Plan Review Details - Permit 03011747
Plan Review Stops For Permit 03011747
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-02-07 Cont ID  
Sent By btrobaug Date 2003-02-06 Time 17:46 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-02-06 Cont ID  
Sent By kstevens Date 2003-02-04 Time 17:57 Rev Time 0.25
Received By btrobaug Date 2003-02-06 Time 17:26 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-24 Cont ID  
Sent By dpalmer Date 2003-01-24 Time 11:20 Rev Time 0.00
Received By dpalmer Date 2003-01-24 Time 11:19 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-02-11 Cont ID  
Sent By kstevens Date 2003-02-11 Time 11:24 Rev Time 0.25
Received By kstevens Date 2003-02-11 Time 11:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-02-04 Cont ID  
Sent By sgraham Date 2003-02-04 Time 11:59 Rev Time 0.50
Received By kstevens Date 2003-02-04 Time 17:46 Sent To E
Notes
2003-02-04 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-4 92, AND NSPI-5. (ADD TO
 NOTES)
 2) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER.
 3) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 4) POOL LAYOUT SHEET SHOWS VAC LINE, BUT
 SPECIFICATIONS SAYS NO VACUUM. PLEASE
 CLAIRFY.
 5) TWO PIPING SCHEMATIC SHOWN. ONE SHOWS
 A PUMP WITH BLOWER PICKING UP MAIN DRAIN
 AND RETURNING TO SPA. THE OTHER SHOWS
 A PUMP WITH TWO SETS OF MAIN DRAINS.
 IS THERE TWO PUMPS?? PLEASE CLAIRFY.
 PLEASE SUBMIT ONE SCHEMATIC WILL ALL
 PIPING AND PUMPS AND NOT NUMERIOUS PIP-
 ING SCHEMATICS.
 6) ALL CHANGES TO A SIGNED AND SEALED
 SET OF PLANS SHALL BE INITIALED AND
 DATED BY ENGINEER OF RECORD OR NEW SHEET
 SUBMITTED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2003-02-04 Cont ID  
Sent By dpalmer Date 2003-01-24 Time 11:20 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***