Plan Review Details - Permit 03012114
Plan Review Stops For Permit 03012114
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-03-18 Cont ID  
Sent By lhatten Date 2003-03-18 Time 06:52 Rev Time 2.50
Received By lhatten Date 2003-02-27 Time 06:50 Sent To  
Notes
2003-03-18 00:00:00REVIEW & STAMPED PLANS 02/27/2003
 REDLINED CORRECTIONS PER STEVE WALSH
 CALC. FEES & PRINT CARD 03/18/2003

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-02-11 Cont ID  
Sent By btrobaug Date 2003-02-13 Time 09:46 Rev Time 4.00
Received By rmcdouga Date 2003-02-11 Time 15:13 Sent To M
Notes
2003-02-11 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PLEASE CLARIFY NOTE #9 UNDER GENERAL
 NOTES ON SHEET 1 TO INCLUDE WINDOWS THAT
 ARE WITHIN THREE FEET HORIZONTALLY OF
 THE TUB OR SHOWER. SEE FBC 2405.2.1.
  
 3) SPECIFY ON THE PLANS THAT THE WIRE
 MESH IN THE SLAB IS REQUIRED TO BE
 SUPPORTED AT A MAXIMUM OF THREE FEET ON
 CENTER PER FBC 1909.3.
  
 4) SPECIFY THE SIZES OF THE FIXED GLASS
 TRANSOM AND THE SIDELITE AT THE FRONT
 DOOR ON THE PLANS.
  
 5) THE ROOF FRAMING PLAN ON 3A, 3B AND
 3C SPECIFY AN A-5 TRUSS CONNECTOR FOR
 THE HIP GIRDER AT THE GARAGE. THERE IS
 NO A-5 CONNECTOR LISTED IN THE ANCHOR
 SCHEDULE ON SHEET 2. PLEASE CLARIFY.
  
 6) PLEASE SPECIFY THE LENGTH OR EMBED
 DEPTH OF THE 5/8" EXPANSION BOLTS FOR
 THE OVERHEAD GARAGE DOOR BUCKS ON DETAIL
 3 ON SHEET 4.
  
 7) THE ENERGY CALCULATION FORM INDICATES
 THAT THE HVAC CREDIT FOR CEILING FANS IS
 BEING TAKEN. PLEASE INDICATE THE MINIMUM
 FAN SIZE REQUIRED FOR EACH ROOM ON THE
 PLANS. SEE FBC CHAPTER 13-607.1.A.1 AND
 TABLE 6-6.
  
 8) PROVIDE THE MANUFACTURER'S SPECS. AND
 UL LISTING INFORMATION FOR THE ONE HOUR
 RATED GLASS BLOCK ASSEMBLY.
  
 9) THE NORANDEX SITE SPECIFIC PRODUCT
 APPROVALS ARE REQUIRED TO BE SEALED BY
 THE DESIGNER OF RECORD OF THE STRUCTURE
 AND THE LOCATION OF THE JOB IS ALSO
 REQUIRED ON THE FORM. NOTE:THE SIGNATURE
 ON THE PRODUCT APPROVAL SUBMITTED IS
 FROM THE ENGINEER (STEVE WALSH), WHO HAS
 NOT SIGNED AND SEALED THE PLANS FOR THIS
 PROJECT.
  
 10) PROVIDE A PRODUCT APPROVAL FOR THE
 96"X 60" GLIDER WINDOW WITH AN XOX
 CONFIGURATION AS SHOWN ON THE PLANS. THE
 NORANDEX PRODUCT APPROVALS SUBMITTED DO
 NOT COVER THIS SIZE OR CONFIGURATION.
  
 11) THE SURVEY HAS THE INCORRECT LOMR
 CASE NUMBER AND DATE FOR THE FLOOD ZONE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-02-13 Cont ID  
Sent By jleech Date 2003-02-12 Time 18:12 Rev Time 0.50
Received By btrobaug Date 2003-02-13 Time 09:24 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-29 Cont ID  
Sent By dpalmer Date 2003-01-29 Time 13:08 Rev Time 0.00
Received By dpalmer Date 2003-01-29 Time 13:08 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-02-12 Cont ID  
Sent By rmcdouga Date 2003-02-11 Time 17:14 Rev Time 0.33
Received By jleech Date 2003-02-12 Time 18:12 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-02-08 Cont ID  
Sent By sgraham Date 2003-02-04 Time 16:27 Rev Time 0.25
Received By jleech Date 2003-02-08 Time 09:26 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-02-04 Cont ID  
Sent By dpalmer Date 2003-01-29 Time 13:08 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***