Plan Review Details - Permit 03020682
Plan Review Stops For Permit 03020682
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-03-12 Cont ID  
Sent By alange Date 2003-08-11 Time 10:38 Rev Time 5.00
Received By lhatten Date 2003-03-08 Time 18:18 Sent To  
Notes
2003-03-12 00:00:00REVIEW & STAMPED PLANS 03/08/2003

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-08-09 Cont ID  
Sent By dpalmer Date 2005-08-09 Time 19:46 Rev Time 0.20
Received By dpalmer Date 2005-08-09 Time 19:45 Sent To  
Notes
2005-08-09 00:00:00CORRECTED PANEL SCHEDULE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-07-21 Cont ID  
Sent By dpalmer Date 2005-07-21 Time 13:02 Rev Time 0.33
Received By dpalmer Date 2005-07-21 Time 13:02 Sent To  
Notes
2005-07-21 00:00:00REDLINED:
 PLEASE SEE NUMEROUS AWG'S ON B-2 WHICH
 DOES NOT CORRELATE WITH OCP. ALL AWG'S
 SHOWN HIGHER THAN REQUIRED??
 PLEASE SEE 26ABRKR SHOWN ON A/C PANEL.
 (MISPRINT).

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-11-20 Cont ID  
Sent By btrobaug Date 2003-11-20 Time 11:42 Rev Time 0.50
Received By btrobaug Date 2003-11-20 Time 11:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-03-04 Cont ID  
Sent By pkrauss Date 2003-03-03 Time 10:24 Rev Time 1.00
Received By btrobaug Date 2003-03-04 Time 12:53 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-08-08 Cont ID  
Sent By adarroug Date 2005-08-08 Time 11:14 Rev Time 0.00
Received By adarroug Date 2005-08-08 Time 11:14 Sent To E
Notes
2005-08-08 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-07-20 Cont ID  
Sent By adarroug Date 2005-07-20 Time 14:09 Rev Time 0.00
Received By adarroug Date 2005-07-20 Time 14:09 Sent To E
Notes
2005-07-20 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-04-22 Cont ID  
Sent By adarroug Date 2005-04-22 Time 17:43 Rev Time 0.00
Received By adarroug Date 2005-04-22 Time 17:43 Sent To E
Notes
2005-04-22 00:00:00TO "BTROBAUG" DESK

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-01-13 Cont ID  
Sent By csiegber Date 2004-01-13 Time 14:39 Rev Time 0.00
Received By csiegber Date 2004-01-13 Time 14:39 Sent To M
Notes
2004-01-13 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-12-02 Cont ID  
Sent By csiegber Date 2003-12-02 Time 16:42 Rev Time 0.00
Received By csiegber Date 2003-12-02 Time 16:42 Sent To M
Notes
2003-12-02 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-08-11 Cont ID  
Sent By alange Date 2003-08-11 Time 10:38 Rev Time 0.00
Received By alange Date 2003-08-11 Time 10:38 Sent To B
Notes
2003-08-11 00:00:00TO LH DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-07-31 Cont ID  
Sent By alange Date 2003-07-31 Time 13:58 Rev Time 0.00
Received By alange Date 2003-07-31 Time 13:57 Sent To B
Notes
2003-07-31 00:00:00TO LH DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-03-18 Cont ID  
Sent By sthyng Date 2003-03-18 Time 08:32 Rev Time 0.00
Received By sthyng Date 2003-03-18 Time 08:32 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-02-27 Cont ID  
Sent By dpalmer Date 2003-02-27 Time 14:02 Rev Time 0.00
Received By dpalmer Date 2003-02-27 Time 14:02 Sent To  
Notes
2003-02-27 00:00:00SUBMITTAL ADDED TO PLANS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-11 Cont ID  
Sent By dpalmer Date 2003-02-11 Time 09:34 Rev Time 0.00
Received By dpalmer Date 2003-02-11 Time 09:34 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-01-26 Cont ID  
Sent By pkrauss Date 2004-01-26 Time 14:49 Rev Time 0.25
Received By pkrauss Date 2004-01-26 Time 14:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2003-12-08 Cont ID  
Sent By csiegber Date 2004-01-13 Time 14:39 Rev Time 0.33
Received By pkrauss Date 2003-12-08 Time 07:25 Sent To  
Notes
2003-12-08 00:00:00DENIED:
 BEDROOM #3 - SUPPLY DUCT INDICATED TO
 THE BEDROOM AS 4" 25 CFM?
  
 BEDROOM #4 - SUPPLY DUCT TO INDICATES
 9" AND RETURN IS ONLY 8" 2001 FBC(M)
 601.4, RETURN SHALL BE EQUAL TO SUPPLY.
  
 PLEASE CORRECT & RE-SUBMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-03-19 Cont ID  
Sent By csiegber Date 2003-12-02 Time 16:43 Rev Time 0.35
Received By pkrauss Date 2003-03-19 Time 10:18 Sent To B
Notes
2003-03-19 00:00:00MECHANICAL PERMIT 03020685

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-03-03 Cont ID  
Sent By sthyng Date 2003-03-18 Time 08:32 Rev Time 1.00
Received By pkrauss Date 2003-03-03 Time 09:22 Sent To E
Notes
2003-03-03 00:00:00PLEASE CLARIFY THE FOLLOWING INFORMATION
  
 1.CONDENSING UNIT SCHEDULE INDICATES
 11 SEER FOR C.U. #1A & 1B, ENERGY CACLS
 SHOW A 11.5 SEER UNIT.
  
 2.AHU SCHEDULE INDICATES 1995 CFM FOR
 AHU #1, MANUAL J CALCS SHOW 2,221.
  
 3.FAN SHUTDOWN REQUIRED AS PER 2001
 FBC(M) 606.2.1.
  
 4.PLEASE NOTE, SHOULD GAS DRYER BE
 INSTALLED, CHECK ROOM VOLUME FOR
 CLASSIFICATION OF "CONFINED" (LESS THAN
 50 CUBIC FT PER 1,000 BTUS OF THE AGGRE-
 GATE INPUT RATING OF ALL APPLIANCES
 INSTALLED IN THAT SPACE).CONFINED
 SPACES SHALL COMPLY WITH 2001 FBC(M) 703
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-02-28 Cont ID  
Sent By sgraham Date 2003-02-19 Time 14:09 Rev Time 0.25
Received By kstevens Date 2003-02-28 Time 17:41 Sent To  
Notes
2003-02-28 00:00:00NO PLUMBING SHOWN ON PLANS - SEPARATE
 POOL PERMIT REQUIRED.

Review Stop Z ZONING
Rev No 1 Status P Date 2003-02-19 Cont ID  
Sent By dpalmer Date 2003-02-11 Time 09:34 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***