Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2003-02-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-01-30 |
Time |
12:41 |
Rev Time |
1.00 |
Received By |
pkrauss |
Date |
2003-02-10 |
Time |
15:25 |
Sent To |
|
|
Notes |
2003-02-10 00:00:00 | PROVISO: | | | | PLANS DO NOT INDICATE RATED WALLS, | | FLOORS OR PARTITIONS.PLEASE INDICATE | | ALL FIRE DAMPERS WHETHER NEW OR EXISTING | | ON PLAN. | | | | FIRE DAMPERS SHALL BE INSTALLED IN | | ACCORDANCE WITH MANUFACTURER'S | | INSTALLATION INSTRUCTIONS IN THE | | FOLLOWING LOCATIONS. | | 1. DUCTS PENETRATING WALLS OR PARTITIONS | | HAVING FIRE RESISTANCE RATING OF 1 OR | | MORE HRS. | | 2. DUCTS PENETRATING SHAFT WALLS HAVING | | A FIRE RESISTANCE RATING OF 1 OR MORE | | HRS. | | 3. DUCTS PENETRATING ONLY ONE FLOOR OF A | | BUILDING REQUIRING THE PROTECTION OF | | VERTICAL OPENING (FIRE DAMPER). | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
|