Plan Review Details - Permit 03020281
Plan Review Stops For Permit 03020281
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-02-27 Cont ID  
Sent By dpalmer Date 2003-02-20 Time 07:56 Rev Time 2.00
Received By jgomez Date 2003-02-27 Time 11:47 Sent To  
Notes
2003-02-27 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-FLOOD ZONE A8. NEED THE ELEVATION
 CERTIFICATE.
 3-SHEET A-1: REVISE NOTE #24. SEE SEC.
 1007.5.1 FBC 2001 FOR HANDRAIL HEIGHT.
 4-GLASS BLOCK TO BE SAFETY GLASS IF FACE
 THICKNESS IS LESS THAN 0.25". SECTION
 2405.2.2 FBC 2001.
 5-SHEET A-4: REVISE NOTE #1. SEE SECTION
 1007.5.1 FBC 2001 FOR HANDRAIL HEIGHT.
 6-PROVIDE GENERAL SPECS FOR FIREBLOCKING
 AT ALL CONCEALED SPACES AS REQUIRED BY
 SEC. 2305.1.4 FBC 2001.
 7-PROVIDE COMPLETE DETAIL/SECTION FOR
 CONNECTION AT TOP OF COLUMN LOCATED
 BETWEEN GARAGE AND KITCHEN. CLARIFY
 HOW ARE STRAPS HOLDING THE TWO GIRDER
 TRUSSES. SEC. 104.2.1.2 CITY AMENDMENT
 8-SHEET S-3: PROVIDE SPECS ON STRUCTURAL
 WALL SECTIONS FOR FIRECUT REQUIREMENTS
 SEC. 2305.4 FBC 2001.
 9-GARAGE DOOR STRUCTURAL BUCK DETAIL:
 SPECIFY EMBEDMENT FOR ANCHOR AND SIZE
 OF WASHER. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-08-11 Cont ID  
Sent By dpalmer Date 2003-08-11 Time 06:30 Rev Time 0.25
Received By dpalmer Date 2003-08-11 Time 06:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-02-20 Cont ID  
Sent By alange Date 2003-08-05 Time 15:46 Rev Time 0.25
Received By dpalmer Date 2003-02-20 Time 07:56 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-08-05 Cont ID  
Sent By alange Date 2003-08-05 Time 15:46 Rev Time 0.00
Received By alange Date 2003-08-05 Time 15:45 Sent To E
Notes
2003-08-05 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-31 Cont ID  
Sent By alange Date 2003-07-31 Time 15:01 Rev Time 0.00
Received By alange Date 2003-07-31 Time 15:01 Sent To E
Notes
2003-07-31 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-04 Cont ID  
Sent By dpalmer Date 2003-03-04 Time 08:26 Rev Time 0.00
Received By dpalmer Date 2003-03-04 Time 08:26 Sent To M
Notes
2003-03-04 00:00:00TO HM'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-06 Cont ID  
Sent By dpalmer Date 2003-02-06 Time 12:41 Rev Time 0.00
Received By dpalmer Date 2003-02-06 Time 12:41 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-08-11 Cont ID  
Sent By pkrauss Date 2003-08-11 Time 08:01 Rev Time 0.25
Received By pkrauss Date 2003-08-11 Time 07:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-03-10 Cont ID  
Sent By hmoser Date 2003-03-10 Time 19:17 Rev Time 0.25
Received By hmoser Date 2003-03-10 Time 19:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-02-19 Cont ID  
Sent By dpalmer Date 2003-03-04 Time 08:26 Rev Time 0.25
Received By hmoser Date 2003-02-19 Time 18:11 Sent To E
Notes
2003-02-19 00:00:00PLAN DENIED
 1) ENERGY PERFORMANCE LEVEL DISPLAY CARD
 AND ENERGY CALCULATIONS DO NOT MATCH.
 2) EQUIPMENT SELESTION ON MANUAL (J) NOT
 COMPLETE.
 3) COOLING & HEATING BTU.ON MANUAL (J)
 DO NOTMATCH PLANS.
 PLAN REVIEW BY HAROLD MOSER
 (561)689-8096 EXT.8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-02-10 Cont ID  
Sent By sgraham Date 2003-02-06 Time 14:35 Rev Time 0.25
Received By kstevens Date 2003-02-10 Time 13:39 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-02-06 Cont ID  
Sent By dpalmer Date 2003-02-06 Time 12:41 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***