Plan Review Details - Permit 03012452
Plan Review Stops For Permit 03012452
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-05-15 Cont ID  
Sent By sthyng Date 2003-05-13 Time 18:22 Rev Time 3.00
Received By sthyng Date 2003-05-13 Time 18:22 Sent To M
Notes
2003-05-13 00:00:00******CORRECTIONS*******
  
 1.)FOUR SHEETS OF 2B WERE SUBMITTED;
 TWO ARE UNSEALED.UNSURE AS TO WHY TWO
 EXTRA COPIES WERE SUBMITTED BUT THEY
 NEED TO BE SIGNED AND SEALED IF THEY ARE
 TO BE A PART OF THE PERMIT PACKAGE.
  
 2.)PROVIDE A LICENSE NUMBER FOR THE
 ARCHITECT; HAVE HIM SIGN,SEAL & DATE THE
 PLAN AS HIS TITLE BLOCK IS ON THE PLAN.
  
 3.)SEPARATE PERMITS REQUIRED;ELECTRIC,
 PLUMBING, MECHANICAL, ROOFING.
  
 4.)A NOTICE OF COMMENCEMENT IS
 REQUIRED TO BE FILED WITH THE CLERK OF
 COURTS BEFORE A PERMIT CAN BE ISSUED.
  
 5.)SEE PREVIOUS CORRECTION NOTICE,
 ITEM #1.SUBMIT PRODUCT APPROVALS FOR
 THE MULLIONS, GARAGE DOOR, AND 3'0X6'8
 DOOR.
  
 6.)IF YOU MAKE CHANGES TO A SEALED
 DRAWING IN INK, THE CHANGES MUST BE
 INITIALED BY WHOEVER SEALS THE PLAN.
  
 7.)FBC 1606.1.7, INFORMATION REQUIRED
 TO BE ON DRAWINGS.
  
 8.)CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC, 2111.1.9 'WHERE EXTERIOR
 WALL MASONRY UNITS BEAR ON A CONCRETE
 FLOOR SURFACE, A 1.5 INCH RECESS SHALL
 BE PROVIDED TO MINIMIZE WATER INTRUSION
 INTO FINISHED AREA.'
  
 9.)ENERGY CALCS REQUIRED FBC13-101.2.
  
 10.)FBC 2307.1.1, SILL ANCHORAGE TO
 HAVE A MINIMUM EMBEDMENT OF 7".
  
 11.)FIRESTOP REQUIRED FBC 705.3.
  
 12.)PROVIDE NUMBER OF SOFFIT VENTS
 REQUIRED WITH SIZES.
  
 13.)ATTIC ACCESS REQUIRED FBC 2309.
  
 14.)AREA CALCULATIONS SHOULD SHOW A
 TOTAL OF LIVING SPACE, AND A TOTAL OF
 NON-A/C SPACE, NOT SHOW CALCS BY FLOOR.
  
 15.)PROVIDE ROOF SHEATHING ATTACHMENT
 SCHEDULE, CITY OF WPB AMENDMENTS TO
 THE FBC, TABLE 2306.1.
  
 16.)FBC 1403.1.6, 6" CLEARANCE FROM
 EXTERIOR WALL COVERING TO EARTH.
  
 17.)PROVIDE ATTACHMENT UPLIFT
 INFORMATION.
  
 18.)THE SITE PLAN SHOWS A NEW
 DRIVEWAY, SLAB ON THE NORTH SIDE OF THE
 PROPERTY, AND ADDITIONS TO THE FRONT
 AND REAR OF THE EXISTING HOUSE.REVISE
 TO REFLECT THE WORK TO BE PERFORMED
 UNDER THIS PERMIT.THE TRUSS PLANS
 SHOW WORK FOR THE ADDITION TO THE
 EXISTING HOUSE.
  
 19.)THE PREVIOUS CORRECTION LIST #3,
 SUBMIT DETAILED DRAWINGS OF THE STAIRS,
 WAS NOT ADDRESSED. ONLY DRAWINGS FOR THE
 LANDING WERE GIVEN.STAIRS AND HANDRAIL
 TO COMPLY WITH FBC 1007.
  
 20.)REFERENCE THE LANDING DETAIL;
 IN REGARDS TO THE POST TO BE
 EMBEDDED 2' INTO THE GROUND, IS THAT
 FOR THE SHORT POST AT THE BASE OF THE
 STAIRS, OR THE TALL POST GOING TO THE
 TOP OF THE STAIRS, OR BOTH?WILL THERE
 BE ANYTHING STABILIZING THE POSTS IN
 THE GROUND (STEEL THROUGH THE BASE,
 CONCRETE)?
  
 21.)ANY CHANGES TO THE PLAN MUST GET
 HISTORIC APPROVAL.CHANGES WERE DRAWN
 IN FOR WINDOW SIZE AND CHANGING SINGLE
 WINDOWS TO DOUBLE.AFTER MAKING THE
 CHANGES TO THE PLAN, CLOUDED, TAKE BACK
 TO HISTORIC TO BE STAMPED.
  
 WHEN RESUBMITTING, PLEASE ASSEMBLE TWO
 COMPLETE PLAN SETS, IN ORDER.OLD
 SHEETS ARE TO BE BOUND SEPARATELY.
 MAKE A NOTATION ON THIS LIST AS TO HOW
 EACH ITEM HAS BEEN ADDRESSED IN ORDER
 TO EXPEDITE PLAN REVIEW.CLOUD CHANGES
 MADE TO THE PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-04-01 Cont ID  
Sent By pkrauss Date 2003-03-05 Time 16:23 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
2003-04-01 00:00:00************FAILED*************
 1. WINDOWS ON PLANS SHOW IMPACT GLASS.
 SUBMIT PRODUCT APPROVAL FOR ALL
 OPENINGS PER FBC 2001. (DOORS &
 WINDOWS,INCLUDING MULLS, EXTERIOR
 DOORS)2. SUBMIT FLA. ENERGY CODE FORM
 FOR A/C LIVING AREA.
 3. SUBMIT DETAILED DRAWINGS ON STAIRS
 TOMEET CODE.
 4. SEPARATE PERMITS REQUIRED FOR
 ELECTRIC, PLUMBING AND MECHANICAL WORK.
 5. PLANS MUST BE SUBMITTED TO PBC FOR
 IMPACT FEES FOR ADDITIONAL LIVING AREA.
 6. IF WINDOWS ARE NOT IMPACT WINDOWS
 STORM PANELS WILL HAVE TO BE INSALLED
 PER FBC 2001 BY SEPARATE PERMIT &
 SUBMITTAL OF PRODUCT APPROVAL &
 SCHEDULE SHOWING SPACING OF ANCHORS.
  
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH,BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-05-13 Cont ID  
Sent By dpalmer Date 2003-05-13 Time 08:34 Rev Time 1.00
Received By dpalmer Date 2003-05-13 Time 08:34 Sent To  
Notes
2003-05-13 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SEE RISER DIAGRAM, A
 NEW LARGER SERVICE IS NOW BEING SHOW
 W/WIRE NOT RATED FOR FOR SERVICE SIZE,
 PLEASE SIZE CONDUCTORS PER 310-15,240-3
  
 2)NOTE:PLEASE CLARIFY GROUNDING ELECTR-
 ODE COMING FROM CONDUIT.??
 PLEASE SHOW GROUNDING ELECTRODE FOR
 BLDG AS / FOOTER STEEL, COLD WATER ETC
 PER 250-50/250-31
  
 3)NOTE: PLEASE CLARFIY SIZE OF EXISTING
 SEC`S AND METER. SHOW EXISTING MAIN OCP.
  
 4)NOTE: PLEASE SEE RISER DIAGRAM, SHOWS
 12 CIR PANEL AND 150 PANEL SCHEDULE
 SHOWS ATLEAST 28?
  
 5)NOTE: PLAN SHOWS METER AT SAME BLDG,
 AND YET NO OTHER (EXIST) MAIN/DISC IS
 SHOWN?? 230-72/215-5 ETC
  
 PLEASE NOTE, ALL PLANS MUST BE
 SIGNED DATED AND SEALED BY THE ARCH/ENG
 OF RECORD. PER FS/FAC 471.025/481.221
 61G15-23.002/61G1-16.004,,,
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE QUESTIONS, PLEASE
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-03-04 Cont ID  
Sent By shernand Date 2003-05-09 Time 08:56 Rev Time 1.00
Received By dpalmer Date 2003-03-04 Time 14:40 Sent To M
Notes
2003-03-04 00:00:00*************** UNSAT ***************
  
 1)NOTE: PANEL NOT PERMITTED IN BATHROOM
 240-24E
  
  
 2)NOTE: PLEASE SHOW LOCATION OF SERVICE
 AND PLEASE SEE 230-72 FOR GROUPING OF
 MAINS.
  
 3)NOTE: PLEASE SEE 210-52-C1 FOR OUTLET
 SPACING ALONG KITCHEN COUNTERSPACE.
  
 4)NOTE: RISER DIAGRAM SHOWS AN EQUIPMENT
 GROUND BETWEEN METER AND MAIN DISC.
 EQUIPMENT GROUNDING CONDUCTOR IS ONLY
 INSTALLED AFTER THE FIRST MEANS OF DISC.
 250-24
  
 5)NOTE: PLEASE PLACE A SD IN LIVING/
 ADAPTABLE SLEEPING AREA ON SECONG FLOOR.
  
 6)NOTE:PLEASE LIST THE REQ`D BATH
 CIRCUIT PER 210-52D/210-11-C3, 20A,#12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096
 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-09 Cont ID  
Sent By shernand Date 2003-05-09 Time 08:56 Rev Time 0.00
Received By shernand Date 2003-05-09 Time 08:56 Sent To E
Notes
2003-05-09 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-31 Cont ID  
Sent By sgraham Date 2003-02-11 Time 13:08 Rev Time 0.00
Received By btrobaug Date 2003-01-31 Time 17:48 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2003-05-15 Cont ID  
Sent By sthyng Date 2003-05-15 Time 16:59 Rev Time 0.25
Received By pkrauss Date 2003-05-15 Time 15:27 Sent To  
Notes
2003-05-15 00:00:00NO MECHANICAL PLANS SUBMITTED FOR REVIEW
 NO ENERGY OR MANUAL J CACLS - HISTORIC

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-03-05 Cont ID  
Sent By sthyng Date 2003-05-13 Time 19:16 Rev Time 0.30
Received By pkrauss Date 2003-03-05 Time 16:21 Sent To B
Notes
2003-03-05 00:00:00NO MECHANICAL PLANS SUBMITTED FOR REVIEW
 NO ENERGY OR MANUAL J CALCS - HISTORIC

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-02-27 Cont ID  
Sent By kstevens Date 2003-02-27 Time 10:34 Rev Time 0.33
Received By kstevens Date 2003-02-27 Time 10:33 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-02-11 Cont ID  
Sent By btrobaug Date 2003-01-31 Time 17:48 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***