Plan Review Details - Permit 03011198
Plan Review Stops For Permit 03011198
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2003-10-21 Cont ID  
Sent By jwitmer Date 2003-10-21 Time 12:08 Rev Time 0.50
Received By jwitmer Date 2003-10-21 Time 12:08 Sent To E
Notes
2003-10-21 00:00:00REVISION# 4 OCT.06/03BUILDING OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2003-05-22 Cont ID  
Sent By jwitmer Date 2003-05-07 Time 11:42 Rev Time 1.50
Received By jwitmer Date 2003-05-07 Time 11:42 Sent To  
Notes
2003-05-22 00:00:00REQUIRES HISTORICS APPROVAL FOR
 ELEVATION CHANGES. SEE SHERRY PILAND.
2003-05-07 00:00:005-07-03 SUBMIT PLANS TO HISTORICS
 SHERRY PILANDJW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-04-08 Cont ID  
Sent By shernand Date 2003-05-06 Time 10:05 Rev Time 0.75
Received By jwitmer Date 2003-04-08 Time 15:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-03-26 Cont ID  
Sent By sthyng Date 2003-04-03 Time 09:39 Rev Time 0.75
Received By jwitmer Date 2003-03-26 Time 15:10 Sent To  
Notes
2003-03-26 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03011198
 ADD: 539 CLEMATIS ST
 CONT: COMPLETE PROPERTY MANAGEMENT
 TEL: (561)626-2778
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 MISSING PRODUCT TESTING REPORT FOR DOOR
 # 3 THE EXTERIOR VESTIBULE DOOR.
  
 2)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-01-28 Cont ID  
Sent By sthyng Date 2003-03-20 Time 11:35 Rev Time 3.25
Received By jwitmer Date 2003-01-28 Time 09:44 Sent To  
Notes
2003-01-28 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 03011198
 ADD:537 CLEMATIS STREET
 CONT: COMPLETE PROPERTY MANAGEMENT
 TEL: (561)626-2778
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) NEW ADDRESSES TO BE USED!
 A) 535 CLEMATIS ST- SITE ADDRESS
 B) 537 CLEMATIS ST- NEW FIRST FL TENANT
 C) 539 CLEMATIS ST- 2ND FL TENANT
 D) 541 CLEMATIS ST- RESTAURANT
  
 2) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSINGREPORTS:
 A) FIXED WINDOWS/ LARGE MISSLE IMPACT.
 RESISTANCE
 B) MULLION (HORIZONTAL) W/ LARGE
 MISSLE IMPACT RESISTANCE
 C) EXTERIOR METAL DOOR/ FRAME EXTERIOR
 SWING. REPORT SUBMITTED RESIDENTIAL
 INSWING.
  
 3)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 4)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 5) 1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 6)705.7.1 JOINTS INSTALLED IN OR BE-
 TWEEN FIRE RESISTANT WALLS, FIRE RESIS-
 TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES
 AND FIRE RESISTANT ROOFS OR ROOF/ CEIL-
 ING ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
 FOR A PERIOD NOT LESS THAN THE RE-
 QUIRED FIRE RESISTANCE RATING OF THE
 WALL, FLOOR OR FLOOR IN OR BETWEEN
 WHICH IT IS INSTALLED.
  
 7)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 MECHANIACAL PLANS INDICATE THAT THE AIR
 HANDLER IS TO BE HUNG FROM THE CONCRETE
 DECK ABOVE. SHEET A-3.00 INDICATES WOOD
 FLOOR TRUSSES, ENGINEER LETTER FOR THE
 ADDITIONAL LOADS BEING TRANSFERRED TO
 THE WOOD FLOOR TRUSSES. WILL ADDITIONAL
 BACKING BE REQUIRED? WHAT TYPE OF FASTEN
 ER IS TO BE USED TO MAKE THE CONNECTION
 TO THE 1/2" SUSPENTION RODS?
  
 8)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 9)FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
  
 10)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-10-27 Cont ID  
Sent By dpalmer Date 2003-10-27 Time 07:39 Rev Time 0.33
Received By dpalmer Date 2003-10-27 Time 07:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-01-27 Cont ID  
Sent By jwitmer Date 2003-10-21 Time 12:10 Rev Time 0.33
Received By dpalmer Date 2003-01-27 Time 16:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-10-30 Cont ID  
Sent By mcarsill Date 2003-10-30 Time 06:50 Rev Time 0.00
Received By mcarsill Date 2003-10-30 Time 06:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-02-04 Cont ID  
Sent By nmccray Date 2003-02-04 Time 11:10 Rev Time 0.00
Received By nmccray Date 2003-02-04 Time 11:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-10-21 Cont ID  
Sent By csiegber Date 2003-10-21 Time 13:55 Rev Time 0.00
Received By csiegber Date 2003-10-21 Time 13:54 Sent To  
Notes
2003-10-21 00:00:00TO COMM BD#8/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-05-06 Cont ID  
Sent By shernand Date 2003-05-06 Time 10:03 Rev Time 0.00
Received By shernand Date 2003-05-06 Time 10:03 Sent To B
Notes
2003-05-06 00:00:00JW DESK. BUILDING REVISION.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-04-03 Cont ID  
Sent By sthyng Date 2003-04-03 Time 09:39 Rev Time 0.00
Received By sthyng Date 2003-04-03 Time 09:39 Sent To B
Notes
2003-04-03 00:00:00TO JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-03-20 Cont ID  
Sent By sthyng Date 2003-03-20 Time 11:35 Rev Time 0.00
Received By sthyng Date 2003-03-20 Time 11:35 Sent To B
Notes
2003-03-20 00:00:00TO JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-27 Cont ID  
Sent By btrobaug Date 2003-01-27 Time 15:08 Rev Time 0.00
Received By btrobaug Date 2003-01-27 Time 15:08 Sent To  
Notes
2003-01-27 00:00:00COMM BOARD # 24./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-17 Cont ID  
Sent By sgraham Date 2003-01-23 Time 13:39 Rev Time 0.00
Received By btrobaug Date 2003-01-16 Time 18:23 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-11-04 Cont ID  
Sent By pkrauss Date 2003-11-04 Time 16:42 Rev Time 0.40
Received By pkrauss Date 2003-11-04 Time 16:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-02-04 Cont ID  
Sent By pkrauss Date 2003-02-04 Time 13:00 Rev Time 0.40
Received By pkrauss Date 2003-02-04 Time 12:59 Sent To  
Notes
2003-02-04 00:00:00PROVISO:MECHANICAL PERMIT 03020138
  
 1.PLAN SHEET A1.00 REFLECTED CEILING
 PLAN, PLEASE NOTE CLEARANCES AROUND AHU
 SHALL BE SUFFICIENT TO ALLOW FOR REPAIR,
 SERVICE, REPLACEMENT OR INSPECTION.
 2001 FBC(M) 306.1.
  
 2.PLAN SHEET M1.00, RETURN AIR FROM
 THE RETAIL SPACE (101) INTO THE
 VESTIBULE (102) SHALL BE DUCTED.
  
 3.PLAN SHEET M1.00 A/C SCHEDULE NOTE
 #6, FIRESTAT IN RETURN AIR DUCT...2001
 FBC(M) 606.2.1, DETECTORS SHALL BE
 INSTALLED IN THE SUPPLY AIR DUCT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-01-30 Cont ID  
Sent By kstevens Date 2003-01-30 Time 18:03 Rev Time 0.50
Received By kstevens Date 2003-01-30 Time 18:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-01-23 Cont ID  
Sent By btrobaug Date 2003-01-17 Time 18:24 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***