Plan Review Details - Permit 03011955
Plan Review Stops For Permit 03011955
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-05-14 Cont ID  
Sent By shernand Date 2003-05-14 Time 16:44 Rev Time 4.00
Received By rmcdouga Date 2003-05-13 Time 11:26 Sent To  
Notes
2003-05-13 00:00:00BUILDING PROVISO
  
 1) SUBMIT PRODUCT APPROVALS FOR INSWING
 DOUBLE FRONT DOORS UNDER A SEPARATE
 PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-04-16 Cont ID  
Sent By shernand Date 2003-05-12 Time 12:07 Rev Time 5.00
Received By rmcdouga Date 2003-04-16 Time 08:45 Sent To  
Notes
2003-04-16 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) THE SOME OF THE DESIGN CRITERA ON A5
 IS NOT CORRECT. THE CITY OF WPB IS NOT
 IN THE HIGH VELOCITY HURRICANE ZONE.
 THE INTERNAL PRESSURE COEFFICENT FOR AN
 ENCLOSED STRUCTURE IS + OR - 0.18.
 THE EXPOSURE CATEGORY IS B. SEE FBC
 TABLES 1606.2B AND 1606.2C FOR WIND
 PRESSURES FOR COMPONENTS AND CLADDING.
  
 4) CASEMENT WINDOWS IN SLEEPING ROOMS
 MUST COMPLY WITH FBC 1005.4 FOR
 EMERGENCY ESCAPE AND RESCUE. THE OFFICE
 WHICH COULD BE USED FOR A BEDROOM MUST
 COMPLY. THE MINIMUM NET CLEAR OPENING
 HEIGHT IS 24" AND WIDTH IS 20". THE
 MINIMUM NET CLEAR OPENING AREA IS 5.7
 SQFT.
  
 5) BECAUSE A FULL BATH IS PROVIDED ON
 HABITABLE GRADE, IT IS REQUIRED BY FBC
 CHAPTER 11 SECTION 11-11 TO HAVE A DOOR
 A 29" CLEAR OPENING.
  
 6) THE CALCULATIONS FOR BEAM (B3) DO NOT
 CONSIDER THE WIND LOADS THAT WOULD BE
 TRANSFERED TO THE BEAM. SEE FBC 1609.
 PLEASE PROVIDE A COVER SHEET WITH A
 TITLE BLOCK (FAC 61G15-30.003) AND A
 SUMMARY WITH CONCLUSIONS.
  
 7) SPECIFY THE LOCATIONS AND MATERIAL
 THAT WILL BE USED TO PROVIDE DRAFTSTOPP-
 ING AT THE FLOOR/CEILING ASSEMBLY. SEE
 FBC 2305.2.2. THIS IS REQUIRED AT THE
 FLOOR TRUSSES ON THE SECOND FLOOR NOT IN
 THE ATTIC.
  
 8) PROVIDE THE MANUFACTURER'S SPECS. AND
 UL LISTING INFORMATION FOR THE PREFAB
 FIREPLACE AND CHIMNEY.
  
 9) INDICATE ON THE STAIR DETAIL THE
 FIREBLOCKING THAT IS REQUIRED FOR THE
 CONCEALED SPACES OF THE STAIRS AT THE
 TOP AND BOTTOM OF THE RUN. FBC 2305.1.4
  
 10) PROVIDE DETAILS FOR THE CONSTRUCTION
 OF THE COLUMNS AT THE FRONT AND REAR
 BALCONIES TO WHICH THE GUARDRAILS ARE
 ATTACHED.
  
 11) UPDATE THE CONCRETE STANDARDS IN THE
 NOTES ON A5 TO ACI-99.
  
 12) PROVIDE PRODUCT APPROVALS FOR THE
 DOUBLE INSWING FRONT DOORS AS SHOWN ON
 THE PLANS.
  
 13) THE LABELS ON THE GARAGE DOOR BUCK
 DETAILS ON A13 ARE REVERSED.
  
 14) PROVIDE DETAILS OF THE TUBE STEEL
 COLUMN CAPS.
  
 15) THE CONNECTOR SPECIFIED FOR THE
 SECOND FLOOR ROOF GIRDER TRUSS(T27,2PLY)
 IS INCORRECT. THIS TRUSS SITS ON TOP OF
 THE TIE BEAM AND A SIMPSON MBHA, WHICH
 IS A HANGER, IS SPECIFIED.
  
 16) THE UPLIFT VALUES SPECIFIED ON THE
 PLANS FOR MOST OF THE ROOF GIRDER
 TRUSSES ARE LOWER THAN REQUIRED BY THE
 TRUSS DRAWINGS. THE CONNECTORS AS
 SPECIFIED WILL NOT BE CAPABLE OF
 RESISTING THE REQUIRED LOADS.
  
 17) THE NEW PLANS WILL HAVE TO BE
 RTEVIEWED AND APPROVED BY THE HISTORIC
 PRESERVATION BEFORE PERMIT IS ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-03-06 Cont ID  
Sent By btrobaug Date 2003-03-06 Time 09:14 Rev Time 8.00
Received By rmcdouga Date 2003-03-06 Time 08:46 Sent To  
Notes
2003-03-06 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SHEET A-13 IS MISSING FROM THE PLANS.
  
 4) THE DESIGN CRITERIA ON A-5 IS NOT
 CORRECT. PLEASE REVISE TO 2001 FBC,
 ASCE 7-98 AND 140 MPH WIND SPEED.
 FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 5) REVISE ROOF FASTENING INFORMATION ON
 A5 TO COMPLY WITH CITY OF WPB AMENDMENTS
 TABLE 2306.1. ZONE 3 SPACING 4"OC AT
 EDGES AND 6"OC INTERMEDIATE. 8D RING
 SHANK NAILS REQUIRED IN ZONE 3 FOR MEAN
 ROOF HEIGHT GREATER THAN 25'.
  
 6) INDICATE ATTIC ACCESS TO SPACE ABOVE
 GUEST ROOM. SEE FBC 2309.6.
  
 7) SEPARATE PERMITS ARE REQUIRED FOR THE
 CONCRETE WALL AND POOL.
  
 8) PROVIDE WINDOW AND DOOR SCHEDULE.
  
 9) EGRESS WINDOWS OR DOORS REQUIRED FOR
 SLEEPING ROOMS. FBC 1005.4
  
 10) THE FULL BATH ON THE GROUND FLOOR IS
 REQUIRED TO HAVE DOORS WITH 29" CLEAR
 OPENING.FBC CHAPTER 11.
  
 11) WINDOWS WITHIN 3' HORIZONTALLY OF
 TUB OR SHOWER SHALL BE SAFETY GLAZING.
 FBC 2405.2 IMPACT GLASS IS ACCEPTABLE.
  
 12) PROVIDE AN ENGINEERED ANALYSIS OF
 THE REINFORCED CONCRETE BLOCK WALL
 SUPPORTING BEAM B-3.
  
 13) SPECIFY THE LOCATIONS AND MATERIAL
 THAT WILL BE USED TO PROVIDE THE
 DRAFTSTOPPING AT THE FLOOR/CEILING
 ASSEMBLY. SEE FBC 2305.2.2.
  
 14) SPECIFY ATTIC VENTILATION REQUIRED
 BY FBC 2309.7.
  
 15) PROVIDE A DETAIL OF THE INTERIOR
 LOAD BEARING WALLS.
  
 16) PROVIDE BUCK DETAILS FOR THE DOORS,
 WINDOWS AND GARAGE DOORS.
  
 17) THE FIRST FLOOR PLAN ON A1 INDICATES
 A 42" PREFAB FIREPLACE AND THE SECTION
 ON A12 IS A MASONRY FIREPLACE. PLEASE
 CLARIFY.
  
 18) INDICATE ON PLANS THAT CHIMNEY IS TO
 EXTEND AT LEAST 2' HIGHER THAN ANY
 PORTION OF ROOF WITHIN 10' HORIZONTALLY.
 SEE FBC 2804.2.4.
  
 19) THE FOOTING INDICATED IN THE SECTION
 ON A12 DOES NOT CORRESPOND WITH THE
 FOUNDATION PLAN ON A2.
  
 20) PROVIDE ADDITIONAL DETAILS FOR THE
 MASONRY CHIMNEY AND FIREPLACE. INCLUDE
 THE FLUE SIZE AND THICKNESS, THE FIRE-
 PLACE DIMENSIONS, FIREBOX LINING, FRESH
 AIR INTAKE, HEARTH EXTENSION DIMENSIONS,
 FIREPLACE OPENING SIZE, ETC. SEE FBC
 2113 AND 2114.
  
 21) FLUE DAMPER IS REQUIRED BY FBC 13-
 606.1.1(3).
  
 22) PROVIDE UL LISTING INFORMATION FOR
 SPARK ARRESTOR.
  
 23) IF PREFAB FIREPLACE PROVIDE
 MANUFACTURER'S SPECIFICATIONS AND
 LISTING INFORMATION.
  
 24) INDICATE FIREBLOCKING AT CONCEALDED
 SPACES OF THE STAIRS AT THE TOP AND
 BOTTOM OF THE RUNS. FBC 2305.1.4(3)
  
 25) GUARDRAILS ON THE OPEN SIDES OF
 STAIRS ARE REQUIRED TO BE 36" HIGH AND
 INTERMEDIATE RAILS SHALL REJECT THE
 PASSAGE OF A 4" SPHERE. SEE FBC 1015 AND
 1026.5
  
 26) SPECIFY THE BALCONY RAILINGS HEIGHT,
 INTERMEDIATE RAIL SPACING, BOTTOM RAIL
 HEIGHT, FASTENING DETAILS, ETC. PROVIDE
 CONSTRUCTION DETAILS FOR COLUMNS TO
 WHICH RAILS ARE ATTACHED. FBC 1015 AND
 1608.2.2
  
 27) PROVIDE A PRECAST LINTEL SCHEDULE.
  
 28) UPDATE THE CONCRETE STANDARDS IN
 NOTES ON A5 TO ACI-99. FBC CHAPTER 35
  
 29) PROVIDE PRODUCT APPROVALS FOR THE
 DOUBLE INSWING FRONT DOORS.
  
 30) THE TRUSS LAYOUT AND TRUSS DRAWINGS
 ARE REQUIRED TO BE SIGNED SEALED AND
 DATED BY THE TRUSS ENGINEER AND BE
 REVIEWED AND APPROVED BY THE DESIGNER OF
 RECORD. THE DESIGNER OF RECORD SHOULD
 STAMP AND SIGN THE LAYOUT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-10-21 Cont ID  
Sent By btrobaug Date 2003-10-21 Time 13:37 Rev Time 0.50
Received By btrobaug Date 2003-10-21 Time 13:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-04-14 Cont ID  
Sent By csiegber Date 2003-10-20 Time 14:33 Rev Time 1.00
Received By btrobaug Date 2003-04-14 Time 06:13 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-02-25 Cont ID  
Sent By shernand Date 2003-04-11 Time 14:59 Rev Time 1.00
Received By btrobaug Date 2003-02-25 Time 13:06 Sent To P
Notes
2003-02-25 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 PLANS AND RESUBMIT FOR REVIEW.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR
 MUST COMPLY WITH 250-66,AND THE SYSTEM
 WITH 250-50,ENTIRE ARTICLE.
  
 2} THE SMALL APPLIANCE CIRCUITS ARE
 SHOWN AS 1200 VA.PLEASE CALCULATE PER
 220-16(A).
  
 3} PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECT--ED PER 210-8-A-6.
 INCLUDES KITCHEN ISLANDS.
  
 4} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 5} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 6} PLEASE LOCATE SMOKE DETECTORS TO
 COMPLY WITH NFPA-72 8-1.4.1.6,ENTIRE
 ARTICLE.
  
 7} ALL RECEPTACLE SPACING TO COMPLY WITH
 210-52.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-10-22 Cont ID  
Sent By csiegber Date 2003-10-22 Time 14:28 Rev Time 0.00
Received By csiegber Date 2003-10-22 Time 14:28 Sent To M
Notes
2003-10-22 00:00:00TO PK BOX

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-10-20 Cont ID  
Sent By csiegber Date 2003-10-20 Time 14:33 Rev Time 0.00
Received By csiegber Date 2003-10-20 Time 14:33 Sent To E
Notes
2003-10-20 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-05-14 Cont ID  
Sent By shernand Date 2003-05-14 Time 16:44 Rev Time 0.00
Received By shernand Date 2003-05-14 Time 16:44 Sent To B
Notes
2003-05-14 00:00:00RM DESK, SUBMITTAL.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-05-12 Cont ID  
Sent By shernand Date 2003-05-12 Time 12:07 Rev Time 0.00
Received By shernand Date 2003-05-12 Time 12:07 Sent To B
Notes
2003-05-12 00:00:00RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-04-11 Cont ID  
Sent By shernand Date 2003-04-11 Time 14:59 Rev Time 0.00
Received By shernand Date 2003-04-11 Time 14:59 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-02-04 Cont ID  
Sent By dpalmer Date 2003-02-04 Time 09:16 Rev Time 0.00
Received By dpalmer Date 2003-02-04 Time 09:16 Sent To  
Notes
2003-02-04 00:00:00TRUSS SUBMITTAL PUT OUTFRONT UNDER "R"
 COULD NOT FIND ORIG PLANS.
 FAILED BY ZONING BUT DID NOT FIND PLANS
 IN OUTGOING?

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-27 Cont ID  
Sent By dpalmer Date 2003-01-27 Time 11:15 Rev Time 0.00
Received By dpalmer Date 2003-01-27 Time 11:15 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-10-22 Cont ID  
Sent By hmoser Date 2003-10-22 Time 17:24 Rev Time 0.50
Received By hmoser Date 2003-10-22 Time 17:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-03-01 Cont ID  
Sent By csiegber Date 2003-10-22 Time 14:28 Rev Time 1.00
Received By hmoser Date 2003-03-01 Time 12:21 Sent To B
Notes
2003-03-01 00:00:00PASS/PROVISO
 1) NEED FAN SHUTDOWN FOR FINAL.SECTION
 606 FBC (M)
 2) REFER TO SECTION 601.4 BALANCED
 RETURN AIR
 3) NEED MANUFACTURER INSTALLATION
 INSTRUCTIONS FOR COOK TOP,ON JOB SITE
 AT TIME OF UNDER GROUND INSPECTION
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8221

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-02-26 Cont ID  
Sent By btrobaug Date 2003-02-25 Time 14:20 Rev Time 0.33
Received By jleech Date 2003-02-26 Time 17:30 Sent To M
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2003-05-15 Cont ID  
Sent By rmcdouga Date 2003-05-15 Time 14:44 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2003-05-13 Cont ID  
Sent By rmcdouga Date 2003-05-13 Time 15:24 Rev Time 0.00
Received By rmcdouga Date 2003-05-15 Time 14:44 Sent To  
Notes
2003-05-13 00:00:00OWES IMPACT FEES,RADON,NOC,SEALED LETTER
 FROM ENGINEER, ZONING STAMP ON PLANS.
 5-13-03 RM

Review Stop Z ZONING
Rev No 2 Status P Date 2003-02-24 Cont ID  
Sent By sgraham Date 2003-02-24 Time 15:09 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-01-27 Cont ID  
Sent By dpalmer Date 2003-01-27 Time 11:15 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-01-27 00:00:00DENIED BY ZONING, MAX HEIGHT IS 33'
 MEASURED FROM THE GRADE NOT FLOOR GRADE