Plan Review Details - Permit 03011798
Plan Review Stops For Permit 03011798
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-02-21 Cont ID  
Sent By sthyng Date 2003-02-21 Time 08:48 Rev Time 1.50
Received By sthyng Date 2003-02-21 Time 08:47 Sent To  
Notes
2003-02-21 00:00:00SHORING DETAIL REVIEWED BY LS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-02-07 Cont ID  
Sent By btrobaug Date 2003-02-07 Time 07:42 Rev Time 1.00
Received By sthyng Date   Time   Sent To  
Notes
2003-02-07 00:00:00******CORRECTIONS********
  
 1.)PLEASE PROVIDE SHORING DETAIL
 SEALED BY ENGINEER FOR THE SECTION OF
 THE POOL THAT IS 2.5' FROM THE HOUSE
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CALL LEA SMITH OR SAMANTHA THYNG
 561-659-8096 EXT 8340

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-02-07 Cont ID  
Sent By sthyng Date 2003-02-19 Time 13:33 Rev Time 0.50
Received By btrobaug Date 2003-02-07 Time 07:42 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-02-11 Cont ID  
Sent By dpalmer Date 2003-02-11 Time 12:02 Rev Time 0.00
Received By dpalmer Date 2003-02-11 Time 12:02 Sent To P
Notes
2003-02-11 00:00:00TO PLUMB INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-24 Cont ID  
Sent By dpalmer Date 2003-01-24 Time 11:15 Rev Time 0.00
Received By dpalmer Date 2003-01-24 Time 11:15 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-02-21 Cont ID  
Sent By pschmitz Date 2003-02-21 Time 08:37 Rev Time 0.66
Received By pschmitz Date   Time   Sent To  
Notes
2003-02-21 00:00:00RESUB APPR, PES

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-02-19 Cont ID  
Sent By dpalmer Date 2003-02-11 Time 12:02 Rev Time 0.60
Received By sthyng Date 2003-02-04 Time 18:33 Sent To E
Notes
2003-02-04 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 2) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 3) ALL CHANGES TO A SIGNED AND SEALED
 SET OF PLANS SHALL BE INITIALED AND
 DATED BY THE ENGINEER OF RECORD OR NEW
 SHEETS SUBMITTED IN SET OF PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2003-01-31 Cont ID  
Sent By dpalmer Date 2003-01-24 Time 11:15 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***