Plan Review Stops For Permit 03020550 |
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2003-02-10 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-02-10 |
Time |
17:09 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2003-02-10 |
Time |
17:09 |
Sent To |
|
|
Notes |
2003-02-10 00:00:00 | PASSED/PROVISO | | | | 1100 CU. FT. REQUIRED FOR DRYER ROOM. | | 497 CU. FT. PROVIDED @ 9'4" CEILING. | | CONFINED SPACE - TWO OPENINGS REQUIRED | | MINIMUM OF 100 SQ. IN. EACH PER SEC | | 304.3.1 |
|
|
|