2003-02-10 00:00:00 | BUILDING DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) PLEASE CLARIFY NOTE #9 UNDER GENERAL |
| NOTES ON SHEET 1 TO INCLUDE WINDOWS THAT |
| ARE WITHIN THREE FEET HORIZONTALLY OF |
| THE TUB OR SHOWER. SEE FBC 2405.2.1. |
| |
| 3) SPECIFY ON THE PLANS THAT THE WIRE |
| MESH IN THE SLAB IS REQUIRED TO BE |
| SUPPORTED AT A MAXIMUM OF THREE FEET ON |
| CENTER PER FBC 1909.3. |
| |
| 4) SPECIFY THE SIZES OF THE FIXED GLASS |
| TRANSOM AND THE AND THE SIDELITE AT THE |
| FRONT DOOR ON THE PLANS. |
| |
| 5) THE ROOF FRAMING PLAN ON 3A, 3B AND |
| 3C SPECIFY AN A-5 TRUSS CONNECTOR FOR |
| THE HIP GIRDER AT THE GARAGE. HOWEVER, |
| THERE IS NO A-5 CONNECTOR LISTED IN THE |
| ANCHOR SCHEDULE ON SHEET 2. PLEASE |
| CLARIFY. |
| |
| 6) DETAIL 3 ON 4 DOES NOT SPECIFY THE |
| LENGTH OR EMBEDMENT DEPTH OF THE 5/8" |
| EXPANSION BOLTS FOR THE OVERHEAD GARAGE |
| DOOR. PLEASE SPECIFY. |
| |
| 7) THE HVAC CREDIT IS BEING TAKEN FOR |
| CEILING FANS ON THE ENERGY CALCULATIONS. |
| PLEASE INDICATE THE REQUIRED MINIMUM FAN |
| SIZE FOR EACH ROOM ON THE PLANS. SEE FBC |
| CHAPTER 13-607.1.A.1 AND TABLE 6-6. |
| |
| 8) PROVIDE THE MANUFACTURER'S SPECS. AND |
| UL LISTING INFORMATION FOR THE ONE HOUR |
| FIRE RATED GLASS BLOCK ASSEMBLY. |
| |
| 9) THE JOB LOCATION IS REQUIRED TO BE ON |
| THE SITE SPECIFIC PRODUCT APPROVALS FROM |
| NORANDEX. |
| |
| 10) THERE IS NO PRODUCT INFORMATION IN |
| THE NORANDEX SITE SPECIFIC APPROVALS FOR |
| THE 96"X 60" GLIDER WINDOW WITH AN XOX |
| CONFIGURATION. PLEASE SUBMIT ONE. |
| |
| 11) THE SURVEY HAS THE INCORRECT LOMR |
| CASE # AND DATE FOR THE FLOOD ZONE. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |