Plan Review Details - Permit 03020790
Plan Review Stops For Permit 03020790
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-03-07 Cont ID  
Sent By dpalmer Date 2003-03-06 Time 07:52 Rev Time 2.50
Received By lsmith Date 2003-03-07 Time 15:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-07-10 Cont ID  
Sent By btrobaug Date 2003-07-10 Time 17:06 Rev Time 0.50
Received By btrobaug Date 2003-07-10 Time 16:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-03-14 Cont ID  
Sent By shernand Date 2003-07-09 Time 08:41 Rev Time 0.50
Received By btrobaug Date 2003-03-14 Time 08:55 Sent To  
Notes
2003-03-14 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE CORRECT THE PLANS TO REFLECT THE
 FOLLOWING:
  
 1} PLEASE CORRELATE THE OCP AND
 CONDUCTOR SIZE FOR AHU #2.
  
 2} PLEASE INDICATE THE OCP FOR"SP PMP".
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-03-06 Cont ID  
Sent By sthyng Date 2003-03-12 Time 16:21 Rev Time 0.33
Received By dpalmer Date 2003-03-06 Time 07:04 Sent To B
Notes
2003-03-06 00:00:00********* NOTES/PROVISO******
  
 1)NOTE: PLEASE CORRELATE OCP AND AWG
 FOR AHU #2. SHOW 2P-60A ON#10.
  
 2)NOTE: PLEASE SEE RISER DIAGRAM, SHOWS
 A EXT PANEL AND NO PANEL SCHEDULE IS
 SUBMITTED. RISER SHOWS ITEMS FROM EXT
 PANEL AND DOES NOT LIST ANY OCP .
  
 3)NOTE: PLEASE SEE MISSING RECEPT
 UPSTAIRS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ROUGH INSPECTION.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-09 Cont ID  
Sent By shernand Date 2003-07-09 Time 08:41 Rev Time 0.00
Received By shernand Date 2003-07-09 Time 08:41 Sent To E
Notes
2003-07-09 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-12 Cont ID  
Sent By sthyng Date 2003-03-12 Time 16:21 Rev Time 0.00
Received By sthyng Date 2003-03-12 Time 16:21 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-12 Cont ID  
Sent By dpalmer Date 2003-02-12 Time 16:42 Rev Time 0.00
Received By dpalmer Date 2003-02-12 Time 16:42 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-03-04 Cont ID  
Sent By jleech Date 2003-03-01 Time 08:13 Rev Time 0.33
Received By jleech Date 2003-03-04 Time 16:49 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-03-01 Cont ID  
Sent By sgraham Date 2003-02-19 Time 12:26 Rev Time 0.25
Received By jleech Date 2003-03-01 Time 08:13 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-02-19 Cont ID  
Sent By dpalmer Date 2003-02-12 Time 16:42 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***