Plan Review Details - Permit 03020461
Plan Review Stops For Permit 03020461
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-04-15 Cont ID  
Sent By dpalmer Date 2003-04-09 Time 06:41 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2003-04-14 00:00:00PROVISO
  
 1) SUBMIT SOIL BORING TEST REPORT AS
 REQUIRED BY FBC 1804.2.2, PRIOR TO
 POURING FOUNDATION.
  
 2) SUBMIT REVISION INDICATING THAT NO
 OPENINGS ARE IN ANGLED WALL THAT IS
 WITHIN 3 FEET OF PROPERTY LINE.
  
 3) SUBMIT REVISED INSTALLATION SCHEDULE
 FOR STORM PANELS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-03-04 Cont ID  
Sent By shernand Date 2003-04-08 Time 08:34 Rev Time 4.00
Received By rmcdouga Date 2003-03-04 Time 13:22 Sent To P
Notes
2003-03-04 00:00:00BUILDING DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PROVIDE A SOIL BORING TEST REPORT AS
 REQUIRED BY FBC 1804.1.1.
  
 4) REVISE THE CONSTRUCTION TYPE TO VI
 UNDER GENERAL NOTES ON C1.
  
 5) INDICATE THE INTERNAL PRESSURE
 COEFFICENT WITH THE DESIGN CRITERIA ON
 ON C1.
  
 6) THE NOTE AT THE BOLLARD ON A2 REFERS
 TO DETAIL #54. THIS DETAIL DOES NOT
 APPEAR ON THE PLANS.
  
 7) SUBMIT THE MANUFACTURER'S SPECS. AND
 UL LISTING INFORMATION FOR THE ONE HOUR
 FIRE RATED GLASS BLOCK ASSEMBLY.
  
 8) THERE ARE TWO DETAILS LABELED #1 ON
 A6. ONE OF THE SHOULD BE #7.
  
 9) THE ENERGY CALCULATIONS INCORRECTLY
 LIST THE EXTERIOR WALLS AS WOOD FRAME.
  
 10) SPECIFY THAT THE DOOR BETWEEN THE
 GARAGE AND CONDITIONED SPACE IS REQUIRED
 TO BE A SOLID CORE DOOR PER FBC CHAPTER
 13.
  
 11) THERE ARE TWO DIFFERENT SHEETS
 NUMBERED A4. PLEASE CORRECT.
  
 12) THE DETAILS ON A4 ARE INCORRECTLY
 LABELED AS A3.
  
 13) INDICATE ON THE SLIDING GLASS DOOR
 BUCK DETAIL THAT ANCHORS ARE REQUIRED TO
 BE FASTENED THROUGH BUCKS AND INTO THE
 SUBSTRATE.
  
 14) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - SINGLE FRENCH DOOR
 - DOUBLE OUTSWING GLAZED DOORS (NOA THAT
 WAS SUBMITTED IS A PRELIMINARY REPORT)
  
 15) ONE PAGE OF THE DRAWINGS IS MISSING
 FROM THE SINGLE HUNG WINDOW PRODUCT
 APPROVAL.
  
 16) THE OPENING SIZE GIVEN ON THE PLANS
 FOR THE GLASS BLOCK EXCEEDS THE MAXIMUM
 SIZE ALLOWED BY THE PRODUCT APPROVAL.
  
 17) INDICATE ON THE PLANS THAT THE WALL
 BETWEEN THE GARAGE AND THE CONDITIONED
 SPACE IS INSULATED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-11-04 Cont ID  
Sent By dpalmer Date 2003-11-04 Time 09:36 Rev Time 0.33
Received By dpalmer Date 2003-11-04 Time 09:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-04-09 Cont ID  
Sent By csiegber Date 2003-10-28 Time 15:22 Rev Time 0.25
Received By dpalmer Date 2003-04-09 Time 06:39 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-02-20 Cont ID  
Sent By hmoser Date 2003-02-18 Time 20:05 Rev Time 0.25
Received By dpalmer Date 2003-02-20 Time 06:35 Sent To B
Notes
2003-02-20 00:00:00**************** UNSAT ************
  
 1)NOTE: SD NOT PERMITTED IN KITCHEN PER
 NFPA-72 8-1.4.1.2
  
 2)NOTE: SERVICE SHOWN AS 400A, PLEASE
 SIZE GROUNDING ELECTRODE CONDUCTORS PER
 250-66 BASED ON SEC`S FROM 310-15.
  
 3)NOTE: MAIN SHOWS A PANEL "B"? PLEASE
 PROVIDE PANEL SCHEDULE AND SHOW PANEL
 ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-28 Cont ID  
Sent By csiegber Date 2003-10-28 Time 15:22 Rev Time 0.00
Received By csiegber Date 2003-10-28 Time 15:22 Sent To E
Notes
2003-10-28 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-08 Cont ID  
Sent By shernand Date 2003-04-08 Time 08:33 Rev Time 0.00
Received By shernand Date 2003-04-08 Time 08:33 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-06 Cont ID  
Sent By dpalmer Date 2003-02-06 Time 17:15 Rev Time 0.00
Received By dpalmer Date 2003-02-06 Time 17:15 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-02-18 Cont ID  
Sent By hmoser Date 2003-02-18 Time 20:05 Rev Time 0.25
Received By hmoser Date 2003-02-18 Time 20:05 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-03-06 Cont ID  
Sent By rmcdouga Date 2003-03-04 Time 13:22 Rev Time 0.25
Received By kstevens Date 2003-03-06 Time 11:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-02-07 Cont ID  
Sent By dpalmer Date 2003-02-06 Time 17:15 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***