Plan Review Details - Permit 03020296
Plan Review Stops For Permit 03020296
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-02-25 Cont ID  
Sent By dpalmer Date 2003-02-20 Time 07:45 Rev Time 2.00
Received By jgomez Date 2003-02-24 Time 17:55 Sent To  
Notes
2003-02-25 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-FLOOD ZONE A8. NEED TO PROVIDE THE
 ELEVATION CERTIFICATE.
 3-REVISE HANDRAIL DIMENSION ON STAIR
 SECTION B/A-4. SEE SECTION 1007.5.1
 FBC 2001.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-02-20 Cont ID  
Sent By hmoser Date 2003-02-19 Time 19:00 Rev Time 0.25
Received By dpalmer Date 2003-02-20 Time 07:44 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-08 Cont ID  
Sent By shernand Date 2003-07-08 Time 16:12 Rev Time 0.00
Received By shernand Date 2003-07-08 Time 16:12 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-04 Cont ID  
Sent By dpalmer Date 2003-03-04 Time 08:48 Rev Time 0.00
Received By dpalmer Date 2003-03-04 Time 08:48 Sent To M
Notes
2003-03-04 00:00:00TO HM`S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-06 Cont ID  
Sent By dpalmer Date 2003-02-06 Time 12:46 Rev Time 0.00
Received By dpalmer Date 2003-02-06 Time 12:46 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-07-11 Cont ID  
Sent By pkrauss Date 2003-07-11 Time 14:46 Rev Time 0.25
Received By pkrauss Date 2003-07-11 Time 14:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-03-10 Cont ID  
Sent By shernand Date 2003-07-08 Time 16:12 Rev Time 0.25
Received By hmoser Date 2003-03-10 Time 18:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-02-19 Cont ID  
Sent By dpalmer Date 2003-03-04 Time 08:49 Rev Time 0.25
Received By hmoser Date 2003-02-19 Time 19:00 Sent To E
Notes
2003-02-19 00:00:00PLAN DENIED
 1) ENERGY PERFORMANCE LEVEL DISPLAY CARD
 AND ENERGY CALCULATIONS DO NOT MATCH.
 2) EQUIPMENT SELESTION ON MANUAL (J) NOT
 COMPLETE.
 3) COOLING & HEATING BTU.ON MANUAL (J)
 DO NOTMATCH PLANS.
 PLAN REVIEW BY HAROLD MOSER
 (561)689-8096 EXT.8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-02-14 Cont ID  
Sent By sgraham Date 2003-02-07 Time 15:44 Rev Time 0.00
Received By lsmith Date 2003-02-25 Time 11:39 Sent To  
Notes
2003-03-19 00:00:00PER KS2/14/03 LS

Review Stop Z ZONING
Rev No 1 Status P Date 2003-02-07 Cont ID  
Sent By dpalmer Date 2003-02-06 Time 12:46 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***