Plan Review Stops For Permit 03012264 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2003-01-29 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2003-01-29 |
Time |
17:05 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2003-01-29 |
Time |
17:05 |
Sent To |
|
|
Notes |
2003-01-29 00:00:00 | 1) DUCT SMOKE DETECTORS ARE REQUIRED TO | | ACTIVATE THE FIRE ALARM SYSTEM. A | | SUPERVISORY SIGNAL WILL NOT BE ALLOWED. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|