Review Stop P PLUMBING
Rev No 1 Status P Date 2003-02-10 Cont ID  
Sent By kstevens Date 2003-02-10 Time 16:56 Rev Time 0.50
Received By kstevens Date 2003-02-10 Time 16:56 Sent To  
Notes
2003-02-10 00:00:00PASSED/PROVISO
  
 1100 CU. FT. REQUIRED FOR DRYER ROOM.
 405 CU. FT. PROVIDED @ 8' CEILING.
 CONFINED SPACE - TWO OPENINGS REQUIRED
 WITH A MINIMUM OF 100 SQ. IN. PER SEC
 304.3.1