Plan Review Details - Permit 03011211
Plan Review Stops For Permit 03011211
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-08-05 Cont ID  
Sent By rmcdouga Date 2003-08-05 Time 11:50 Rev Time 3.00
Received By rmcdouga Date 2003-08-05 Time 11:49 Sent To  
Notes
2003-08-05 00:00:00BUILDING PROVISO
  
 1) SUBMIT ENGINEERING FOR THE BOW WINDOW
 WALL ASSEMBLY WHICH SPECIFIES HOW THE
 DEAD LOAD FROM THE MULLION AND UPPER
 WINDOW WALL WILL BE SUPPORTED. THE
 PRODUCT APPROVAL FOR THE WINDOW WALL
 SYSTEM DOES NOT INDICATE THAT THE FRAMES
 AND WINDOWS ARE CAPABLE OF SUPPORTING
 ANY DEAD LOAD FROM ABOVE. THIS IS TO BE
 SUBMITTED FOR APPROVAL PRIOR TO THE
 FRAMING INSPECTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-07-15 Cont ID  
Sent By alange Date 2003-08-01 Time 15:34 Rev Time 3.00
Received By rmcdouga Date 2003-07-15 Time 11:08 Sent To  
Notes
2003-07-15 00:00:00BUILDING DENIED
  
 1) THE ENERGY CALCULATION FORMS ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE
 OWNER/AGENT.
  
 2) SUBMIT SIGNED AND SEALED COPIES OF
 THE TEST REPORT FOR THE 90 DEGREE
 SLIDING GLASS DOORS.
  
 3) THE ENGINEERING FOR THE BAY WINDOW
 MULLION REFERENCES THE WRONG LOT NUMBER.
 SITE SPECIFIC ENGINEERING IS REQUIRED TO
 BE REVIEWED AND APPROVED BY THE DESIGNER
 OF RECORD FOR THE STRUCTURE. THE NOTES
 ON THE DRAWING INDICATE THAT THE MULLION
 IS NOT CAPABLE OF SUPPORTING THE DEAD
 LOADS OF THE WINDOWS ABOVE AND THE
 PRODUCT APPROVAL FOR THE STORE FRONT
 WINDOW WALL DOES NOT ADDRESS SUPPORTING
 ANY DEAD LOAD FROM ABOVE. THERE ARE NO
 OVERALL DIMENSIONS FOR THE MULLION GIVEN
  
 4) THE PRODUCT APPROVAL THAT SUBMITTED
 DOES NOT INDICATE THAT THE WINDOW WALL
 SYSTEM CAN BE INSTALLED ON A RADIUS.
 SITE SPECIFIC ENGINEERING WITH DRAWINGS
 AND ANALYSIS,WHICH HAS BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD, IS
 REQUIRED. TESTING OF THE ASSEMBLY IS
 REQUIRED FOR IMPACT RESISTANCE. THE
 ASSEMBLY AS INDICATED ON THE PLANS IS
 THE UPPER AND LOWER WINDOW WALL SYSTEMS
 AND THE MULLION BETWEEN THEM. IF THE
 ASSEMBLY IS NOT TESTED, THEN IT MUST BE
 SHUTTERED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-03-20 Cont ID  
Sent By hmoser Date 2003-07-08 Time 17:03 Rev Time 0.00
Received By rmcdouga Date 2003-03-20 Time 11:07 Sent To  
Notes
2003-03-20 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) FBC 2305.2.2 REQUIRES DRAFTSTOPPING
 PARALLEL TO THE MAIN FRAMING MEMBERS IN
 FLOOR/CEILING ASSEMBLIES SEPARATING IT
 INTO AREAS NO GREATER THAN 550 SQFT.
 INDICATE THE LOCATIONS AND MATERIAL THAT
 WILL BE USED ON THE PLANS.
  
 3) SPECIFY THE GUARDRAIL HEIGHT, SPACING
 OF INTERMEDIATE RAILS, BOTTOM RAIL
 SPACING, ATTACMENT METHOD FOR THE
 EXTERIOR BALCONY AND THE INTERIOR LOFTS.
  
 4) PROVIDE DETAILS OF STAIRS. SPECIFY
 THE TREAD AND RISER DIMENSIONS PER FBC
 1007.3. CIRCULAR STAIRS SHALL COMPLY
 WITH FBC 1007.8.3. SPIRAL STAIRWAY SHALL
 COMPLY WITH FBC 1007.8.2. PROVIDE DETAIL
 OF GUARDRAILS ON THE OPEN SIDE OF THE
 STAIRS. SEE FBC 1015 & 1026.5.
  
 5) INDICATE FIREBLOCKING AT VERTICAL AND
 HORIZONTAL COCEALED DRAFT OPENINGS AND
 CONCEALED SPACES OF STAIR STRINGERS AT
 THE TOP AND BOTTOM OF THE RUN. SEE FBC
 2305.1 & 2305.1.4.
  
 6) INDICATE THE LOCATIONS OF THE SHEAR
 WALLS AT THE SECOND FLOOR WOOD FRAME
 WALLS ON THE PLANS. PROVIDE DETAILS AND
 LOCATIONS OF HOLD DOWNS.
  
 7) NO ID TAGS ARE GIVEN ON THE PLANS
 THAT CORRESPOND TO THE COLUMN DETAILS ON
 5F. PROVIDE ID TAGS FOR ALL OF THE
 COLUMNS AND BEARING POINTS ON THE
 FOUNDATION PLAN ON SHEET 4 AND PROVIDE
 DETAILS FOR EACH.
  
 8) THE CROSS SECTION ON 5F REFERS TO
 DETAIL 7 ON 5C FOR THE STEEL COLUMN.
 THERE IS NO DETAIL ON 5C.
  
 9) THE SECTION ON 4S1 HAS INCORRECT
 DIMENSION FOR THE FOOTING.
  
 10) PROVIDE A SQFT BREAKDOWN OF HOUSE.
 INDICATE THE SQFT LIVING AREA ON EACH
 FLOOR, PORCHES, GARAGES, ETC.
  
 11) THE ENERGY CALCULATIONS LIST THE
 CONDITONED FLOOR AREA AS 6950 SQFT. IS
 THIS THE TOTAL SQFT OF THE HOUSE OR THE
 CONDITIONED SPACE?
  
 12) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - SLIDING GLASS DOOR
 - THE PRODUCT APPROVAL FOR THE ROOF
 TILE HAS EXPIRED (12-16-02).
 - PROVIDE COVER SHEET FOR THE DESIGNER
 SERIES-FIXED WINDOWS NOA # 02-0318.02
 THAT IS IN WITH THE STORMLINE DOORS.
 - THE TEST INFO SUBMITTED FOR THE
 WINDOOR 90 DEGREE SLIDING GLASS DOOR IS
 NOT AN ACCEPTABLE PRODUCT APPROVAL. IT
 MUST BE METRO-DADE, SBCCI OR SITE
 SPECIFIC ENGINEERING.(ENGINEERED
 DRAWINGS SHOWING ALL ATTACHMENTS ARE
 REQUIRED)
  
 13) THE PRODUCT APPROVAL FOR THE STORE-
 FRONT WINDOW IS LIMITED TO A MAXIMUM
 FRAME HEIGHT OF TWELVE FT. A STRUCTURAL
 HORIZONTAL MULLION THAT IS ON A RADIUS
 WILL BE REQUIRED. THE PRODUCT APPROVAL
 DOES NOT COVER A RADIUS APPLICATION SUCH
 AS THIS ASSEMBLY. SITE SPECIFIC
 ENGINEERING ALONG WITH A ENGINEERED
 ANALYSIS AND DRAWINGS WILL BE REQUIRED.
  
 14) THE HEADER DETAIL ON 4S3 FOR THE 90
 DEGREE SLIDING GLASS DOORS AT THE SECOND
 FLOOR SHOWS THE C9X15 CHANNEL ANCHORED
 TO THE WALL WITH EXPANSION BOLTS. THE
 SECOND FLOOR WALLS IN THIS LOCATION IS
 WOOD FRAME. SEE 5A & 5E. THE TRUSSES IN
 THE DETAIL ARE INDICATED WITH ID TAGS
 THAT DO NOT CORRESPOND WITH TRUSS IDS ON
 5E.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-07-02 Cont ID  
Sent By btrobaug Date 2003-07-02 Time 15:45 Rev Time 1.00
Received By btrobaug Date 2003-07-02 Time 13:34 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-02-28 Cont ID  
Sent By shernand Date 2003-06-26 Time 10:12 Rev Time 1.00
Received By btrobaug Date 2003-02-28 Time 09:50 Sent To P
Notes
2003-02-28 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 DRAWINGS AND RESUBMIT FOR REVIEW.
  
 1} THE PANEL IN THE GARAGE IS NOT SHOWN
 ON THE RISER DIAGRAM.
  
 2} THERE IS NO PANEL SCHEDULE FOR THE
 PANEL IN THE GARAGE.PLEASE PROVIDE
 SAME.( NOTES 1&2 REFER TO GARAGE #2).
  
 3} THE WATER HEATER IS NOT IN THE LOAD
 CALC OR LISTED ON A PANEL SCHEDULE,IF
 IT IS TO BE GAS PLEASE INDICATE SAME.
  
 4} ALL DISCONNECT LOCATIONS MUST COMPLY
 WITH 110-26,CANNOT BE LOCATED BEHIND THE
 UNITS.
  
 5} THE CONDENSER LOCATIONS ON THE
 ELECTRICAL DRAWINGS DO NOT MATCH THE
 MECHANICAL PLANS.PLEASE CORRELATE.ALSO
 THE AHU DESIGNATIONS.
  
 6} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210-52E
  
 7} BEDROOM #5 IS NOT LISTED ON THE
 PANELSCHEDULE.(NOTE BOTH PANELS ARE
 FULL!!)
  
 8} PLEASE CHECK RECEPTACLE SPACING PER
 210-52,ENTIRE ARTICLE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-03-23 Cont ID  
Sent By adarroug Date 2005-03-23 Time 11:15 Rev Time 0.00
Received By rmcdouga Date 2005-03-23 Time 11:15 Sent To B
Notes
2005-03-25 00:00:00RESTAMP WAS FOR MECHANICAL ONLY WAS SENT
 TO PATTY KRAUSS' DESK.
2005-03-23 00:00:00TO "RMCDOUGAL" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-05-04 Cont ID  
Sent By csiegber Date 2004-05-04 Time 13:15 Rev Time 0.00
Received By csiegber Date 2004-05-04 Time 13:15 Sent To M
Notes
2004-05-04 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-08-01 Cont ID  
Sent By alange Date 2003-08-01 Time 15:34 Rev Time 0.00
Received By alange Date 2003-08-01 Time 15:34 Sent To B
Notes
2003-08-01 00:00:00TO RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-06-26 Cont ID  
Sent By shernand Date 2003-06-26 Time 10:12 Rev Time 0.00
Received By shernand Date 2003-06-26 Time 10:12 Sent To E
Notes
2003-06-26 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-06-23 Cont ID  
Sent By shernand Date 2003-06-23 Time 16:26 Rev Time 0.00
Received By shernand Date 2003-06-23 Time 16:26 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date 2003-02-28 Cont ID  
Sent By lmartine Date 2003-02-28 Time 09:03 Rev Time 0.00
Received By lmartine Date   Time   Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-02-27 Cont ID  
Sent By sgraham Date 2003-02-28 Time 08:57 Rev Time 0.00
Received By dpalmer Date 2003-02-27 Time 13:46 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-17 Cont ID  
Sent By btrobaug Date 2003-01-17 Time 17:40 Rev Time 0.00
Received By btrobaug Date 2003-01-16 Time 17:40 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By pkrauss Date 2005-03-29 Time 13:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-05-19 Cont ID  
Sent By spalmer Date 2004-05-19 Time 11:29 Rev Time 0.05
Received By spalmer Date   Time   Sent To  
Notes
2004-05-19 00:00:00APPROVED PER PATTY KRAUSS ON
 MAY 14, 2004

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-07-08 Cont ID  
Sent By csiegber Date 2004-05-04 Time 13:15 Rev Time 0.50
Received By hmoser Date 2003-07-08 Time 17:02 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-03-11 Cont ID  
Sent By btrobaug Date 2003-07-02 Time 15:44 Rev Time 1.00
Received By hmoser Date 2003-03-11 Time 19:00 Sent To B
Notes
2003-03-11 00:00:00ATTIC ACCESS OPENING SHALL BE NO LESS
 THAN 30" X 22" AS PER 2001 FBC(M) 306.3
  
 2001 FBC CHAPTER 13 610.1.ABC.3.5.2 -
 1. THE SERVICE PANEL OF THE EQUIPMENT IS
 LOCATED WITHIN 6 FT OF AN ATTIC
 ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE
 OWNER OR SHUT DOWN WHEN THE
 CONDENSATE DRAIN IS NOT WORKING
 PROPERLY.
 4. A NOTICE IS POSTED ON THE ELECTRIC
 SERVICE PANEL INDICATING TO THE
 HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC.

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-03-10 Cont ID  
Sent By btrobaug Date 2003-02-28 Time 13:18 Rev Time 0.33
Received By jleech Date 2003-03-10 Time 18:44 Sent To  
Notes
2003-03-10 00:00:00NO RISER DIAGRAM.

Review Stop Z ZONING
Rev No 3 Status P Date 2003-08-05 Cont ID  
Sent By rmcdouga Date 2003-08-05 Time 14:43 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2003-08-05 00:00:00OK PER M.MCLEAN 6-25-03

Review Stop Z ZONING
Rev No 2 Status F Date 2003-02-28 Cont ID  
Sent By shernand Date 2003-06-23 Time 16:26 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
2003-02-28 00:00:00DENIED 2ND CHECKLIST, CHIMNEY AND ROOF
 LINE MUST BE 33' IN HEIGHT

Review Stop Z ZONING
Rev No 1 Status F Date 2003-01-24 Cont ID  
Sent By dpalmer Date 2003-02-27 Time 13:46 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-01-24 00:00:00DENIED BY ZONING
 1. MAX HEIGHT OF BLDG WITH THE TOWER
 33', MEASURED FROM GRADE NOT FLOOR
 ELEVATION