Plan Review Details - Permit 03011798
Plan Review Stops For Permit 03011798 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2003-02-21 |
|
|
Cont ID |
|
Sent By |
sthyng |
Date |
2003-02-21 |
Time |
08:48 |
Rev Time |
1.50 |
Received By |
sthyng |
Date |
2003-02-21 |
Time |
08:47 |
Sent To |
|
|
Notes |
2003-02-21 00:00:00 | SHORING DETAIL REVIEWED BY LS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2003-02-07 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2003-02-07 |
Time |
07:42 |
Rev Time |
1.00 |
Received By |
sthyng |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2003-02-07 00:00:00 | ******CORRECTIONS******** | | | | 1.)PLEASE PROVIDE SHORING DETAIL | | SEALED BY ENGINEER FOR THE SECTION OF | | THE POOL THAT IS 2.5' FROM THE HOUSE | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CALL LEA SMITH OR SAMANTHA THYNG | | 561-659-8096 EXT 8340 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2003-02-07 |
|
|
Cont ID |
|
Sent By |
sthyng |
Date |
2003-02-19 |
Time |
13:33 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2003-02-07 |
Time |
07:42 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2003-02-11 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-02-11 |
Time |
12:02 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2003-02-11 |
Time |
12:02 |
Sent To |
P |
|
Notes |
2003-02-11 00:00:00 | TO PLUMB INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-01-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-01-24 |
Time |
11:15 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2003-01-24 |
Time |
11:15 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2003-02-21 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2003-02-21 |
Time |
08:37 |
Rev Time |
0.66 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2003-02-21 00:00:00 | RESUB APPR, PES |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2003-02-19 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-02-11 |
Time |
12:02 |
Rev Time |
0.60 |
Received By |
sthyng |
Date |
2003-02-04 |
Time |
18:33 |
Sent To |
E |
|
Notes |
2003-02-04 00:00:00 | DENIED | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | | A) PLEASE ADJUST YOUR NOTES, DETAILS, OR | | SUBMITTALS TO REFLECT THE FOLLOWING IN- | | FORMATION REQUIRED FOR PLAN REVIEW | | 1) FBC-2001 424.2.9 WATER SUPPLY, LOCAL | | ORD. #2853-95, BACKFLOW REQUIRED ON | | WATER SERVICE. (ADD TO NOTES) | | 2) FBC-2001 424.2.12.1 PRESSURE TESTS. | | PER MANUFACTURE RECOMMENDATIONS, NO AIR | | TEST SHALL BE APPROVED FOR PVC PIPE AND | | FITTINGS. (ADD TO NOTES) | | 3) ALL CHANGES TO A SIGNED AND SEALED | | SET OF PLANS SHALL BE INITIALED AND | | DATED BY THE ENGINEER OF RECORD OR NEW | | SHEETS SUBMITTED IN SET OF PLANS. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2003-01-31 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-01-24 |
Time |
11:15 |
Rev Time |
0.00 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
P |
|
Notes |
|
|
|