Plan Review Stops For Permit 03020431 |
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2003-02-14 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-02-14 |
Time |
09:24 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2003-02-14 |
Time |
09:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2003-02-11 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-02-11 |
Time |
13:31 |
Rev Time |
1.15 |
Received By |
pkrauss |
Date |
2003-02-11 |
Time |
13:30 |
Sent To |
|
|
Notes |
2003-02-11 00:00:00 | DENIED: | | REFERENCE BUILDING PERMIT 01091426 | | 1997 SBC.PLANS CALL FOR A 1 HR RATED | | BECAUSE OF 3 STORY CONSTRUCTION. | | MECHANICAL PLANS NEED TO REFLECT WHAT | | PROTECTION IS BEING USED FOR THE | | PENETRATIONS OF THESE RATED FLOORS, | | CEILINGS ETC. (RADIATION DAMPERS AT | | 1ST & 2ND FL LEVELS FIRE DAMPER AT | | 3RD FL GRILLE?)PLEASE CLARIFY. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
|