Plan Review Details - Permit 03011510
Plan Review Stops For Permit 03011510
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-03-14 Cont ID  
Sent By rmcdouga Date 2003-03-14 Time 15:40 Rev Time 3.00
Received By rmcdouga Date 2003-03-14 Time 15:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-02-14 Cont ID  
Sent By sthyng Date 2003-03-14 Time 10:13 Rev Time 4.00
Received By rmcdouga Date 2003-02-14 Time 14:39 Sent To  
Notes
2003-02-14 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PROVIDE A COPY OF THE SOIL REPORT
 THAT IS SIGNED AND SEALED BY THE SOIL
 ENGINEER FOR PUBLIC RECORD.
  
 4) THE ENERGY CALCULATION DATA ON A-2 OF
 THE PLANS DO NOT MATCH THE INFORMATION
 LISTED ON THE ENERGY CALC. FORM IN
 SEVERAL CATEGORIES. PLEASE CORRECT.
  
 5) PROVIDE AN INSTALLATION SCHEDULE
 WHICH PROVIDES THE INFORMATION LISTED ON
 THE CITY OF WPB FORM THAT IS ATTACHED TO
 THIS REVIEW.
  
 6) SEMCO AND HUGHES WERE PURCHASED BY
 USP SOMETIME AGO. PLEASE UPDATE THE
 DETAILS ON A-8.
  
 7) PROVIDE A BUCK DETAIL FOR THE SIDE
 SWING EXTERIOR DOOR. COORDINATE WITH
 PRODUCT APPROVAL (2X BUCK).
  
 8) NOTES FOR THE WINDOW BUCK ATTACHMENT
 AT DETAIL 5 ON A-8 HAVE CONFLICTING
 INFORMATION. CLARIFY.
  
 9) THE GARAGE DOOR BUCK FASTENING DETAIL
 ON A-8 OF PLANS DOES NOT MEET THE
 SPACING REQUIREMENT OF THE CLOPAY
 PRODUCT APPROVAL.
  
 10) SUBMIT A PRODUCT APPROVAL FOR THE
 SINGLE OUTSWING EXTERIOR DOOR WITH ONE
 SIDELITE.
  
 11) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR THE GLASS BLOCK, WHICH
 INDICATES THE DESIGN WIND PRESSURES.
  
 12) PROVIDE THE APPROVED DRAWINGS,WHICH
 ARE PART OF THE PRODUCT APPROVAL, FOR
 THE HORIZONTAL ROLLING WINDOWS AND THE
 SINGLE HUNG WINDOWS.
  
 13) PROVIDE LEGIBLE DRAWINGS FOR THE
 RECTANGULAR FIXED GLASS WINDOWS AND THE
 RADIUS FIXED GLASS WINDOWS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-02-10 Cont ID  
Sent By jleech Date 2003-02-08 Time 11:22 Rev Time 0.50
Received By dpalmer Date 2003-02-10 Time 14:45 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-14 Cont ID  
Sent By sthyng Date 2003-03-14 Time 10:13 Rev Time 0.00
Received By sthyng Date 2003-03-14 Time 10:13 Sent To B
Notes
2003-03-14 00:00:00TO RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-22 Cont ID  
Sent By btrobaug Date 2003-01-22 Time 17:10 Rev Time 0.00
Received By btrobaug Date 2003-01-21 Time 17:09 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-02-08 Cont ID  
Sent By jleech Date 2003-02-01 Time 07:07 Rev Time 0.50
Received By jleech Date 2003-02-08 Time 11:22 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-02-01 Cont ID  
Sent By sgraham Date 2003-01-24 Time 15:54 Rev Time 0.33
Received By jleech Date 2003-02-01 Time 07:06 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-01-24 Cont ID  
Sent By btrobaug Date 2003-01-22 Time 17:10 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***