO EXITING. PLEASE
 EXPLAIN HOW EXITING WILL WORK IN THE
 GARAGE WHEN SECURITY DEVICES ARE
 INSTALLED.
  
 5) THE TRASH CHUTE EXHAUST ON THE ROOF
 MUST EXTEND AT LEAST THREE FEET ABOVE
 THE ROOF.
  
 6) TACTILE SIGNAGE REQUIRED AT
 STAIRWELLS.
  
 7) PLEASE EXPLAIN THE (4) 2 1/2 X 2 1/2
 X 6" SIAMESE CONNECTION. HOW MANY
 SIAMESE CONNECTIONS ARE PROPOSED. THIS
 OFFICE WILL ONLY REQUIRED TWO OF THEM.
  
 8) THE COMMERCIAL SPACES ARE TO BE FIRE
 SPRINKLER PROTECTED AT THE TIME THE
 BUILDING IS COMPLETED.
  
 9) SEPARATE PLANS AND PERMIT REQUIRED
 FOR ABOVE GROUND FUEL TANK.
  
 10) EXIT SIGN APPEARS TO BE MISSING
 ON SOUTH SIDE OF GUEST PARKING AREA.
  
 11) EMERGENCY LIGHTING COULD NOT BE
 LOCATED IN THE FIRE PUMP ROOM.
  
 12) ARE THERE ANY EMERGENCY LIGHTS
 PRESENT FOR STAIR # 3 AND 4.
  
 13) THERE APPEARS TO BE ISSUES WITH
 FIRE RATED DOORS AND WALLS IN SOME
 LOCATIONS. PLEASE REVISE THE PLANS.
  
 14) PLEASE ILLUSTRATE COMPLIANCE WITH
 FBC 412.5. THE DESIGN INTENT IS NOT
 CLEAR TO THIS WRITER AT TIME OF
 THIS REVIEW.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-02-20 Cont ID  
Sent By mcarsill Date 2003-02-20 Time 14:54 Rev Time 0.00
Received By mcarsill Date 2003-02-20 Time 14:54 Sent To  
Notes
2003-02-20 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 2) SUITABLE ROADS ARE TO BE PROVIDED
 FOR FIRE AND PARAMEDICAL EQUIPMENT.
  
 3) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHES THREE STORIES
 OR THIRTY FEET IN HEIGHT.
  
 4) ALL CONSTRUCTION, DEMOLITION, AND
 RENOVATION WORK TO COMPLY WITH NFPA
 241.
  
 5) ELECTRONIC TAMPER SWITCHES, A CHAIN
 AND LOCK ARE REQUIRED ON THE FIRE LINE
 BACKFLOW DEVICE.
  
 6) A KNOX-BOX RAPID ENTRY SYSTEM WILL
 BE REQUIRED FOR THE BUILDING.
  
 7) THE PARKING GARAGE IS TO BE SEPARATED
 BY AT LEAST A TWO HOUR FIRE RATING.
  
 8) STAIR IDENTIFICATION SIGNS ARE
 REQUIRED.
  
 9) ALL SHAFTS THAT ARE LARGE ENOUGH
 FOR PERSONS TO FALL INTO MUST BE MARKED
 "SHAFTWAY" IN RED LETTERS.
  
 10) PLEASE REVIEW SECTION 412.4.3 OF
 THE FBC,"FIRE COMMAND CENTER", TO ENSURE
 ALL REQUIRED EQUIPMENT IS CONTAINED
 WITHIN.
  
 11) QUICK RESPONSE OR LISTED
 RESIDENTIAL FIRE SPRINKLER HEADS ARE
 TO BE USED.
  
 12) PLEASE INDICATE WHICH ELEVATORS
 COMPLY WITH THE FBC, SECTION 3003.4
 "STRETCHER REQUIREMENTS".
  
 13) PLEASE SHOW SIGNAGE "IN A FIRE
 EMERGENCY, DO NOT USE ELEVATOR". USE
 EXIT STAIRS" IN ACCORDANCE WITH FBC,
 SECTION 3003.3.
  
 14) SHEET P-1 INDICATES A 6" FIRE LINE
 BUT OTHER SHEETS DISPLAY AN 8" LINE.
 IF THE FIRE PUMP IS 1000 GPM, THEN AN
 8" LINE IS THE MINIMUM SIZE. PLEASE
 CORRECT DISCREPANCY.
  
 15) PLEASE INDICATE ON THE PLANS, WHAT
 THE VOICE EVACUATION MESSAGE WILL SAY
 FOR THE FIRE ALARM SYSTEM.
  
 16) THE BUILDING ADDRESS SIGN SHOWN ON
 A3.1.01 SHALL HAVE AT LEAST 6" NUMERALS.
  
 17) PLEASE INDICATE COMPLIANCE WITH
 FBC,SECTION 412.5, "SMOKE CONTROL".
  
 18) PLANS MAKE REFERENCE TO NFPA 13R.
 NFPA 13R IS NOT APPLICABLE TO THIS
 PROJECT.
  
 19) SECURITY GATES SHOWN IN THE GARAGE.
 HOW DOES THESE DEVICES RESTRICT
 EXITING.
  
 20) HOW DOES PERSONS EXIT VIA THE
 VEHICLE INGRESS AND EGRESS POINTS OF
 THE GARAGE.
  
 21) INCOMPLETE LOCKING DEVICE NOTES ON
 PAGE LS1.02.
  
 22) THE TWO EXITS SHOWN IN THE PARTY
 ROOM ARE NOT PROPERLY SEPARATED FROM
 ONE ANOTHER.
  
 23) SEVERAL DOORS ON LEVEL 5 NEAR STAIR
 # 1 OPEN OUTWARD IN CLOSE PROXIMITY TO
 ONE ANOTHER.
  
 24) SOME 20 MINUTE OR OTHER SYMBOLS
 ARE MISSING NEAR ELEVATOR LOBBY NEAR
 STAIR # 1.
  
 25) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR METAL GUARDRAILS
 MOUNTED ABOVE CRASH WALL.
  
 26) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR TEMPERED GLASS
 RAILING NOTED ON PAGE A1.1.05.
  
 27) ALL RAMPS AND STAIRS TO HAVE
 HANDRAILS.
  
 28) ALL FABRIC AWNINGS ARE TO BE FIRE
 RETARDANT.
  
 29) DOOR SCHEDULE DIFFICULT TO READ.
  
 30) AN EXIT SIGN APPEARS TO BE MISSING
 FROM GUEST PARKING.
  
 31) PLEASE CLEARLY IDENTIFY ALL
 EMERGENCY LIGHTS.
  
 32) ARE EMERGENCY LIGHTS PRESENT IN
 THE STAIRTOWERS. THE SYSMBOL USED DOES
 NOT SUGGEST THAT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 169 Status N Date 2005-07-29 Cont ID  
Sent By adarroug Date 2005-07-29 Time 14:21 Rev Time 0.00
Received By adarroug Date 2005-07-29 Time 14:21 Sent To B
Notes
2005-07-29 00:00:00TO "RBROWN" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 168 Status N Date 2005-07-19 Cont ID  
Sent By adarroug Date 2005-07-19 Time 09:02 Rev Time 0.00
Received By adarroug Date 2005-07-19 Time 09:02 Sent To M
Notes
2005-07-19 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 167 Status N Date 2005-06-24 Cont ID  
Sent By adarroug Date 2005-06-24 Time 08:44 Rev Time 0.00
Received By adarroug Date 2005-06-24 Time 08:44 Sent To ENG
Notes
2005-07-01 00:00:00SENT TO ZONING:ANGELLA JONES-VAN
  
  
  
2005-06-24 00:00:00TO "MAMINI" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 166 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By shill Date 2005-06-08 Time 09:13 Sent To  
Notes
2005-06-08 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 165 Status N Date 2005-05-31 Cont ID  
Sent By adarroug Date 2005-05-31 Time 16:30 Rev Time 0.00
Received By adarroug Date 2005-05-31 Time 16:30 Sent To B
Notes
2005-05-31 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 164 Status N Date 2005-05-31 Cont ID  
Sent By adarroug Date 2005-05-31 Time 08:55 Rev Time 0.00
Received By adarroug Date 2005-05-31 Time 08:55 Sent To B
Notes
2005-05-31 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 163 Status N Date 2005-05-24 Cont ID  
Sent By adarroug Date 2005-05-24 Time 16:39 Rev Time 0.00
Received By adarroug Date 2005-05-24 Time 16:39 Sent To B
Notes
2005-05-24 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 162 Status N Date 2005-05-20 Cont ID  
Sent By rbrown Date 2005-05-20 Time 14:10 Rev Time 0.00
Received By rbrown Date 2005-05-20 Time 14:10 Sent To  
Notes
2005-05-20 00:00:00TO "RBROWN" DESK/EASTERN GUARDRAIL
 SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 161 Status N Date 2005-05-11 Cont ID  
Sent By adarroug Date 2005-05-11 Time 14:22 Rev Time 0.00
Received By adarroug Date 2005-05-11 Time 14:22 Sent To B
Notes
2005-05-11 00:00:00TO "RBROWN" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 160 Status N Date 2005-05-11 Cont ID  
Sent By adarroug Date 2005-05-11 Time 14:21 Rev Time 0.00
Received By adarroug Date 2005-05-11 Time 14:21 Sent To B
Notes
2005-05-11 00:00:00TO "RBROWN"DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 159 Status N Date 2005-05-09 Cont ID  
Sent By adarroug Date 2005-05-09 Time 13:50 Rev Time 0.00
Received By adarroug Date 2005-05-09 Time 13:50 Sent To  
Notes
2005-05-18 00:00:00TO "COMM" BD#51
2005-05-09 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 158 Status N Date 2005-05-03 Cont ID  
Sent By adarroug Date 2005-05-03 Time 13:41 Rev Time 0.00
Received By adarroug Date 2005-05-03 Time 13:41 Sent To B
Notes
2005-05-03 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 157 Status N Date 2005-04-29 Cont ID  
Sent By adarroug Date 2005-04-29 Time 09:18 Rev Time 0.00
Received By adarroug Date 2005-04-29 Time 09:18 Sent To B
Notes
2005-04-29 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 156 Status N Date 2005-04-29 Cont ID  
Sent By adarroug Date 2005-04-29 Time 09:17 Rev Time 0.00
Received By adarroug Date 2005-04-29 Time 09:17 Sent To B
Notes
2005-04-29 00:00:00TO "RBROWN" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 155 Status N Date 2005-04-29 Cont ID  
Sent By adarroug Date 2005-04-29 Time 09:16 Rev Time 0.00
Received By adarroug Date 2005-04-29 Time 09:16 Sent To B
Notes
2005-04-29 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 154 Status N Date 2005-04-29 Cont ID  
Sent By adarroug Date 2005-04-29 Time 09:06 Rev Time 0.00
Received By adarroug Date 2005-04-29 Time 09:06 Sent To B
Notes
2005-04-29 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 153 Status N Date 2005-04-29 Cont ID  
Sent By adarroug Date 2005-04-29 Time 09:04 Rev Time 0.00
Received By adarroug Date 2005-04-29 Time 09:04 Sent To B
Notes
2005-04-29 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 152 Status N Date 2005-04-25 Cont ID  
Sent By adarroug Date 2005-04-25 Time 16:40 Rev Time 0.00
Received By adarroug Date 2005-04-25 Time 16:40 Sent To FIRE
Notes
2005-04-25 00:00:00TO "F" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 151 Status N Date 2005-04-19 Cont ID  
Sent By adarroug Date 2005-04-19 Time 08:56 Rev Time 0.00
Received By adarroug Date 2005-04-19 Time 08:56 Sent To M
Notes
2005-04-19 00:00:00TO "PKRAUSS" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 150 Status N Date 2005-04-19 Cont ID  
Sent By adarroug Date 2005-04-19 Time 08:24 Rev Time 0.00
Received By adarroug Date 2005-04-19 Time 08:24 Sent To  
Notes
2005-04-19 00:00:00TO "COMM" BD#17

Review Stop I INCOMING/PROCESSING
Rev No 149 Status N Date 2005-04-18 Cont ID  
Sent By adarroug Date 2005-04-18 Time 14:09 Rev Time 0.00
Received By adarroug Date 2005-04-18 Time 14:09 Sent To B
Notes
2005-04-18 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 148 Status N Date 2005-04-14 Cont ID  
Sent By adarroug Date 2005-04-14 Time 11:01 Rev Time 0.00
Received By adarroug Date 2005-04-14 Time 11:01 Sent To B
Notes
2005-04-14 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 147 Status N Date 2005-04-07 Cont ID  
Sent By adarroug Date 2005-04-07 Time 09:50 Rev Time 0.00
Received By adarroug Date 2005-04-07 Time 09:50 Sent To E
Notes
2005-04-07 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 146 Status N Date 2005-04-07 Cont ID  
Sent By adarroug Date 2005-04-07 Time 09:28 Rev Time 0.00
Received By adarroug Date 2005-04-07 Time 09:28 Sent To B
Notes
2005-04-07 00:00:00TO "RBROWN" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 145 Status N Date 2005-04-04 Cont ID  
Sent By adarroug Date 2005-04-04 Time 16:45 Rev Time 0.00
Received By adarroug Date 2005-04-04 Time 16:45 Sent To B
Notes
2005-04-04 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 144 Status N Date 2005-03-31 Cont ID  
Sent By adarroug Date 2005-03-31 Time 11:23 Rev Time 0.00
Received By adarroug Date 2005-03-31 Time 11:23 Sent To E
Notes
2005-03-31 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 143 Status N Date 2005-03-31 Cont ID  
Sent By adarroug Date 2005-03-31 Time 11:20 Rev Time 0.00
Received By adarroug Date 2005-03-31 Time 11:20 Sent To B
Notes
2005-04-01 00:00:00GIVEN TO D PALMER ON 4/1/05
  
  
2005-03-31 00:00:00TO "RBROWN" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 142 Status N Date 2005-03-23 Cont ID  
Sent By adarroug Date 2005-03-23 Time 13:16 Rev Time 0.00
Received By adarroug Date 2005-03-23 Time 13:16 Sent To B
Notes
2005-03-23 00:00:00TO "RBROWN" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 141 Status N Date 2005-03-22 Cont ID  
Sent By adarroug Date 2005-03-22 Time 15:00 Rev Time 0.00
Received By adarroug Date 2005-03-22 Time 15:00 Sent To B
Notes
2005-03-22 00:00:00TO "RBROWN" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 140 Status N Date 2005-03-22 Cont ID  
Sent By adarroug Date 2005-03-22 Time 14:59 Rev Time 0.00
Received By adarroug Date 2005-03-22 Time 14:59 Sent To B
Notes
2005-03-22 00:00:00TO "RBROWN" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 139 Status N Date 2005-03-22 Cont ID  
Sent By adarroug Date 2005-03-22 Time 14:58 Rev Time 0.00
Received By adarroug Date 2005-03-22 Time 14:58 Sent To B
Notes
2005-03-22 00:00:00TO "RBROWN" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 138 Status N Date 2005-03-22 Cont ID  
Sent By adarroug Date 2005-03-22 Time 14:58 Rev Time 0.00
Received By adarroug Date 2005-03-22 Time 14:58 Sent To B
Notes
2005-03-22 00:00:00TO "RBROWN" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 137 Status N Date 2005-03-08 Cont ID  
Sent By adarroug Date 2005-03-08 Time 15:15 Rev Time 0.00
Received By adarroug Date 2005-03-08 Time 15:15 Sent To P
Notes
2005-03-08 00:00:00TO "KSTEVENS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 136 Status N Date 2005-03-08 Cont ID  
Sent By adarroug Date 2005-03-08 Time 15:10 Rev Time 0.00
Received By adarroug Date 2005-03-08 Time 15:10 Sent To E
Notes
2005-03-08 00:00:00TO "DP" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 135 Status N Date 2005-03-08 Cont ID  
Sent By adarroug Date 2005-03-08 Time 15:07 Rev Time 0.00
Received By adarroug Date 2005-03-08 Time 15:07 Sent To M
Notes
2005-03-08 00:00:00TO PKRAUSS BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 134 Status N Date 2005-03-03 Cont ID  
Sent By mjacobs Date 2005-03-03 Time 09:13 Rev Time 0.00
Received By mjacobs Date 2005-03-03 Time 09:13 Sent To B
Notes
2005-03-03 00:00:00TO "RB" DESK/REV.

Review Stop I INCOMING/PROCESSING
Rev No 133 Status N Date 2005-02-28 Cont ID  
Sent By adarroug Date 2005-02-28 Time 09:08 Rev Time 0.00
Received By adarroug Date 2005-02-28 Time 09:08 Sent To B
Notes
2005-02-28 00:00:00TO "RBROWN" DESK
 SMOKE BOMB LAYOUT, SUBMITTED ON 2/25/05,
 SENT TO PATTI KRAUSS' DESK.ALREADY
 REVIEWED BY FIRE.
  

Review Stop I INCOMING/PROCESSING
Rev No 132 Status N Date 2005-02-22 Cont ID  
Sent By adarroug Date 2005-02-22 Time 14:19 Rev Time 0.00
Received By adarroug Date 2005-02-22 Time 14:19 Sent To B
Notes
2005-02-22 00:00:00TO RBROWN DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 131 Status N Date 2005-02-22 Cont ID  
Sent By adarroug Date 2005-02-22 Time 14:18 Rev Time 0.00
Received By adarroug Date 2005-02-22 Time 14:18 Sent To B
Notes
2005-02-22 00:00:00TO RBROWN DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 130 Status N Date 2005-02-22 Cont ID  
Sent By adarroug Date 2005-02-22 Time 14:17 Rev Time 0.00
Received By adarroug Date 2005-02-22 Time 14:17 Sent To B
Notes
2005-02-22 00:00:00TO RBROWN DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 129 Status N Date 2005-02-22 Cont ID  
Sent By adarroug Date 2005-02-22 Time 14:14 Rev Time 0.00
Received By adarroug Date 2005-02-22 Time 14:14 Sent To B
Notes
2005-02-22 00:00:00TO RBROWN DESK/REVISOION

Review Stop I INCOMING/PROCESSING
Rev No 128 Status N Date 2005-02-11 Cont ID  
Sent By adarroug Date 2005-02-11 Time 11:23 Rev Time 0.00
Received By adarroug Date 2005-02-11 Time 11:23 Sent To B
Notes
2005-02-11 00:00:00TO RBROWN DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 127 Status N Date 2005-02-08 Cont ID  
Sent By adarroug Date 2005-02-08 Time 10:14 Rev Time 0.00
Received By adarroug Date 2005-02-08 Time 10:14 Sent To E
Notes
2005-02-08 00:00:00TO DPALMER DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 126 Status N Date 2005-02-09 Cont ID  
Sent By adarroug Date 2005-02-09 Time 08:53 Rev Time 0.00
Received By adarroug Date 2005-02-09 Time 08:53 Sent To B
Notes
2005-02-09 00:00:00TO RBROWN DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 125 Status N Date 2005-02-04 Cont ID  
Sent By adarroug Date 2005-02-04 Time 10:18 Rev Time 0.00
Received By adarroug Date 2005-02-04 Time 10:18 Sent To E
Notes
2005-02-04 00:00:00TO DPALMER DESK

Review Stop I INCOMING/PROCESSING
Rev No 124 Status N Date 2005-02-01 Cont ID  
Sent By mjacobs Date 2005-02-01 Time 13:08 Rev Time 0.00
Received By mjacobs Date 2005-02-01 Time 13:07 Sent To B
Notes
2005-02-01 00:00:00TO "RB" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 123 Status N Date 2005-02-01 Cont ID  
Sent By mjacobs Date 2005-02-01 Time 11:44 Rev Time 0.00
Received By mjacobs Date 2005-02-01 Time 11:44 Sent To M
Notes
2005-02-01 00:00:00TO M/AC BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 122 Status N Date 2005-01-20 Cont ID  
Sent By mjacobs Date 2005-01-20 Time 09:43 Rev Time 0.00
Received By mjacobs Date 2005-01-20 Time 09:43 Sent To B
Notes
2005-01-20 00:00:00TO "RB" DESK/REV.

Review Stop I INCOMING/PROCESSING
Rev No 121 Status N Date 2005-01-04 Cont ID  
Sent By mjacobs Date 2005-01-04 Time 09:54 Rev Time 0.00
Received By mjacobs Date 2005-01-04 Time 09:54 Sent To M
Notes
2005-01-04 00:00:00TO "M/AC" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 120 Status N Date 2004-12-21 Cont ID  
Sent By mjacobs Date 2004-12-21 Time 12:29 Rev Time 0.00
Received By mjacobs Date 2004-12-21 Time 12:29 Sent To B
Notes
2004-12-21 00:00:00SENT TO "RB" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 119 Status N Date 2004-12-21 Cont ID  
Sent By mjacobs Date 2004-12-21 Time 12:17 Rev Time 0.00
Received By mjacobs Date 2004-12-21 Time 12:17 Sent To B
Notes
2004-12-21 00:00:00SENT TO "RB" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 118 Status N Date 2004-12-14 Cont ID  
Sent By mjacobs Date 2004-12-14 Time 10:37 Rev Time 0.00
Received By mjacobs Date 2004-12-14 Time 10:37 Sent To B
Notes
2004-12-14 00:00:00SENT TO "RB" DESK/REV./SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 117 Status N Date 2004-11-19 Cont ID  
Sent By mjacobs Date 2004-11-19 Time 12:06 Rev Time 0.00
Received By mjacobs Date 2004-11-19 Time 12:06 Sent To FIRE
Notes
2004-11-19 00:00:00SENT TO FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 116 Status N Date 2004-11-19 Cont ID  
Sent By mjacobs Date 2004-11-19 Time 12:04 Rev Time 0.00
Received By mjacobs Date 2004-11-19 Time 12:04 Sent To M
Notes
2004-11-19 00:00:00SENT TO "M/AC" BOX

Review Stop I INCOMING/PROCESSING
Rev No 115 Status N Date 2004-11-19 Cont ID  
Sent By mjacobs Date 2004-11-19 Time 11:58 Rev Time 0.00
Received By mjacobs Date 2004-11-19 Time 11:58 Sent To M
Notes
2004-11-19 00:00:00SENT TO "M" TO PK BOX

Review Stop I INCOMING/PROCESSING
Rev No 114 Status N Date 2004-11-19 Cont ID  
Sent By csiegber Date 2004-11-19 Time 10:59 Rev Time 0.00
Received By csiegber Date 2004-11-19 Time 10:59 Sent To E
Notes
2004-11-19 00:00:00TO DP DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 113 Status N Date 2004-11-12 Cont ID  
Sent By csiegber Date 2004-11-12 Time 16:49 Rev Time 0.00
Received By csiegber Date 2004-11-12 Time 16:49 Sent To B
Notes
2004-11-12 00:00:00TO RB DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 112 Status N Date 2004-11-01 Cont ID  
Sent By csiegber Date 2004-11-01 Time 15:44 Rev Time 0.00
Received By csiegber Date 2004-11-01 Time 15:44 Sent To B
Notes
2004-11-01 00:00:00TO RB DESK/SUBMITTAL
 POUR LETTERS

Review Stop I INCOMING/PROCESSING
Rev No 111 Status N Date 2004-10-20 Cont ID  
Sent By csiegber Date 2004-10-20 Time 10:36 Rev Time 0.00
Received By csiegber Date 2004-10-20 Time 10:36 Sent To B
Notes
2004-10-20 00:00:00TO RB DESK/2 SUBMITTALS
 POUR LETTERS-EAST POOL CONVENTIONAL SLAB
 SSK-96

Review Stop I INCOMING/PROCESSING
Rev No 110 Status N Date 2004-10-12 Cont ID  
Sent By csiegber Date 2004-10-12 Time 16:05 Rev Time 0.00
Received By csiegber Date 2004-10-12 Time 16:05 Sent To B
Notes
2004-10-12 00:00:00TO RB DESK/GROUND FLOOR LIFE SAFETY

Review Stop I INCOMING/PROCESSING
Rev No 109 Status N Date 2004-10-07 Cont ID  
Sent By csiegber Date 2004-10-07 Time 10:00 Rev Time 0.00
Received By csiegber Date 2004-10-07 Time 10:01 Sent To B
Notes
2004-10-07 00:00:00TO RB DESK/REV-REF4,10,16/SSK85-SF1&2/
 RFI537
 SUBMITTAL-DEMONSTRATION LETTER

Review Stop I INCOMING/PROCESSING
Rev No 108 Status N Date 2004-10-06 Cont ID  
Sent By csiegber Date 2004-10-06 Time 09:48 Rev Time 0.00
Received By csiegber Date 2004-10-06 Time 09:48 Sent To  
Notes
2004-10-06 00:00:00TO COMM BD#3

Review Stop I INCOMING/PROCESSING
Rev No 107 Status N Date 2004-10-05 Cont ID  
Sent By csiegber Date 2004-10-05 Time 16:35 Rev Time 0.00
Received By csiegber Date 2004-10-05 Time 16:35 Sent To  
Notes
2004-10-05 00:00:00TO COMM BD#

Review Stop I INCOMING/PROCESSING
Rev No 106 Status N Date 2004-10-05 Cont ID  
Sent By csiegber Date 2004-10-05 Time 15:33 Rev Time 0.00
Received By csiegber Date 2004-10-05 Time 15:33 Sent To E
Notes
2004-10-05 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 105 Status N Date 2004-10-05 Cont ID  
Sent By csiegber Date 2004-10-05 Time 15:29 Rev Time 0.00
Received By csiegber Date 2004-10-05 Time 15:29 Sent To E
Notes
2004-10-05 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 104 Status N Date 2004-10-05 Cont ID  
Sent By csiegber Date 2004-10-05 Time 15:25 Rev Time 0.00
Received By csiegber Date 2004-10-05 Time 15:25 Sent To B
Notes
2004-10-05 00:00:00TO RB DESK/SUBMITTAL
 POUR LETTERS

Review Stop I INCOMING/PROCESSING
Rev No 103 Status N Date 2004-10-05 Cont ID  
Sent By csiegber Date 2004-10-05 Time 10:54 Rev Time 0.00
Received By csiegber Date 2004-10-05 Time 10:54 Sent To B
Notes
2004-10-05 00:00:00TO RB DESK/SUBMITTAL
 DRYWALL DAMAGE LETTERS

Review Stop I INCOMING/PROCESSING
Rev No 102 Status N Date 2004-10-04 Cont ID  
Sent By csiegber Date 2004-10-04 Time 11:52 Rev Time 0.00
Received By csiegber Date 2004-10-04 Time 11:52 Sent To P
Notes
2004-10-04 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 101 Status N Date 2004-09-20 Cont ID  
Sent By csiegber Date 2004-09-20 Time 16:12 Rev Time 0.00
Received By csiegber Date 2004-09-20 Time 16:12 Sent To B
Notes
2004-09-20 00:00:00TO RB DESK/SUBMITTAL
 5TH FLR POUR

Review Stop I INCOMING/PROCESSING
Rev No 100 Status N Date 2004-09-20 Cont ID  
Sent By csiegber Date 2004-09-20 Time 16:11 Rev Time 0.00
Received By csiegber Date 2004-09-20 Time 16:11 Sent To B
Notes
2004-09-20 00:00:00TO RB REV/PHOTOMETRICS

Review Stop I INCOMING/PROCESSING
Rev No 99 Status N Date 2004-09-15 Cont ID  
Sent By csiegber Date 2004-09-15 Time 14:56 Rev Time 0.00
Received By csiegber Date 2004-09-15 Time 14:56 Sent To B
Notes
2004-09-15 00:00:00TO RB DESK/4 REVS
 SSK-83, SSK 89A, SSK-94
 3000PSI GROUT MIX DESIGN FOR MASONRY
 FILL CELLS
 REV PT16 & PT16R EAST ROOF REV
 PT SHOPS FOR 5TH FLOOR

Review Stop I INCOMING/PROCESSING
Rev No 98 Status N Date 2004-09-01 Cont ID  
Sent By csiegber Date 2004-09-01 Time 10:14 Rev Time 0.00
Received By csiegber Date 2004-09-01 Time 10:14 Sent To B
Notes
2004-09-01 00:00:00TO RB DESK/SUBMITTAL
 FES-ELEVATOR USING VVVF DRIVE
 TRANSFORMERS

Review Stop I INCOMING/PROCESSING
Rev No 97 Status N Date 2004-08-25 Cont ID  
Sent By csiegber Date 2004-08-25 Time 14:45 Rev Time 0.00
Received By csiegber Date 2004-08-25 Time 14:45 Sent To B
Notes
2004-08-25 00:00:00TO RB DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 96 Status N Date 2004-08-25 Cont ID  
Sent By csiegber Date 2004-08-25 Time 14:45 Rev Time 0.00
Received By csiegber Date 2004-08-25 Time 14:45 Sent To  
Notes
2004-08-25 00:00:00TO COMM BD#36

Review Stop I INCOMING/PROCESSING
Rev No 95 Status N Date 2004-08-23 Cont ID  
Sent By csiegber Date 2004-08-23 Time 08:52 Rev Time 0.00
Received By csiegber Date 2004-08-23 Time 08:52 Sent To B
Notes
2004-08-23 00:00:00TO RB DESK/2 SUBMITTALS
 INTERMEDIATE POOL SLAB WEST GARAGE POUR
 LETTERS
 DOORS L1-23A-L1-27A

Review Stop I INCOMING/PROCESSING
Rev No 94 Status N Date 2004-08-17 Cont ID  
Sent By csiegber Date 2004-08-17 Time 10:08 Rev Time 0.00
Received By csiegber Date 2004-08-17 Time 10:08 Sent To B
Notes
2004-08-17 00:00:00TO RB DESK/REV
 REVISED SHORING
 ELONGATION LETTER/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 93 Status N Date 2004-08-12 Cont ID  
Sent By csiegber Date 2004-08-12 Time 09:42 Rev Time 0.00
Received By csiegber Date 2004-08-12 Time 09:42 Sent To B
Notes
2004-08-12 00:00:00TO RB DESK/SUBMITTAL
 GROUT/SLIDING GLASS DOOR TRACKS CLARIFI-
 CATION LETTER

Review Stop I INCOMING/PROCESSING
Rev No 92 Status N Date 2004-08-11 Cont ID  
Sent By csiegber Date 2004-08-11 Time 10:53 Rev Time 0.00
Received By csiegber Date 2004-08-11 Time 10:53 Sent To B
Notes
2004-08-11 00:00:00TO RB DESK/2 SUBMITTALS
 SIGNED & SEALED A1.1.01 AWNING PERMIT
 ELONGATION LETTERS 8/3/04

Review Stop I INCOMING/PROCESSING
Rev No 91 Status N Date 2004-08-05 Cont ID  
Sent By csiegber Date 2004-08-05 Time 09:16 Rev Time 0.00
Received By csiegber Date 2004-08-05 Time 09:16 Sent To B
Notes
2004-08-05 00:00:00TO RB DESK/POUR LETTER ROOF

Review Stop I INCOMING/PROCESSING
Rev No 90 Status N Date 2004-08-05 Cont ID  
Sent By csiegber Date 2004-08-05 Time 09:14 Rev Time 0.00
Received By csiegber Date 2004-08-05 Time 09:14 Sent To P
Notes
2004-08-05 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 89 Status N Date 2004-08-02 Cont ID  
Sent By csiegber Date 2004-08-02 Time 16:18 Rev Time 0.00
Received By csiegber Date 2004-08-02 Time 16:18 Sent To B
Notes
2004-08-02 00:00:00TO RB DESK/REV
 OAL AT SERVICE CORRIDOR

Review Stop I INCOMING/PROCESSING
Rev No 88 Status N Date 2004-08-02 Cont ID  
Sent By csiegber Date 2004-08-02 Time 12:27 Rev Time 0.00
Received By csiegber Date 2004-08-02 Time 12:27 Sent To B
Notes
2004-08-02 00:00:00TO RB DESK/SUBMITTAL
 PTE ELONGATION LETTERS

Review Stop I INCOMING/PROCESSING
Rev No 87 Status N Date 2004-07-28 Cont ID  
Sent By csiegber Date 2004-07-28 Time 14:32 Rev Time 0.00
Received By csiegber Date 2004-07-28 Time 14:32 Sent To B
Notes
2004-07-28 00:00:00TO RB DESK/POUR LETTRS 7/28/2004

Review Stop I INCOMING/PROCESSING
Rev No 86 Status N Date 2004-07-28 Cont ID  
Sent By csiegber Date 2004-07-28 Time 12:26 Rev Time 0.00
Received By csiegber Date 2004-07-28 Time 12:26 Sent To B
Notes
2004-07-28 00:00:00TO RB DESK/POUR LETTER 7/28/2004

Review Stop I INCOMING/PROCESSING
Rev No 85 Status N Date 2004-07-26 Cont ID  
Sent By csiegber Date 2004-07-26 Time 11:16 Rev Time 0.00
Received By csiegber Date 2004-07-26 Time 11:16 Sent To B
Notes
2004-07-26 00:00:00TO RB DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 84 Status N Date 2004-07-22 Cont ID  
Sent By csiegber Date 2004-07-22 Time 16:53 Rev Time 0.00
Received By csiegber Date 2004-07-22 Time 16:53 Sent To  
Notes
2004-07-22 00:00:00TO COMM BD#18

Review Stop I INCOMING/PROCESSING
Rev No 83 Status N Date 2004-07-22 Cont ID  
Sent By csiegber Date 2004-07-22 Time 16:52 Rev Time 0.00
Received By csiegber Date 2004-07-22 Time 16:52 Sent To B
Notes
2004-07-22 00:00:00TO RB DESK/SUBMITTALS
 WINDOW CLEANING & SAFETY SYSTEM SHOP DRW

Review Stop I INCOMING/PROCESSING
Rev No 82 Status N Date 2004-07-21 Cont ID  
Sent By csiegber Date 2004-07-21 Time 16:02 Rev Time 0.00
Received By csiegber Date 2004-07-21 Time 16:02 Sent To B
Notes
2004-07-21 00:00:00TO RB DESK/3 SUBMITTALS
 STAIR SHIMS
 POUR 2,16TH FLOOR & ELONGATIONS
 POST TENSIONED SYSTEM POUR 1-17TH FLR

Review Stop I INCOMING/PROCESSING
Rev No 81 Status N Date 2004-07-14 Cont ID  
Sent By csiegber Date 2004-07-14 Time 15:51 Rev Time 0.00
Received By csiegber Date 2004-07-14 Time 15:51 Sent To E
Notes
2004-07-14 00:00:00TO COMM BD#60

Review Stop I INCOMING/PROCESSING
Rev No 80 Status N Date 2004-07-14 Cont ID  
Sent By csiegber Date 2004-07-14 Time 15:42 Rev Time 0.00
Received By csiegber Date 2004-07-14 Time 15:42 Sent To B
Notes
2004-07-14 00:00:00TO RB DESK/4 SUBMITTALS
 PTE ELONGATIONS 7/13/2004
 PTE ELONGATIONS 7/7/2004
 PTE ELONGATIONS 7/1/2004
 SF-2 & SF-2

Review Stop I INCOMING/PROCESSING
Rev No 79 Status N Date 2004-07-12 Cont ID  
Sent By csiegber Date 2004-07-12 Time 16:24 Rev Time 0.00
Received By csiegber Date 2004-07-12 Time 16:24 Sent To B
Notes
2004-07-12 00:00:00TO RB DESK/POUR LETTER 7/13/04

Review Stop I INCOMING/PROCESSING
Rev No 78 Status N Date 2004-07-12 Cont ID  
Sent By csiegber Date 2004-07-12 Time 14:51 Rev Time 0.00
Received By csiegber Date 2004-07-12 Time 14:51 Sent To M
Notes
2004-07-12 00:00:00TO PK BOX/SUBMITTALS/
 AC1,AC 8A CU,AC1

Review Stop I INCOMING/PROCESSING
Rev No 77 Status N Date 2004-07-07 Cont ID  
Sent By csiegber Date 2004-07-07 Time 09:24 Rev Time 0.00
Received By csiegber Date 2004-07-07 Time 09:24 Sent To B
Notes
2004-07-07 00:00:00TO RB DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 76 Status N Date 2004-06-30 Cont ID  
Sent By csiegber Date 2004-06-30 Time 09:18 Rev Time 0.00
Received By csiegber Date 2004-06-30 Time 09:18 Sent To B
Notes
2004-06-30 00:00:00TO RB DESK/3 SUBMITTALS/
 PTE ELONGATION LETTERS 6/29
 PTE ELONGATION LETTERS 6/23
 PTE ELONGATION LETTERS 6/15

Review Stop I INCOMING/PROCESSING
Rev No 75 Status N Date 2004-06-28 Cont ID  
Sent By csiegber Date 2004-06-28 Time 11:13 Rev Time 0.00
Received By csiegber Date 2004-06-28 Time 11:13 Sent To B
Notes
2004-06-28 00:00:00TO RB DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 74 Status N Date 2004-06-24 Cont ID  
Sent By csiegber Date 2004-06-24 Time 08:22 Rev Time 0.00
Received By csiegber Date 2004-06-24 Time 08:22 Sent To B
Notes
2004-06-24 00:00:00TO RB DESK/SUBMITTAL/POUR LETTERS 6/24
 & ROOF BAND TENDONS & SUPPORT LAYOUT

Review Stop I INCOMING/PROCESSING
Rev No 73 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By csiegber Date 2004-06-18 Time 15:12 Sent To  
Notes
2004-06-18 00:00:00TO RB DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 72 Status N Date 2004-06-16 Cont ID  
Sent By csiegber Date 2004-06-16 Time 14:16 Rev Time 0.00
Received By csiegber Date 2004-06-16 Time 14:16 Sent To B
Notes
2004-06-16 00:00:00TO RB DESK/2 SUBMITTALS/
 PTE ELONGATION LETTERS & CONCRETE MIX

Review Stop I INCOMING/PROCESSING
Rev No 71 Status N Date 2004-06-14 Cont ID  
Sent By mjacobs Date 2004-06-14 Time 14:21 Rev Time 0.00
Received By mjacobs Date 2004-06-14 Time 14:21 Sent To B
Notes
2004-06-14 00:00:00TO RB DESK/SUBMITTALS/POUR LETTER 6-14

Review Stop I INCOMING/PROCESSING
Rev No 70 Status N Date 2004-06-11 Cont ID  
Sent By csiegber Date 2004-06-10 Time 11:13 Rev Time 0.00
Received By csiegber Date 2004-06-10 Time 11:13 Sent To FIRE
Notes
2004-06-10 00:00:00/SIEMEN'S FIRE SAFETY

Review Stop I INCOMING/PROCESSING
Rev No 69 Status N Date 2004-06-10 Cont ID  
Sent By csiegber Date 2004-06-10 Time 11:11 Rev Time 0.00
Received By csiegber Date 2004-06-10 Time 11:14 Sent To B
Notes
2004-06-10 00:00:00TO RB DESK/2 SUBMITTALS/PTE
 POOL WEST BAND/UNIFORM CABLES & REBAR
 SSK-86 & 85

Review Stop I INCOMING/PROCESSING
Rev No 68 Status N Date 2004-06-08 Cont ID  
Sent By csiegber Date 2004-06-08 Time 10:58 Rev Time 0.00
Received By csiegber Date 2004-06-08 Time 10:57 Sent To B
Notes
2004-06-08 00:00:00TO RB DESK/5 SUBMITTAL/POUR 6/7/04
 PTE ELONGATION LETTERS/ELONGATION
 LETTERS 5/28/04/ELONGATION 5/27/04/
 POUR LETTER 6/8/04

Review Stop I INCOMING/PROCESSING
Rev No 67 Status N Date 2004-06-03 Cont ID  
Sent By csiegber Date 2004-06-03 Time 08:19 Rev Time 0.00
Received By csiegber Date 2004-06-03 Time 08:19 Sent To B
Notes
2004-06-03 00:00:00TO RB DESK/SUBMITTAL/LEVEL 2,3,4
 SHORING PLAN

Review Stop I INCOMING/PROCESSING
Rev No 66 Status N Date 2004-06-02 Cont ID  
Sent By csiegber Date 2004-06-02 Time 07:55 Rev Time 0.00
Received By csiegber Date 2004-06-02 Time 07:55 Sent To B
Notes
2004-06-02 00:00:00TO RB DESK/SUBMITTAL/LEVEL 12/POUR 1

Review Stop I INCOMING/PROCESSING
Rev No 65 Status N Date 2004-05-26 Cont ID  
Sent By alange Date 2004-05-26 Time 10:03 Rev Time 0.00
Received By alange Date 2004-05-26 Time 10:03 Sent To B
Notes
2004-05-26 00:00:00TO RB DESK

Review Stop I INCOMING/PROCESSING
Rev No 64 Status N Date 2004-05-26 Cont ID  
Sent By alange Date 2004-05-26 Time 09:28 Rev Time 0.00
Received By alange Date 2004-05-26 Time 09:28 Sent To B
Notes
2004-05-26 00:00:00TO SH DESK

Review Stop I INCOMING/PROCESSING
Rev No 63 Status N Date 2004-05-26 Cont ID  
Sent By alange Date 2004-05-26 Time 09:27 Rev Time 0.00
Received By alange Date 2004-05-26 Time 09:27 Sent To B
Notes
2004-05-26 00:00:00TO SH DESK

Review Stop I INCOMING/PROCESSING
Rev No 62 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By alange Date 2004-05-25 Time 15:29 Sent To  
Notes
2004-05-25 00:00:00TO RB DESK

Review Stop I INCOMING/PROCESSING
Rev No 61 Status N Date 2004-05-21 Cont ID  
Sent By csiegber Date 2004-05-21 Time 08:46 Rev Time 0.00
Received By csiegber Date 2004-05-21 Time 08:46 Sent To B
Notes
2004-05-21 00:00:00TO RB DESK/POUR LETTERS 5/21/04

Review Stop I INCOMING/PROCESSING
Rev No 60 Status N Date 2004-05-21 Cont ID  
Sent By csiegber Date 2004-05-21 Time 08:38 Rev Time 0.00
Received By csiegber Date 2004-05-21 Time 08:38 Sent To B
Notes
2004-05-21 00:00:00TO RB DESK/SUBMITTAL/SSK-77-82

Review Stop I INCOMING/PROCESSING
Rev No 59 Status N Date 2004-05-17 Cont ID  
Sent By csiegber Date 2004-05-17 Time 11:12 Rev Time 0.00
Received By csiegber Date 2004-05-17 Time 11:12 Sent To B
Notes
2004-05-17 00:00:00TO RB DESK/POUR LETTERS

Review Stop I INCOMING/PROCESSING
Rev No 58 Status N Date 2004-05-12 Cont ID  
Sent By csiegber Date 2004-05-12 Time 14:49 Rev Time 0.00
Received By csiegber Date 2004-05-12 Time 14:49 Sent To B
Notes
2004-05-12 00:00:00TO RB DESK/SUBMITTAL/POUR LETTER 5/12/04

Review Stop I INCOMING/PROCESSING
Rev No 57 Status N Date 2004-05-11 Cont ID  
Sent By csiegber Date 2004-05-11 Time 11:23 Rev Time 0.00
Received By csiegber Date 2004-05-11 Time 11:23 Sent To B
Notes
2004-05-11 00:00:00TO COMM BD#62

Review Stop I INCOMING/PROCESSING
Rev No 56 Status N Date 2004-05-05 Cont ID  
Sent By csiegber Date 2004-05-05 Time 16:40 Rev Time 0.00
Received By csiegber Date 2004-05-05 Time 16:40 Sent To B
Notes
2004-05-05 00:00:00TO RB DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 55 Status N Date 2004-04-30 Cont ID  
Sent By csiegber Date 2004-04-30 Time 15:20 Rev Time 0.00
Received By csiegber Date 2004-04-30 Time 15:20 Sent To B
Notes
2004-04-30 00:00:00TO RB DESK/POUR LETTERS

Review Stop I INCOMING/PROCESSING
Rev No 54 Status N Date 2004-04-30 Cont ID  
Sent By csiegber Date 2004-04-30 Time 11:33 Rev Time 0.00
Received By csiegber Date 2004-04-30 Time 11:33 Sent To B
Notes
2004-04-30 00:00:00TO RB DESK/SUBMITTAL/PT CABLE
 ELONGATION

Review Stop I INCOMING/PROCESSING
Rev No 53 Status N Date 2004-04-26 Cont ID  
Sent By csiegber Date 2004-04-26 Time 13:11 Rev Time 0.00
Received By csiegber Date 2004-04-26 Time 13:11 Sent To B
Notes
2004-04-26 00:00:00TO RB DESK/SUBMITTAL/POUR LETTERS

Review Stop I INCOMING/PROCESSING
Rev No 52 Status N Date 2004-04-22 Cont ID  
Sent By alange Date 2004-04-22 Time 12:01 Rev Time 0.00
Received By alange Date 2004-04-22 Time 12:01 Sent To B
Notes
2004-04-22 00:00:00TO SH DESK

Review Stop I INCOMING/PROCESSING
Rev No 51 Status N Date 2004-04-20 Cont ID  
Sent By csiegber Date 2004-04-20 Time 08:44 Rev Time 0.00
Received By csiegber Date 2004-04-20 Time 08:44 Sent To B
Notes
2004-04-20 00:00:00TO RB DESK/5 SUBMITTALS
 POUR LETTERS & LETTERS
 REVIEWING STRESSING 4/14/04 & SSK-75B
 75C, 75A & 5TH FLOOR EAST BANDED TENDONS
 & SUPPORT & 4TH FLOOR WEST PARKING

Review Stop I INCOMING/PROCESSING
Rev No 50 Status N Date 2004-04-14 Cont ID  
Sent By csiegber Date 2004-04-14 Time 10:20 Rev Time 0.00
Received By csiegber Date 2004-04-14 Time 10:20 Sent To B
Notes
2004-04-14 00:00:00TO RB DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 49 Status N Date 2004-04-08 Cont ID  
Sent By csiegber Date 2004-04-08 Time 14:22 Rev Time 0.00
Received By csiegber Date 2004-04-08 Time 14:22 Sent To B
Notes
2004-04-08 00:00:00TO RB DESK/SUBMITTAL/ONMJ LETTERS 3/17/4

Review Stop I INCOMING/PROCESSING
Rev No 48 Status N Date 2004-04-08 Cont ID  
Sent By csiegber Date 2004-04-08 Time 14:03 Rev Time 0.00
Received By csiegber Date 2004-04-08 Time 14:03 Sent To B
Notes
2004-04-08 00:00:00TO RB DESK/SUBMITTAL/POUR LETTER

Review Stop I INCOMING/PROCESSING
Rev No 47 Status N Date 2004-04-06 Cont ID  
Sent By csiegber Date 2004-04-06 Time 08:50 Rev Time 0.00
Received By csiegber Date 2004-04-06 Time 08:50 Sent To B
Notes
2004-04-06 00:00:00TO RB DESK/SUBMITTAL/CONC MIX DESIGN

Review Stop I INCOMING/PROCESSING
Rev No 46 Status N Date 2004-04-01 Cont ID  
Sent By csiegber Date 2004-04-01 Time 14:04 Rev Time 0.00
Received By csiegber Date 2004-04-01 Time 14:04 Sent To B
Notes
2004-04-01 00:00:00TO RB DESK/2ND WEST PARKING SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 45 Status N Date 2004-04-01 Cont ID  
Sent By csiegber Date 2004-04-01 Time 14:03 Rev Time 0.00
Received By csiegber Date 2004-04-01 Time 14:03 Sent To B
Notes
2004-04-01 00:00:00TO RB DESK/LEVEL S SHORING PLAN

Review Stop I INCOMING/PROCESSING
Rev No 44 Status N Date 2004-04-01 Cont ID  
Sent By csiegber Date 2004-04-01 Time 14:02 Rev Time 0.00
Received By csiegber Date 2004-04-01 Time 14:02 Sent To B
Notes
2004-04-01 00:00:00POUR LETTERS

Review Stop I INCOMING/PROCESSING
Rev No 43 Status N Date 2004-04-01 Cont ID  
Sent By csiegber Date 2004-04-01 Time 14:01 Rev Time 0.00
Received By csiegber Date 2004-04-01 Time 14:01 Sent To B
Notes
2004-04-01 00:00:00TO RB DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 42 Status N Date 2004-04-01 Cont ID  
Sent By csiegber Date 2004-04-01 Time 14:01 Rev Time 0.00
Received By csiegber Date 2004-04-01 Time 14:01 Sent To B
Notes
2004-04-01 00:00:00TO RB DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 41 Status   Date 2004-03-25 Cont ID  
Sent By ptjomsto Date 2004-03-25 Time 16:02 Rev Time 0.00
Received By ptjomsto Date 2004-03-25 Time 16:01 Sent To  
Notes
2004-03-25 00:00:00GIVEN TO DON NEELY

Review Stop I INCOMING/PROCESSING
Rev No 40 Status N Date 2004-03-23 Cont ID  
Sent By csiegber Date 2004-03-23 Time 08:57 Rev Time 0.00
Received By csiegber Date 2004-03-23 Time 08:57 Sent To B
Notes
2004-03-23 00:00:00TO RB DESK/SUBMITTAL/5TH LEVEL LOWER
 POOL DECK-PT CABLE SHOPS

Review Stop I INCOMING/PROCESSING
Rev No 39 Status N Date 2004-03-19 Cont ID  
Sent By csiegber Date 2004-03-19 Time 15:16 Rev Time 0.00
Received By csiegber Date 2004-03-19 Time 15:15 Sent To B
Notes
2004-03-19 00:00:00TO RB DESK/SUBMITTAL/POUR LETTERS/
 STRESSING OPERATION LETTER/6-17 FLOOR
 EAST

Review Stop I INCOMING/PROCESSING
Rev No 38 Status N Date 2004-03-16 Cont ID  
Sent By csiegber Date 2004-03-16 Time 15:23 Rev Time 0.00
Received By csiegber Date 2004-03-16 Time 15:22 Sent To B
Notes
2004-03-16 00:00:00TO RB DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 37 Status N Date 2004-03-16 Cont ID  
Sent By csiegber Date 2004-03-16 Time 12:27 Rev Time 0.00
Received By csiegber Date 2004-03-16 Time 12:27 Sent To B
Notes
2004-03-16 00:00:00TO RB DESK/SUBMITTAL/SHORING

Review Stop I INCOMING/PROCESSING
Rev No 36 Status N Date 2004-03-09 Cont ID  
Sent By csiegber Date 2004-03-09 Time 16:03 Rev Time 0.00
Received By csiegber Date 2004-03-09 Time 16:03 Sent To B
Notes
2004-03-09 00:00:00TO RB DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 35 Status N Date 2004-03-05 Cont ID  
Sent By csiegber Date 2004-03-05 Time 14:43 Rev Time 0.00
Received By csiegber Date 2004-03-05 Time 14:43 Sent To B
Notes
2004-03-05 00:00:00TO RB DESK/REV/SSK 59-68

Review Stop I INCOMING/PROCESSING
Rev No 34 Status N Date 2004-03-05 Cont ID  
Sent By csiegber Date 2004-03-05 Time 08:05 Rev Time 0.00
Received By csiegber Date 2004-03-05 Time 08:05 Sent To B
Notes
2004-03-05 00:00:00TO RB DESK/SUBMITTAL/POUR LETTERS 3/4/04

Review Stop I INCOMING/PROCESSING
Rev No 33 Status N Date 2004-03-04 Cont ID  
Sent By csiegber Date 2004-03-04 Time 16:42 Rev Time 0.00
Received By csiegber Date 2004-03-04 Time 16:22 Sent To B
Notes
2004-03-04 00:00:00TO RB DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 32 Status N Date 2004-03-04 Cont ID  
Sent By csiegber Date 2004-03-04 Time 13:33 Rev Time 0.00
Received By csiegber Date 2004-03-04 Time 13:33 Sent To B
Notes
2004-03-04 00:00:00TO RB DESK/SUBMITTAL/PTE 4TH FLR LETTERS
 & PTE - LETTER &5TH FLOOR EAST

Review Stop I INCOMING/PROCESSING
Rev No 31 Status N Date 2004-03-04 Cont ID  
Sent By csiegber Date 2004-03-04 Time 13:29 Rev Time 0.00
Received By csiegber Date 2004-03-04 Time 13:29 Sent To B
Notes
2004-03-04 00:00:00TO RB DESK/SUBMITTAL/LEVEL 4 & 5/SHORING

Review Stop I INCOMING/PROCESSING
Rev No 30 Status N Date 2004-03-02 Cont ID  
Sent By csiegber Date 2004-03-02 Time 10:04 Rev Time 0.00
Received By csiegber Date 2004-03-02 Time 10:03 Sent To B
Notes
2004-03-02 00:00:00TO RB DESK/SUBMITTAL/POUR LETTERS SLADE

Review Stop I INCOMING/PROCESSING
Rev No 29 Status N Date 2004-02-20 Cont ID  
Sent By csiegber Date 2004-02-20 Time 12:13 Rev Time 0.00
Received By csiegber Date 2004-02-20 Time 12:13 Sent To B
Notes
2004-02-20 00:00:00TO RB DESK/PTE SHOP DRAWS 4TH FL
 POST TENSIONED

Review Stop I INCOMING/PROCESSING
Rev No 28 Status N Date 2004-02-20 Cont ID  
Sent By csiegber Date 2004-02-20 Time 11:29 Rev Time 0.00
Received By csiegber Date 2004-02-20 Time 11:29 Sent To B
Notes
2004-02-20 00:00:00TO RB DESK/SHORING

Review Stop I INCOMING/PROCESSING
Rev No 27 Status N Date 2004-02-18 Cont ID  
Sent By csiegber Date 2004-02-18 Time 15:22 Rev Time 0.00
Received By csiegber Date 2004-02-18 Time 15:22 Sent To B
Notes
2004-02-18 00:00:00TO RB DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 26 Status   Date 2004-02-17 Cont ID  
Sent By ptjomsto Date 2004-02-17 Time 08:11 Rev Time 0.00
Received By ptjomsto Date 2004-02-17 Time 08:11 Sent To  
Notes
2004-02-17 00:00:00PLACED ON DON NEELY'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 25 Status   Date 2004-02-17 Cont ID  
Sent By ptjomsto Date 2004-02-17 Time 08:10 Rev Time 0.00
Received By ptjomsto Date 2004-02-17 Time 08:10 Sent To  
Notes
2004-02-17 00:00:00PLACED ON DON NEELY'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2004-02-11 Cont ID  
Sent By csiegber Date 2004-02-11 Time 14:22 Rev Time 0.00
Received By csiegber Date 2004-02-11 Time 14:22 Sent To B
Notes
2004-02-11 00:00:00TO RB DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2004-02-06 Cont ID  
Sent By csiegber Date 2004-02-06 Time 09:50 Rev Time 0.00
Received By csiegber Date 2004-02-06 Time 09:50 Sent To B
Notes
2004-02-06 00:00:00TO RB DESK/SUBMITTAL/3RD LEVEL PTE

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2004-02-05 Cont ID  
Sent By csiegber Date 2004-02-05 Time 14:30 Rev Time 0.00
Received By csiegber Date 2004-02-05 Time 14:30 Sent To B
Notes
2004-02-05 00:00:00TO RB DESK/SUBMITTAL/PILING AS BUILT LET
 TERS/4TH FLR PT & CALCS

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2004-02-03 Cont ID  
Sent By csiegber Date 2004-02-03 Time 16:22 Rev Time 0.00
Received By csiegber Date 2004-02-03 Time 16:22 Sent To  
Notes
2004-02-03 00:00:00TO DON NEELY DESK

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2004-01-28 Cont ID  
Sent By csiegber Date 2004-01-28 Time 16:41 Rev Time 0.00
Received By csiegber Date 2004-01-28 Time 16:41 Sent To B
Notes
2004-01-28 00:00:00TO RB DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2004-01-21 Cont ID  
Sent By csiegber Date 2004-01-21 Time 16:52 Rev Time 0.00
Received By csiegber Date 2004-01-21 Time 16:52 Sent To B
Notes
2004-01-21 00:00:00TO RB DESK/SUBMITTAL/AS BUILT LOCATIONS/
 #30/#29/#31/#34

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2004-01-12 Cont ID  
Sent By csiegber Date 2004-01-12 Time 10:24 Rev Time 0.00
Received By csiegber Date 2004-01-12 Time 10:24 Sent To B
Notes
2004-01-12 00:00:00TO RB DESK/SUBMITTAL/PTE SHOP DRAWINGS

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2003-12-30 Cont ID  
Sent By csiegber Date 2003-12-30 Time 11:38 Rev Time 0.00
Received By csiegber Date 2003-12-30 Time 11:30 Sent To B
Notes
2003-12-30 00:00:00TO RB DESK/SUBMITTAL/PILE CAP &CECO POUR

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2003-12-12 Cont ID  
Sent By csiegber Date 2003-12-12 Time 14:48 Rev Time 0.00
Received By csiegber Date 2003-12-12 Time 14:48 Sent To  
Notes
2003-12-12 00:00:00TO DON NEELY

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2003-12-05 Cont ID  
Sent By csiegber Date 2003-12-05 Time 09:50 Rev Time 0.00
Received By csiegber Date 2003-12-05 Time 09:50 Sent To B
Notes
2003-12-05 00:00:00TO RB DESK/SSK22-43

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2003-11-20 Cont ID  
Sent By csiegber Date 2003-11-20 Time 16:22 Rev Time 0.00
Received By csiegber Date 2003-11-20 Time 16:22 Sent To  
Notes
2003-11-20 00:00:00TO DON NEELY

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2003-11-18 Cont ID  
Sent By csiegber Date 2003-11-18 Time 10:06 Rev Time 0.00
Received By csiegber Date 2003-11-18 Time 10:06 Sent To B
Notes
2003-11-18 00:00:00TO RB DESK/REV/PILE CAP

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2003-11-06 Cont ID  
Sent By csiegber Date 2003-11-06 Time 11:37 Rev Time 0.00
Received By csiegber Date 2003-11-06 Time 11:37 Sent To B
Notes
2003-11-06 00:00:00TO RB DESK/PT SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2003-11-06 Cont ID  
Sent By csiegber Date 2003-11-06 Time 11:37 Rev Time 0.00
Received By csiegber Date 2003-11-06 Time 11:37 Sent To B
Notes
2003-11-06 00:00:00TO RB DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2003-10-29 Cont ID  
Sent By csiegber Date 2003-10-29 Time 14:14 Rev Time 0.00
Received By csiegber Date 2003-10-29 Time 14:14 Sent To  
Notes
2003-10-29 00:00:00TO DON NEELY DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2003-10-16 Cont ID  
Sent By csiegber Date 2003-10-16 Time 16:38 Rev Time 0.00
Received By csiegber Date 2003-10-16 Time 16:38 Sent To B
Notes
2003-10-16 00:00:00TO RB DESK

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2003-10-14 Cont ID  
Sent By csiegber Date 2003-10-14 Time 12:18 Rev Time 0.00
Received By csiegber Date 2003-10-14 Time 12:18 Sent To B
Notes
2003-10-14 00:00:00TO RB DESK/SUBMITTALS OF GROUT MIX/FROUT
 & LINTEL/REBAR SHOP DRAWINGS

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-10-08 Cont ID  
Sent By csiegber Date 2003-10-08 Time 11:54 Rev Time 0.00
Received By csiegber Date 2003-10-08 Time 11:54 Sent To B
Notes
2003-10-08 00:00:00TO RB DESK/SUBMITTAL PT CALC/DRAWINGS

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-10-08 Cont ID  
Sent By csiegber Date 2003-10-08 Time 11:51 Rev Time 0.00
Received By csiegber Date 2003-10-08 Time 11:51 Sent To B
Notes
2003-10-08 00:00:00TO RB DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-09-22 Cont ID  
Sent By csiegber Date 2003-09-22 Time 15:24 Rev Time 0.00
Received By csiegber Date 2003-09-22 Time 15:24 Sent To B
Notes
2003-09-22 00:00:00TO RB DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-07-09 Cont ID  
Sent By shernand Date 2003-07-09 Time 16:29 Rev Time 0.00
Received By shernand Date 2003-07-09 Time 16:29 Sent To  
Notes
2003-07-09 00:00:00COMM BOARD #35,5 PLANS AND SET OF SPECS
 ON RACK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-04-10 Cont ID  
Sent By shernand Date 2003-04-10 Time 10:12 Rev Time 0.00
Received By shernand Date 2003-04-10 Time 10:12 Sent To  
Notes
2003-04-10 00:00:00COMM BOARD #45, LARGE PLANS ON TOP RACK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-02-19 Cont ID  
Sent By dpalmer Date 2003-02-19 Time 15:01 Rev Time 0.00
Received By dpalmer Date 2003-02-13 Time 15:01 Sent To  
Notes
2003-02-19 00:00:00TO #43 COMM BOARD, 1 ROLL IN 43 2 ROLLS
 ON RACK AT CONF ROOM. SECOND SHELF FROM
 BOTTOM.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-12 Cont ID  
Sent By sgraham Date 2003-02-13 Time 09:57 Rev Time 0.00
Received By dpalmer Date 2003-02-12 Time 15:07 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 19 Status P Date 2005-07-25 Cont ID  
Sent By prafter Date 2005-07-25 Time 08:08 Rev Time 1.00
Received By prafter Date 2005-07-25 Time 08:07 Sent To  
Notes
2005-07-25 00:00:00MECH. REVISION #11 ALTERED.
  
 VENTILATION ROOF GOOSNECK AT PUMP
 ROOM ( REV. 12 ) AC- 7 .
  
 PAT RAFTER.

Review Stop M MECHANICAL (A/C)
Rev No 18 Status P Date 2005-06-27 Cont ID  
Sent By hmoser Date 2005-06-27 Time 12:36 Rev Time 0.00
Received By hmoser Date 2005-06-27 Time 12:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 17 Status F Date 2005-06-20 Cont ID  
Sent By hmoser Date 2005-06-20 Time 08:05 Rev Time 0.00
Received By hmoser Date 2005-06-20 Time 08:04 Sent To  
Notes
2005-06-20 00:00:00PLAN DENIED
 CAN NOT VENT POOL EQUIPMENT EXHAUST IN
 PARKING GARAGE.
 PLANREVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 16 Status P Date 2005-06-16 Cont ID  
Sent By hmoser Date 2005-06-16 Time 13:54 Rev Time 0.00
Received By hmoser Date 2005-06-16 Time 13:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 15 Status P Date 2005-06-04 Cont ID  
Sent By hmoser Date 2005-06-04 Time 11:43 Rev Time 0.00
Received By hmoser Date 2005-06-04 Time 11:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 14 Status P Date 2005-05-23 Cont ID  
Sent By pkrauss Date 2005-05-23 Time 07:47 Rev Time 0.35
Received By pkrauss Date 2005-05-23 Time 07:47 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 13 Status P Date 2005-04-25 Cont ID  
Sent By pkrauss Date 2005-04-25 Time 06:38 Rev Time 0.25
Received By pkrauss Date 2005-04-25 Time 06:38 Sent To  
Notes
2005-04-25 00:00:00SUBMITTAL LETTER FROM THE ENGINEER ON
 THE DOORS FOR THE A/C CLOSET.

Review Stop M MECHANICAL (A/C)
Rev No 12 Status P Date 2005-03-30 Cont ID  
Sent By pkrauss Date 2005-03-30 Time 07:28 Rev Time 0.00
Received By pkrauss Date 2005-03-30 Time 06:37 Sent To  
Notes
2005-03-30 00:00:00REVISION AC-05/SUBMITTED AS A "BUILDING
 REVISION" INSTEAD OF A MECHANICAL
 PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 11 Status P Date 2005-03-11 Cont ID  
Sent By pkrauss Date 2005-03-15 Time 15:28 Rev Time 1.20
Received By pkrauss Date 2005-03-11 Time 11:29 Sent To  
Notes
2005-03-11 00:00:00REVISION AC-5 / SEE ALSO PLAN SHEET AC-6
 FOR SEQUENCE OF OPERATION FOR THE SMOKE
 CONTROL TO THE COMMON AREAS (FITNESS &
 PARTY ROOMS)

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2005-02-10 Cont ID  
Sent By pkrauss Date 2005-02-10 Time 10:36 Rev Time 1.00
Received By pkrauss Date 2005-02-10 Time 08:28 Sent To  
Notes
2005-02-10 00:00:00REVISIONS PLAN SHEETS:
 AC-01, AC-04, AC-05 & AC-06 APPROVED.
 AWAITING ORIGINAL PLAN SHEET AC-9C-CU.

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2005-01-12 Cont ID  
Sent By pkrauss Date 2005-01-12 Time 16:49 Rev Time 0.30
Received By pkrauss Date 2005-01-12 Time 16:49 Sent To  
Notes
2005-01-12 00:00:00FIRE DAMPER FOR DUCT PENETRATING ELEV
 LOBBY WILL BE AT THE CORRIDOR WALL
 THEREFOR REVERSING THE PROIR SUBMITTAL.

Review Stop M MECHANICAL (A/C)
Rev No 8 Status   Date 2004-12-08 Cont ID  
Sent By pkrauss Date 2004-12-07 Time 13:33 Rev Time 0.40
Received By pkrauss Date 2004-12-07 Time 13:31 Sent To  
Notes
2004-12-07 00:00:00AWAITING RESPONSE FROM WEITZ AS TO THE
 RATING OF THE CORRIDOR WALL.ARCH &
 PLUMBING PLANS MAY NEED TO BE REVISED.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2004-10-25 Cont ID  
Sent By pkrauss Date 2004-10-25 Time 13:59 Rev Time 0.55
Received By pkrauss Date 2004-10-25 Time 13:59 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2004-09-20 Cont ID  
Sent By pkrauss Date 2004-09-18 Time 10:07 Rev Time 1.40
Received By pkrauss Date 2004-09-18 Time 10:07 Sent To  
Notes
2004-09-18 00:00:00PLAN SHEET AC-13 WAS NOT APPROVED.
 CLARIFY RATIONAL FOR DELETING INDICATOR
 LIGHT FROM THE DRYER.WILL DRYER BE
 INCAPACITATED SHOULD THE BOOSTER FAN
 FAIL?PLEASE MAKE NOTE AS TO THE
 INTENT ON THE PLAN.AS PER OUR ORIGINAL
 MEETING, DRYER MUST NOT BE USED IF THE
 BOOSTER FAN FAILS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2004-07-14 Cont ID  
Sent By pkrauss Date 2004-07-14 Time 11:15 Rev Time 0.55
Received By pkrauss Date 2004-07-14 Time 11:15 Sent To  
Notes
2004-07-14 00:00:00REVISIONS/AC-1,6,8ACCU,11,12

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-06-07 Cont ID  
Sent By pkrauss Date 2004-06-07 Time 08:57 Rev Time 1.45
Received By pkrauss Date 2004-06-07 Time 06:33 Sent To  
Notes
2004-06-07 00:00:00PROVISO:
 PLAN SHEET AC-1 - SMOKE EXHAUST DUCT
 FROM THE MANAGERS OFFICE THROUGH THE
 WALL INTO THE GARAGE, FIRE DAMPER IS NOT
 INDICATED.THE DUCT APPEARS TO BE 12" X
 10" THEREFORE DOES NOT FALL UNDER THE
 EXCEPTION UNDER 607.1.3, DUCT IS GREATER
 THAN 100 SQ INCHES AND SHALL HAVE NO
 OPENINGS FOR NOT LESS THAN 5 FT FROM
 RATED WALL.PLEASE CLARIFY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-07-28 Cont ID  
Sent By pkrauss Date 2003-07-28 Time 15:32 Rev Time 1.00
Received By pkrauss Date 2003-07-28 Time 15:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-05-17 Cont ID  
Sent By pkrauss Date 2003-05-17 Time 08:29 Rev Time 3.50
Received By pkrauss Date 2003-05-17 Time 08:02 Sent To  
Notes
2003-05-17 00:00:00DENIED:
  
 1.PLAN SHEET AC-1, EXHAUST FROM
 BATHROOM & PARCEL RM. PENETRATING2 HR
 WALL, NO FIRE DAMPER INDICATED.
  
 2.COMMENT #4 FROM PREVIOUS REVIEW
 WAS ANSWERED IN RESPONSE LETTER BUT NOT
 CHANGED ON PLAN (AC-5 & AC-6 ELEV LOBBY)
 PLAN INDICATES A FIRE DAMPER ONLY NOT
 A COMBINATION DAMPER.PLEASE CORRECT.
  
 3.SEE COMMENTS FROM PLUMBING ON
 CALCULATIONS FOR COMBUSTION AIR.
  
 4.CONDENSING UNIT STANDS ON THE ROOF
 SHALL COMPLY WITH 2001 FBC 1511.7 FOR
 THE DISTANCE BETWEEN THE ROOF SURFACE
 & THE BOTTOM OF THE SUPPORT RAIL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-03-17 Cont ID  
Sent By pkrauss Date 2003-03-11 Time 13:35 Rev Time 8.00
Received By pkrauss Date 2003-03-11 Time 13:35 Sent To  
Notes
2003-03-11 00:00:00PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.PROVIDE OUTSIDE AIR CALCULATIONS FOR
 THE COMMON AREAS, PER 2001 FBC(M) TABLE
 403.3.
  
 2.PROVIDE OUTSIDE A CALCULATIONS FOR
 THE RESIDENTIAL AREAS BY MEANS OF
 NATURAL VENTILATION (2001 FBC(M) 402.2)
 OR MECHANICAL (2001 FBC(M) TABLE 403.3).
  
 3.SMOKE EVAC IS INDICATED FOR THE
 LOBBY & COMMON AREAS.INDICATE WHAT
 WILL BE DONE FOR THE CORRIDOR EXITS IN
 RESIDENTIAL AREAS.SHOW COMPLIANCE WITH
 2001 FBC 412.5.
  
 4.PLAN SHEETS AC-5 & AC-6 - SUPPLY
 PENETRATION AT ELEVATOR LOBBY INDICATES
 A FIRE DAMPER ONLY.PLEASE CLARIFY,
 SHOULD THIS BE A FIRE/SMOKE DAMPER?
  
 5.PLAN SHEET AC-5 PENETRATION TO P/A 4
 MISSING FIRE/SMOKE DAMPER ALSO.
  
 6.MECHANICAL PLANS INDICATE IN-LINE
 BOOSTER FANS FOR THE DRYERS.PROVIDE
 SUBMITTAL FOR THE IN-LINE FAN.INDICATE
 IF ANY PRECAUTIONS ARE TO BE TAKEN
 SHOULD THE FAN FAIL (I.E. ALARM OR SOME
 TYPE OF NOTIFICATION).
  
 7.PROVIDE ENERGY & MANUAL J CALCS AS
 PER 2001 FBC CHAPTER 13.
  
 8.AS PER FAIR HOUSING GUIDELINES THE
 ENVIRONMENTAL CONTROLAS SHALL BE
 POSITIONED IN ACCESSIBLE LOCATIONS.
 HEIGHT REQUIREMENT SHALL BE A MINIMUM
 OF 15" A.F.F. & MAXIMUM OF 48" A.F.F..
  
 9.PROVIDE SEQUENCE OF OPERATION FOR
 ALL AREAS EVAC AS WELL AS SMOKE CONTROL.
 SHOW COMPLIANCE WITH 2001 FBC 412.5
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 14 Status P Date 2005-06-18 Cont ID  
Sent By pschmitz Date 2005-06-18 Time 08:37 Rev Time 0.00
Received By pschmitz Date 2005-06-18 Time 08:37 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 13 Status P Date 2005-03-26 Cont ID  
Sent By kstevens Date 2005-03-26 Time 07:03 Rev Time 1.15
Received By kstevens Date 2005-03-26 Time 07:03 Sent To  
Notes
2005-03-26 00:00:00REVISION OK - SHTS P-8 & P-13
 P-8 CHANGE TO FS & REROUTE RVD LINES
 P-13 VENT REVISION

Review Stop P PLUMBING
Rev No 12 Status F Date 2005-01-10 Cont ID  
Sent By kstevens Date 2005-01-10 Time 14:34 Rev Time 5.80
Received By kstevens Date 2005-01-10 Time 14:34 Sent To  
Notes
2005-01-10 00:00:00REVISION - DENIED
 FOR SHEETS P-3, P-8, P-8, P-9, P-10,
 P-11, P-12, P-13, P-15, &P-16.
  
 1) SHT P-3 NO CHANGES SHOWN FROM
 REVISION SEALED 07/29/04 AND REVIEWED ON
 08/14/04. PLEASE CLAIRFY. SECTION
 104.2.1.
 2) SHT P-8 FLOOR SINK TO BE LOCATED SO
 PIPING FROM RVD SHALL NOT PRESENT A
 TRIPPING HAZARD.
 3) SHTS P-9 & P-10 NO CHANGES SHOWN FROM
 ORIGINAL STAMPED SHEET SEALED 07/08/03
 AND ISSUED 08/07/03. PLEASE CLARIFY.
 SECTION 104.2.1.
 4) SHTS P-11 & P-12 NO CHANGES SHOWN
 FROM REVISION SEALED 06/28/04, REVIEWED
 08/14/04. PLEASE CLARIFY. SECTION
 104.2.1.
 5) SHT P-13 MANY RISERS SHOW REVISION
 NUMBERS 6 & 10 AND CLOUDED AT THE BASE
 OF THE RISERS, BUT NO CHANGES ARE SHOWN
 ARE SHOWN. PLEASE CLAIRFY. SECTION
 104.2.1. - SANT. RISER #1, OFFSET VENT
 REQUIRED BETWEEN 5TH & 6TH FLOORS.
 SECTION 915.1. - SANT. RISER #17,
 HORIZONTAL DRY VENT NOT APPROVED.
 SECTION 905.3.
 6) SHTS P-15 & P-16 NO CHANGES SHOWN
 FROM REVISION SEALED 08/20/04 AND
 REVIEWED 10/06/04. PLEASE CLARIFY.
 SECTION 104.2.1.
  
 FOLLOWING SHEETS REVISIONS APPROVED. -
 P-2, P-5, P-6, P-9A-CU, P-10A-CU, P-17,
 & P-18
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 11 Status P Date 2004-10-20 Cont ID  
Sent By kstevens Date 2004-10-20 Time 17:41 Rev Time 0.50
Received By kstevens Date 2004-10-20 Time 17:41 Sent To  
Notes
2004-10-20 00:00:00REVISION OK - SHT P-17 REVISIONS 4 & 5

Review Stop P PLUMBING
Rev No 10 Status F Date 2004-10-14 Cont ID  
Sent By kstevens Date 2004-10-14 Time 15:17 Rev Time 0.50
Received By kstevens Date 2004-10-14 Time 15:17 Sent To  
Notes
2004-10-14 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 A SANITARY RISER DIAGRAM IS REQUIRED
 SHOWING ALL CHANGES TO BUILDING RISER
 WITH PIPE SIZES, VENTS ECT. SECTION
 104.3.1.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 9 Status F Date 2004-10-06 Cont ID  
Sent By kstevens Date 2004-10-06 Time 14:55 Rev Time 4.00
Received By kstevens Date 2004-10-06 Time 14:55 Sent To  
Notes
2004-10-06 00:00:00REVISIONS OK FOR SHTS P-2, P-6, P-13,
 P-15, & P-16.
  
 REVISIONS DENIED FOR SHT P-9A-CU, NO
 REVISIONS FOUND FOR REVISION NUMBERS 6 &
 7.
  
 REVISION DENIED FOR SHT P-10A-CU, NO
 REVISIONS FOUND FOR REVISIONS 2, 3, 4, &
 5.
  
 REVISION DENIED FOR SHT P-18, NOT ALL
 CHANGES ARE IDENTIFIED BY CLOUDS OR NUM-
 BERS. SEE HIGHLIGHTED AREAS. CHECK ALL
 CHANGES ON PLANS FROM LAST REVISED SHTS
 AND NUMBER/CLOUD ALL CHANGES/REVISIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 8 Status P Date 2004-08-14 Cont ID  
Sent By kstevens Date 2004-08-14 Time 20:18 Rev Time 1.33
Received By kstevens Date 2004-08-14 Time 20:17 Sent To  
Notes
2004-08-14 00:00:00REVISION OK
  
 SHEETS P1, P2, P3, P4, P7, P8, P9 (NO
 CHANGES), P10 (NO CHANGES), P11, P12,
 P14, P15 (NO CHANGES), P16, P17, P18,

Review Stop P PLUMBING
Rev No 7 Status P Date 2004-08-07 Cont ID  
Sent By kstevens Date 2004-08-07 Time 10:43 Rev Time 2.00
Received By kstevens Date 2004-08-07 Time 10:43 Sent To  
Notes
2004-08-07 00:00:00REVISION OK
  
 REVISIONS REQUIRED FOR SANT. RISERS THAT
 REFLECT CHANGES IN THESE UNITS FOR THE
 9TH AND 11TH FLOORS.
  
 REVISION REQUIRED FOR FAIR HOUSING REQ-
 UIREMENTS 1 THROUGH 7.
  
  
  
  
  
  
  
  
  
 M

Review Stop P PLUMBING
Rev No 6 Status P Date 2004-08-06 Cont ID  
Sent By kstevens Date 2004-08-06 Time 07:54 Rev Time 1.25
Received By kstevens Date 2004-08-05 Time 18:52 Sent To  
Notes
2004-08-06 00:00:00REVISIONS TO SHEETS P-5 & P-6 OK - REV-
 ISIONS REQUIRED FOR RISERS TO REFLECT
 THE REVISIONS APPROVED THIS REVIEW.

Review Stop P PLUMBING
Rev No 5 Status F Date 2004-07-30 Cont ID  
Sent By kstevens Date 2004-07-30 Time 12:25 Rev Time 1.00
Received By kstevens Date 2004-07-30 Time 12:25 Sent To  
Notes
2004-07-30 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 SECTION 104.2.1 TWO OR MORE COPIES OF
 PLANS SHALL BE SUBMITTED FOR REVIEW.
 ONLY ONE SET OF IRRIGATION SHEETS HAVE
 BEEN SUBMITTED IN THE THREE SETS OF
 REVISIONS SUBMITTED.
  
 SEPARATE IRRIGATION PERMIT REQUIRED
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status F Date 2004-06-02 Cont ID  
Sent By kstevens Date 2004-06-02 Time 17:32 Rev Time 5.50
Received By kstevens Date 2004-06-02 Time 17:31 Sent To  
Notes
2004-06-02 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT P-8 BOILER ROOM, 1-1/4" RVD SHALL
 NOT DRAIN INTO THE FLOOR DRAIN. FLOOR
 DRAIN IS NOT AN APPROVED INDIRECT WASTE.
 EITHER A FLOOR SINK OR A HUB DRAIN SHALL
 BE APPROVED FOR INDIRECT WASTE PER SEC.
 802.3 OR 802.3.2.
 2) SHT P-9 HAND DRAWN CHANGES ARE NOT
 APPROVED ON SIGNED/SEALED PLANS. RESUB-
 MIT FOR REVIEW NEW SHEETS WITH REVISION
 NUMBER AND CLOUDS. - ALSO SEE SHT P-10
 3) SHT P-9A-CU WATER HAMMER REQUIRED AT
 KITCHEN SINK FOR DISH WASHER ON HOT SIDE
 SECTION 604.9.
 4) SHTS P-10, P-16, & P-18 ARE IN PLANS
 UPSIDE DOWN. PLEASE CORRECT AND RESUBMIT
 SECTION 104.2.1.
 5) SHT P-10A-CU UNIT COMBO 16-17 PLEASE
 CLARIFY WHICH UNITS IS THIS A COMBO OF?
 CLARIFY NOTE [1], IT STATES OFFSET @
 CEILING UNDER SLAB OF 11TH LEVEL & 9TH
 LEVEL. IS THIS SHEET FOR THE 16TH & 17TH
 FLOORS? - ALSO NO HAND DRAWN CHANGES ON
 SIGNED/SEALED PLANS. SECTION 104.2.1.
 6) SHT P-11 NO HAND DRAWN CHANGES TO A
 SIGNED/SEALED SET OF PLANS. SHOW REVIS-
 ION NUMBER AND CLOUDS. SECTION 104.2.1.
 7) SHTS P-12 & P-15 NOT REVISIONS INDI-
 CATED. PLEASE CLARIFY. SECTION 104.2.1.
 8) SHT P-13 SANT. RISER #39, OFFSET VENT
 REQUIRED PER SECTION 915. SEE ATTACHED
 SHEET FOR OFFSET VENT REQUIREMENTS.
 9) VENT STACK FOR SANT. RISERS SHALL
 CONNECT AT OR BELOW LOWEST HORIZONTAL
 BRANCH AT BASE OF STACK. SEE ATTACHED
 SHEET FOR EXAMPLE. RISERS WITH VENT
 STACKS SHOW THE VENT STACK CONNECTING AT
 THE FIXTURES OF THE FIRST BRANCH. THIS
 IS NOT APPROVED. SECTION 903.4.
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 - INITIALS ARE NOT ACCEPTABLE PER FBPE
 RULING. MINIMUM FIRST & LAST NAME REQ-
 UIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-07-22 Cont ID  
Sent By kstevens Date 2003-07-22 Time 13:40 Rev Time 2.00
Received By kstevens Date 2003-07-21 Time 18:45 Sent To  
Notes
2003-07-22 00:00:00PLUMBING OK - SEPARATE GAS PERMIT REQD.
 MANUF CUT SHEETS REQUIRED FOR POOL HEAT-
 ERS. W/HEATER & BOILER CUT SHEETS OK

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-04-29 Cont ID  
Sent By kstevens Date 2003-04-28 Time 16:00 Rev Time 10.50
Received By kstevens Date 2003-04-26 Time 17:48 Sent To  
Notes
2003-04-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
 FHA-AMEND 98 DESIGN MANUAL
  
 1) FROM PREVIOUS REVIEW. INDICATE THE
 OPENINGS FOR THE W/C'S (WATER CLOSETS)
 PER FHA DESIGN MANUAL. (#2) SHT A5.1.08
 2) FROM PREVIOUS REVIEW. (#7) THE DRAIN
 FROM THE SPRINKLER SHALL DRAIN TO SANT.
 NOT STORM. INDIRECT WASTE INTO A FLOOR
 SINK IS REQUIRED. SHT P-2
 3) FROM PREVIOUS REVIEW. (#8) THE BACK-
 WASH FROM THE POOL FILTERS SHALL DRAIN
 TO SANITARY. SHT P-5/P-4
 4) FROM PREVIOUS REVIEW. (#9) PLEASE
 NOTE THAT THE 3" COLD WATER RISER ON SHT
 P2 IS NEXT TO THE COLUUM ON SHT P-2 AND
 P-3 BUT CHANGES TO 4" COLD WATER ON SHT
 P-4, AND CHANGES BACK TO 3" ON SHT P-5.
 4" DOMESTIC FEED IS SHOWN ON SHTS P-2, &
 P-3 BUT CHANGES TO 3" ON SHT P-4 THEN
 BACK TO 4" ON SHT P-5. PLEASE CLAIRFY.
 5) FROM PREVIOUS REVIEW. (#16) TWO AREAS
 HAVE PIPE SIZE THAT IS TOO SMALL. PLEASE
 CORRECT PIPE SIZE. SHT P-16
 6) FROM PREVIOUS REVIEW. (#17) CLEANOUTS
 REQUIRED PER 708.3.1, 708.3.3 & 708.3.4
 PLEASE SHOW ON PLANS.
 7) FROM PREVIOUS REVIEW. (#18) RELIEF
 VENTS REQUIRED IN SOIL AND WASTE STACKS
 HAVING MORE THAN 10 BRANCH INTERVALS.
 PLEASE SHOW ON RISERS.
 8) FROM PREVIOUS REVIEW. (#20) SOME
 PIPES ARE UNDERSIZED FOR THE AMOUNT OF
 FIXTURE UNITS. SEE 4" @ 251 FU & 4" @
 254 FU. SHT P-16
 9) SHT P-18 STORM BLDG DRAIN AND RISERS,
 SOME SIZES WRONG AND PIPE SIZING NOT
 SHOWN ON SOME PIPES. ALSO SQUARE FOOTAGE
 NOT SHOWN FOR GD'S. PLEASE SIZE ALL PIPE
 AND CORRECT THE SIZE FOR THOSE SECTIONS
 THAT HAVE MORE SQ FT THAN ALLOWED BY
 TABLE 1106.3 @ 4.5 INCHES PER HOUR RAIN-
 FALL.
 10) FROM PREVIOUS REVIEW. (GAS #6) SUB-
 MIT CALCULATIONS FOR COMBUSTION AIR, PER
 FBC-2001 FUEL GAS CODE SECTION 304.
 RESPONSE NOTED, BUT NO CALCULATION FOUND
 SHTS 17 OR 8.
 11) FROM PREVIOUS REVIEW. (GAS #9)
 SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 12) SHT P-18 PLEASE INDICATE WHICH TABLE
 FROM THE FBC-2001 GAS CODE WILL BE USED
 FOR SIZING THE GAS SYSTEM. WE HAVE NOT
 ADOPTED THE NFPA-54 CODE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-03-15 Cont ID  
Sent By kstevens Date 2003-03-15 Time 11:23 Rev Time 10.50
Received By kstevens Date 2003-03-15 Time 11:23 Sent To  
Notes
2003-03-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
 FHA-AMEND 98 DESIGN MANUAL
  
 1) SHT A5.1.05 DETAIL #1 EMPLOYEE REST-
 ROOM, DOOR CAN NOT OPEN INTO THE CLEAR
 FLOOR SPACE OF ANY FIXTURE OR THE 5'
 TURNING CIRCLE. 11-4.22.2. TURNING RADI-
 US SHALL BE UNOBSTURCTED.
 2) SHT A5.1.08 UNIT BATHROOM INTERIOR
 ELEVATIONS, INDICATE OPENINGS FOR W/C'S
 AND LAV HEIGHTS PER FHA DESIGN MANUAL.
 3) SHT A-7.1.0.6 ROOF DRAINS FOR CANOPY,
 PLEASE PROVIDE DRAIN DETAIL, PIPING
 DIAGRAM AND SHOW WHERE THE PIPING TERM-
 INATES.
 4) SHT A-7.1.1.6 DETAIL #1 BREAKROOM
 ELEVATION, PER SECTION 11-4.24.2, MAX.
 HEIGHT FOR SINK SHALL BE 2'10". 2'11"
 SHOWN.
 5) SHTS P-2 AND P-16, VENTS REQUIRED FOR
 FLOOR DRAINS IN PUMP ROOMS.
 6) SHT P-2 MORE INFORMATION REQUIRED FOR
 DEEP STORAGE TANK IN TRANSFORMER VAULT.
 IS THERE ANY PIPING FOR THIS TANK? WHAT
 WILL BE STORED?
 7) SHT P-2 NUMBER 4 IN BOX INDICATES A
 3" SPRINKLER DRAIN, BUT WAS UNABLE TO
 LOCATE. THIS SHALL DRAIN TO SANITARY.
 PLEASE INDICATE WHERE THIS DRAIN IS.
 8) SHT P-5 POOL EQUIPMENT ROOM SHOWS A
 6" HUB DRAIN, BUT IS NOT SHOWN ON ANY
 RISER. PLEASE INDICATE WHAT THE DRAIN IS
 FOR AND WHERE IT PIPES TO. IF IT IS AN
 INDIRECT WASTE IT WILL REQUIRE A FLOOR
 SINK AND SHALL PIPE TO SANITARY.
 9) SHT P-3 3" WATER FOR COOLING TOWER &
 5" DOMESTIC WATER CHANGES ON SHT P-4, &
 CHANGES BACK ON SHT P-5. PLEASE CLAIRFY.
 10) SHT P-6 SANITARY DRAIN LINES DO NOT
 REFLECT FIXTURE LAYOUT FOR PUBLIC BATH-
 ROOM DETAIL.
 11) SHT P-8 WATER SUPPLY LINES FOR COOL-
 ING TOWER SHOWS 3" SUPPLY FROM PUMP, AND
 ANOTHER 3" LINE (#7) TYING INTO THE SYS-
 TEM. WHERE IS THIS LINE COMMING FROM. IS
 THIS A CROSS CONNECTION FROM THE DOMES-
 TIC WATER? PLEASE CLAIRFY.
 12) SHTS P-9 UNIT A-1, & P-10 UNITS B-2A
 B-3, & B-2B, SECTION 909.1 WET VENT.
 ONLY THE FIXTURES WITHIN THE BATHROOM
 GROUP SHALL CONNEDT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. THE WASHMACHINE
 ON THESE STACKS SHALL DRAIN DOWNSTREAM
 OF THE BATHROOM GROUPS. ALSO MAKE CHANG-
 ES TO RISER DIAGRAM SHT P-13.
 13) SHT P-12 WATER RISER DIAGRAMS (ALL).
 AIR CHAMBERS ARE NOT APPROVED. PLEASE
 DELETE THESE FROM THE RISER DIAGRAMS.
 14) WATER RISER FOR PUBLIC BATHROOMS DO
 NOT REFLECT THE FIXTURE LAYOUT. NO WATER
 TO THE SHOWERS, DRINKING FOUNTAINS NOT
 SHOWN ON MENS, 4 LAVS IN WOMENS ROOM.
 PLEASE CLAIRFY.
 15) SHT P-16 SANT. RISER TO PUBLIC BATHS
 DO NOT REFLECT THE FLOOR PLAN.
 16) SHT P-16 PLEASE INDICATE PITCH FOR
 ALL SANITARY PIPE. ALL PIPE WILL BE RUN
 AT A UNIFORM PITCH. SIZING INDICATES
 1/2" PER FOOT REQUIRED FOR SIZE OF PIPE
 AND NUMBER OF FIXTURES UNITS.
 17) SHTS P-2 & P-16 CLEAN OUTS REQUIRED
 PER SECTION 708.3.1 IN THE BLDG DRAIN,
 MAX. 100', PER SECTION 708.3.4 AT CHANGE
 OF DIRECTION OVER 45 DEGREES, AND AT THE
 BASE OF EACH STACK PER 708.3.4. PLEASE
 SHOW C/O'S WHERE REQUIRED.
 18) SHT P-13 SOIL AND WASTE STACKS IN
 BLDGS. HAVING MORE THAN 10 BRANCH INTER-
 VALS SHALL BE PROVIDED WITH A RELIEF
 VENT AT EACH 10TH INTERVAL INSTALLED BE-
 GINNING WITH THE TOP FLOOR. SEC 914.1
 19) PLEASE PROVIDE A HORIZONTAL CONDEN-
 SATE BLDG DRAIN LINE. SHOW ALL PIPE
 SIZES, POINT OF TERMINATION, AND SUPPLY
 CALCULATIONS FOR GALLONS PER MINUTE OF
 DISCHARGE FOR SYSTEM. SYSTEM SHALL RUN
 SEPARATELY OUT OF BLDG WITH A RELIEF
 VENT AS IS EXITS BLDG.
 20) PLEASE PROVIDE A HORIZONTAL BLDG
 STORM DRAIN. SHOW ALL PIPE SIZES, PITCH,
 ACCUMULATED SQUARE FOOTAGE, AND TERMIN-
 ATION POING.
 21) PLEASE PROVIDE A STORM RISER DIAGRAM
 SHOW ALL ROOF DRAIN SIZES, SQ FT DRAINED
 PIPE SIZE, PITCH, AREA DRAINS, AND
 PLANTER DRAINS WITH ACCUMULATED SQ FT.
 22) HEALTH DEPT REVIEW REQUIRED FOR
 FACILITIES FOR POOLS.
 23) SEPARATE PERMIT REQUIRED FOR POOLS.
 24) A GREASE TRAP WILL PROBABLY BE REQ-
 UIRED IF ANY OF THE USES FOR THE RETAIL
 SPACE MENTIONED ON SHT G-4 THAT PREPARE
 OR SERVE FOOD ARE USED. IN THAT EVENT,
 PER UTILITY ORD #2938-96 RODNEY COMPO,
 ENVIRONMENTAL COMPLIANCE WILL BE CONTAC-
 TED FOR GREASE TRAP SIZE. (561) 837-4074
 25) SHT P-8 COOLING TOWER DRAIN TO SAN-
 ITARY AND OVER FLOW TO STORM.
 26) SHT P-8 SHOWS 3" GAS LINE AT WATER
 HEATERS, BUT P-2 SHOWS ONLY 2" GAS AT
 METER. PLEASE CLAIRFY.
 27) SEPARATE GAS PERMIT REQUIRED. THE
 FOLLOWING IS REQUIREMENTS FOR APPLYING.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 28) SEPARATE PERMIT REQUIRED FOR GREASE
 TRAP.
 29) SEPARATE PERMIT REQUIRED FOR IRRIGA-
 TION.
 30) SHT P-2 PENETRATIONS INTO AND OPEN-
 INGS THROUGH A STAIRWAY ENCLOSURE ASSEM-
 BLY ARE PROHIBITED EXCEPT FOR REQUIRED
 EXIT DOORS, DUCTWORK AND EQUIPMENT NEC-
 ESSARY FOR INDEPENDENT STAIR PRESSUREIZ-
 ATION, SPRINKLER PIPING, STANDPIPES AND
 ELECTRICAL CONDUIT SERVING THE STAIRWAY
 AND TERMINATING ATY A STEEL BOX. - THE
 GAS LINE RUNNING THROUGH THE STAINWAY IS
 NOT ALLOWED.SECTION 1006.1.3.1
 30)...........
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 3 Status P Date 2005-07-11 Cont ID  
Sent By mmclean Date 2005-07-11 Time 16:26 Rev Time 0.00
Received By mmclean Date 2005-07-11 Time 16:26 Sent To B
Notes
2005-07-11 00:00:00OK PER ANGELLA JONES-VANN,
 ADMINISTRATOR, PLANNING & ZONING.

Review Stop Z ZONING
Rev No 2 Status P Date 2005-02-23 Cont ID  
Sent By mmclean Date 2005-02-23 Time 16:35 Rev Time 0.00
Received By mmclean Date 2005-02-23 Time 16:35 Sent To B
Notes
2005-02-23 00:00:00REVISION APPROVED BY ANGELLA JONES-VANN
 FOR AN ARCHITECTURAL REVISION WAS
 SUBMITTED ON 2/1/05 FOR SHEETS A1.1.01,
 A1.1.03 AND A2.1.05A.ONE OF MY
 COMMENTS IS AS FOLLOWS:
  
 2) SHEET A1.1.03THE PARKING TABLE HAS
 NOT BEEN REVISED TO REFLECT THE
 REDUCTION IN THE NUMBER OF PARKING
 SPACES.
 THE PROPOSED REVISION WILL OMIT PARKING
 SPACES 367 AND 368.THE REVISED PLANS
 HAVE BEEN ROUTED TO THE ZONING PLAN
 REVIEWER FOR RECORD/REVIEW.

Review Stop Z ZONING
Rev No 1 Status P Date 2003-02-13 Cont ID  
Sent By dpalmer Date 2003-02-12 Time 15:07 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***