Plan Review Details - Permit 03011382
Plan Review Stops For Permit 03011382
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-05-14 Cont ID  
Sent By btrobaug Date 2003-05-14 Time 18:15 Rev Time 0.50
Received By btrobaug Date 2003-05-14 Time 18:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-02-11 Cont ID  
Sent By shernand Date 2003-05-14 Time 15:54 Rev Time 0.75
Received By btrobaug Date 2003-02-11 Time 12:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-01-23 Cont ID  
Sent By btrobaug Date 2003-01-23 Time 14:46 Rev Time 0.00
Received By btrobaug Date 2003-01-23 Time 14:21 Sent To  
Notes
2003-01-23 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CORRECTIONS
 TO PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE PROVIDE A LOAD CALCULATION FOR
 THE 225 AMP PANEL FEEDING THE NEW
 EQUIPMENT,INCLUDING EXISTING LOADS.
  
 2} NOTE THE DICREPANCIES IN
 TRANSFORMER,PANEL AND DISCONNECT
 RATINGS FOR THE NEW EQUIPMENT ON THE 2
 SETS OF PLANS SUBMITED.PLEASE CORRELATE
 TO SHOW ACTUAL VALUES OF THE EQUIPMENT
 TO BE INSTALLED.
  
 3} THE FEEDER SIZES FOR "B","C","D" AND
 "E"RUNS ON THE RISER ARE ALSO DIFFERENT
 ON THE 2 SHEETS SUBMITTED,PLEASE
 CORRELATE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT.8392.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-14 Cont ID  
Sent By shernand Date 2003-05-14 Time 15:54 Rev Time 0.00
Received By shernand Date 2003-05-14 Time 15:54 Sent To E
Notes
2003-05-14 00:00:00BT DESK