Plan Review Details - Permit 03011267
Plan Review Stops For Permit 03011267
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-02-07 Cont ID  
Sent By btrobaug Date 2003-02-05 Time 18:26 Rev Time 2.00
Received By jgomez Date 2003-02-07 Time 10:40 Sent To PC
Notes
2003-02-07 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-FLOOD ZONE A8. NEED TO PROVIDE THE
 ELEVATION CERTIFICATE.
 3-SHEET A-1: REVISE NOTE #24. SEE SEC.
 1007.5.1 FBC 2001 FOR HANDRAIL HEIGHT.
 4-GLASS BLOCK TO BE SAFETY GLASS IF FACE
 THICKNESS IS LESS THAN 0.25". SECTION
 2405.2.2 FBC 2001.
 5-SHEET A-4: REVISE NOTE #1. SEE SECTION
 1007.5.1 FBC 2001 FOR HANDRAIL HEIGHT.
 6-PROVIDE GENERAL SPECS FOR FIREBLOCKING
 AT ALL CONCEALED SPACES AS REQUIRED BY
 SEC. 2305.1.4 FBC 2001.
 7-PROVIDE COMPLETE DETAIL/SECTION FOR
 CONNECTION AT TOP OF COLUMN BETWEEN
 GARAGE AND KITCHEN. CLARIFY HOW IS
 COLUMN TOP CONNECTOR HOLDING 2 GIRDER
 TRUSSES FROM TWO DIFFERENT SIDES. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC.
 8-SHEET S-3: PROVIDE SPECS ON STRUCTURAL
 WALL SECTIONS FOR FIRECUT REQUIREMENTS
 SEC. 2305.4 FBC 2001.
 9-DETAIL R19: SPECIFY ALL CONNECTORS.
 ROOF FRAMING PLAN DOESN'T SPECIFY THEM
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 10-SPECIFY SIZE OF ANCHOR BOLT & WASHER
 FOR GARAGE DOOR STRUCTURAL BUCK DETAIL
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 11-PROVIDE SOIL TEST REPORT PRIOR TO
 CONSTRUCTION.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-02-05 Cont ID  
Sent By jleech Date 2003-02-05 Time 17:12 Rev Time 0.50
Received By btrobaug Date 2003-02-05 Time 18:25 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-08 Cont ID  
Sent By shernand Date 2003-07-08 Time 16:10 Rev Time 0.00
Received By shernand Date 2003-07-08 Time 16:10 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-07 Cont ID  
Sent By dpalmer Date 2003-02-07 Time 15:29 Rev Time 0.00
Received By dpalmer Date 2003-02-07 Time 15:29 Sent To M
Notes
2003-02-07 00:00:00TO H MOSER

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-07-11 Cont ID  
Sent By pkrauss Date 2003-07-11 Time 14:30 Rev Time 0.25
Received By pkrauss Date 2003-07-11 Time 14:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-03-13 Cont ID  
Sent By shernand Date 2003-07-08 Time 16:11 Rev Time 0.25
Received By pkrauss Date 2003-03-13 Time 14:32 Sent To  
Notes
2003-03-13 00:00:00APPROVED 2-20-03

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-02-05 Cont ID  
Sent By dpalmer Date 2003-02-07 Time 15:29 Rev Time 0.33
Received By jleech Date 2003-02-05 Time 17:12 Sent To E
Notes
2003-02-05 00:00:00DENIED;
 PLAN DENIED
 1) ENERGY PERFORMANCE LEVEL DISPLAY CARD
 AND ENERGY CALCULATIONS DO NOT MATCH.
 2) EQUIPMENT SELESTION ON MANUAL (J) NOT
 COMPLETE.
 3) COOLING & HEATING BTU.ON MANUAL (J)
 DO NOTMATCH PLANS.
 PLAN REVIEW BY HAROLD MOSER
 (561)689-8096 EXT.8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-01-28 Cont ID  
Sent By sgraham Date 2003-01-24 Time 16:30 Rev Time 0.25
Received By kstevens Date 2003-01-28 Time 08:03 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-01-24 Cont ID  
Sent By sgraham Date 2003-01-24 Time 16:30 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***