Plan Review Details - Permit 03011776
Plan Review Stops For Permit 03011776 |
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2003-01-30 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-01-30 |
Time |
09:53 |
Rev Time |
1.50 |
Received By |
kstevens |
Date |
2003-01-30 |
Time |
09:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2003-01-25 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-01-25 |
Time |
10:45 |
Rev Time |
1.50 |
Received By |
kstevens |
Date |
2003-01-25 |
Time |
10:45 |
Sent To |
|
|
Notes |
2003-01-25 00:00:00 | DENIED | | REFERENCE: FBC-2001 FUEL GAS | | | | 1) L/P TANK SHALL BE SECURED. PLEASE | | PROVIDE DETAIL. TANK SHALL BE INSPECTED | | PRIOR TO COVERING. | | 2 FOLLOWING INFORMATION REQUIRED FOR | | GAS PERMIT APPLICATION. | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2001 | | FUEL GAS CODE. | | B. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2001 FUEL GAS CODE SECS. 401.8 | | THRU 402.5.2 AND TABLES 402(1) THRU | | 402(34). | | C. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2001 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES (A)(3). | | D. SUBMIT CALCULATIONS FOR COMBUSTION | | AIR (IF APPLICABLE) PER FBC-2001 FUEL | | GAS CODE SECTION 304. FOR DRYER-CEILING | | HEIGHT NOT SHOWN ON PLANS. | | E. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2001 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |