Plan Review Details - Permit 03010600
Plan Review Stops For Permit 03010600
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-04-02 Cont ID  
Sent By jgomez Date 2003-04-02 Time 09:09 Rev Time 2.00
Received By jgomez Date 2003-04-02 Time 09:09 Sent To  
Notes
2003-04-02 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE SOIL TEST REPORT.
 2-SEE COMMENTS ON PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-03-24 Cont ID  
Sent By sthyng Date 2003-03-31 Time 13:23 Rev Time 0.00
Received By sthyng Date 2003-03-21 Time 14:41 Sent To  
Notes
2003-03-21 00:00:00**********CORRECTIONS************
  
 1.)DRAWINGS ARE STILL MISSING
 INFORMATION REQUIRED BY SEC 1606.1.7
 ITEM 4, FBC 2001.
  
 2.)DESIGN PARAMETERS PAGE INDICATE THE
 BUILDING AS A PARTIALLY ENCLOSED
 BUILDING.PLEASE REVISE.
  
 3.)COMPONENT AND CLADDING DESIGN
 WIND PRESSURES ON FIRST PAGE DO NOT
 MATCH ROOF COVERING CLADDING PRESSURES
 ON SHEET A-4.PLEASE CLARIFY.
  
 3.)AS REQUESTED BY JULIO GOMEZ,
 PLEASE GIVE INFORMATION AS TO WHY
 BEDROOMS 1 & 2 HAVE SAFETY GLASS.
  
 4.)PROVIDE A DETAIL FOR THE RAILING;
 MATERIAL, DIMENSIONS, ATTACHMENTS, AND
 LOAD INFORMATION (FBC 1608.2.2).
  
 5.)ROOF PITCH ON PLANS IS 3.5/12.
 ROOF PITCH ON TRUSS DRAWINGS IS 4/12.
 PLEASE REVISE.
  
 6.)PROVIDE PRODUCT APPROVALS FOR
 THE FRONT DOOR.THE PRODUCT APPROVAL
 SUBMITTED IS FOR A SOLID DOOR, NOT ONE
 WITH A WINDOW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 561-659-8096, EXTENSION 8340

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-03-06 Cont ID  
Sent By sthyng Date 2003-03-18 Time 08:17 Rev Time 2.50
Received By jgomez Date 2003-03-06 Time 15:10 Sent To  
Notes
2003-03-06 00:00:001-DRAWINGS ARE STILL MISSING INFORMATION
 REQUIRED BY SEC. 1606.1.7 FBC 2001.
 SEE THIS SECTION FOR REQUIRED FIVE (5)
 ITEMS TO BE INCLUDED IN DRAWINGS.
 2-CLARIFY WHAT ARE THE DESIGN WIND PRE-
 SSURES WRITTEN BY HAND ON THE SITE
 PLAN. ARE THESE FOR COMPONENT AND
 CLADDING?. PLEASE, REVISE ORIGINAL
 DRAWING. DON'T WRITE IT BY HAND.
 3-CLARIFY WHY WINDOWS ON BEDROOMS 1 & 2
 HAVE SAFETY GLASS?. SEC. 104.2.1.2
 CITY AMEMDMENTS TO FBC 2001.
 4-DIMENSIONS GIVEN ON SITE PLAN DON'T
 ADD UP CORRECTLY. REVISE AS REQUIRED.
 5-PROVIDE DETAIL/SPECS FOR CEILING INS-
 TALLATION AT FRONT AND REAR PORCH.
 CLEARLY SPECIFY FASTENERS AND SPACING
 AS REQ'D BY ASTM C926 AND ASTM C1063.
 SECTION 2504.2 FBC 2001.
 6-STORM SHUTTERS INFORMATION SUBMITTED:
 A)DRAWINGS DON'T MATCH PRODUCT APPROVAL.
  
 7-IMPACT FEES: NEED DRAWINGS STAMPED BY
 PALM BEACH COUNTY SHOWING EITHER NO
 FEES DUE OR CREDIT FOR EXISTING HOUSE.
 8-NEED PRODUCT APPROVAL FOR ENTRY DOOR
 W/ GLASS. SEE EXTERIOR ELEVATIONS.
 **NOTE: CLARIFY WHY ENTRY DOOR HAVE NOT
 STORM SHUTTERS IF IT HAS GLASS?SEE
 EXTERIOR ELEVATIONS.
 9-REVISE STRUCTURAL BUCK DETAIL. SEE
 SECTION 1707.4.4 FBC 2001 FOR SPECIFIC
 REQUIREMENTS FOR 2X BUCK AND REVISE
 DETAIL ACCORDINGLY. ALSO, DRAW DETAIL
 AT A LARGER SCALE TO BE ABLE TO SEE
 BUCK LOCATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-02-04 Cont ID  
Sent By kstevens Date 2003-02-28 Time 17:59 Rev Time 3.00
Received By jgomez Date 2003-02-03 Time 10:39 Sent To  
Notes
2003-02-03 00:00:00BUILDING REVIEW CHECKLIST:
 1-A)PROVIDE SITE PLAN DRAWN TO SCALE AND
 WITH DIMENSIONS THAT MATCH SURVEY
 B)SPECIFY BUILDING SIDE SETBACKS ALSO.
 C)WHAT'S FSC SHOWN ON CODE EDITION USED.
 WE USE FLORIDA BUILDING CODE (FBC)2001
 D)BUILDING CODE/WIND LOAD DESIGN CERTIFI
 CATION IS MISSING SOME INFORMATION.
 SEE SEC. 1606.1.7 FBC 2001 FOR ALL
 FIVE ITEMS REQUIRED ON EVERY JOB.
  
 2-PROVIDE SURVEY WITH ORIGINAL SIGNATURE
 AND SEAL AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.
 3-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS AND SEC. 2405.2 FBC 2001.
 4-SPECIFY SIZE OF ATTIC ACCESS. SECTION
 2309.6 FBC 2001.
 5-SPECIFY SIZE OF ATTIC VENTS. SECTION
 2309.7 FBC 2001.
 6-PROVIDE DETAILS/SPECIFICATIONS FOR
 CEILING INSTALLATION AT FRONT AND REAR
 PORCHES. AND SPECIFY FASTENERS SIZE &
 SPACING AS REQUIRED BY ASTM C-926 AND
 ASTM C-1063. SEC. 2504.2 FBC 2001.
 7-CLARIFY WHAT IS SIMPSON LSTA24-4?.
 HOW IS THIS STRAP TIE USED TO CONNECT
 THE WOOD COLUMN TO THE BEAM AT MID AND
 CORNER LOCATIONS? PROVIDE DETAIL. THIS
 TYPE OF CONNECTOR PROVIDES NOT UPLIFT
 AND LATERAL SUPPORT. SEE SIMPSON CAT.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 8-SHEET S-1:
 A)SPECIFY SUPPORTS & SPACING FOR WWM
 IN CONCRETE SLAB. SEE SEC. 1909.3 FBC.
 B)SPECIFY SIZE OF VAPOR BARRIER SEE SEC.
 1909.2 FBC 2001.
 C)SPECIFY FIREBLOCKING IN TYPICAL WALL
 SECTION. SEE SEC. 2305.1.4 FBC 2001.
  
 9-FOOTING SIZE SPECIFIED ON FOUNDATION
 PLAN DOESN'T MATCH SIZE SHOWN ON WALL
 SECTION. REVISE AS REQUIRED.
 10-PROVIDE ROOF FRAMING PLAN SHOWING
 CALCULATED UPLIFT LOADS AND PROVIDE
 TRUSS ANCHOR SCHEDULE AS REQUIRED.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 11-A/C AREA AND UNDER ATTIC AREA SHOWN
 ON THE ENERGY CALCULATIONS DON'T MATCH
 PLANS. REVISE AS REQUIRED. ALSO, WRITE
 SPECIFIC ADDRESS.
 12-PRODUCT APPROVAL FOR EXTERIOR DOORS
 IS EXPIRED. ALSO, CLARIFY IF THIS IS
 THE SAME DOOR FOR ENTRY DOOR,REAR DOOR
 AND STORAGE DOOR. OTHERWISE, PROVIDE
 PRODUCT APPROVAL FOR EACH.
 13-STORM SHUTTERS:
 A)PROVIDE KEY PLAN & COMPLETE INSTALLA-
 TION SCHEDULE. SEE CITY SAMPLE.
 B)CLEARLY MARK ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE &
 SPACING TO BE USED ACCORDING TO THE
 MEAN ROOF HEIGHT, DESIGN PRESSURES,
 EDGE DISTANCE, CONNECTION TYPE, PANEL
 SPAN AND STRUCTURE TO BE ATTACHED TO.
 **NOTE: WHEN INFORMATION IS NOT COMPLETE
 SUB-CONTRACTOR MAY APPLY FOR SEPARATE
 PERMIT. CITY IMPLEMENTATION STANDARD
 FOR HURRICANE MISSILE IMPACT PROTECT'N
 14-CONTRACTOR'S INSURANCE IS EXPIRED.
 15-SHEET A-1: REVISE GENERAL NOTE #1. WE
 USE FLORIDA BUILDING CODE 2001, NOT
 STANDARD BUILDING CODE.
 16-PAY IMPACT FEES TO PALM BEACH COUNTY
 AND BRING BACK STAMPED DRAWINGS AND
 PAID RECEIPT.
 17-NEED RECORDED NOTICE OF COMMENCEMENT.
 18-PROVIDE STRUCTURAL BUCK DETAILS FOR
 DOORS & WINDOWS. SEE SECTION 1707.4.4
 FBC 2001 FOR SPECIFIC REQUIREMENTS
 ACCORDINT TO BUCK SIZE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-02-20 Cont ID  
Sent By btrobaug Date 2003-02-20 Time 18:51 Rev Time 0.50
Received By btrobaug Date 2003-02-18 Time 12:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-01-17 Cont ID  
Sent By btrobaug Date 2003-02-12 Time 16:27 Rev Time 1.00
Received By btrobaug Date   Time   Sent To P
Notes
2003-01-17 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THE FOLLOWING,MAKE
 CORRECTIONS, AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 2} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STAIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 4} THE GROUNDING ELECTRODE SYSYEM MUST
 COMPLY WITH 250-50(A)(B)&(C),CWP IF
 AVAILABLE.
  
 5} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE PER 210-12.
  
 6} NOTE ALL KITCHEN COUNTERTOP
 RECEPTACLES SHALL BE GFCI'S PER
 210-8(A)(6).
  
 7} PROVIDE AN OUTLET FOR THE A/C
 EQUIPMENT PER 210-63.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-03-31 Cont ID  
Sent By sthyng Date 2003-03-31 Time 13:23 Rev Time 0.00
Received By sthyng Date 2003-03-31 Time 13:23 Sent To B
Notes
2003-03-31 00:00:00TO JG DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-03-18 Cont ID  
Sent By sthyng Date 2003-03-18 Time 08:17 Rev Time 0.00
Received By sthyng Date 2003-03-18 Time 08:17 Sent To B
Notes
2003-03-18 00:00:00TO JG DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-02-12 Cont ID  
Sent By btrobaug Date 2003-02-12 Time 16:26 Rev Time 0.00
Received By btrobaug Date 2003-02-12 Time 16:26 Sent To E
Notes
2003-02-12 00:00:00TO WRT./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-14 Cont ID  
Sent By btrobaug Date 2003-01-14 Time 10:51 Rev Time 0.00
Received By btrobaug Date 2003-01-13 Time 10:50 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-01-18 Cont ID  
Sent By kstevens Date 2003-01-17 Time 17:20 Rev Time 0.50
Received By hmoser Date 2003-01-18 Time 10:11 Sent To B
Notes
2003-01-18 00:00:00NO PLANS 01/18/03 H.M.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-02-28 Cont ID  
Sent By kstevens Date 2003-02-28 Time 17:59 Rev Time 0.25
Received By kstevens Date 2003-02-28 Time 17:59 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-01-17 Cont ID  
Sent By btrobaug Date 2003-01-17 Time 10:59 Rev Time 0.75
Received By kstevens Date 2003-01-17 Time 17:14 Sent To M
Notes
2003-01-17 00:00:00DENIED
  
 RISER DIAGRAM SHALL BE IN ISOMETRIC FORM
 PLEASE SEE ATTACHED SHEET FOR EXAMPLE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2003-01-17 Cont ID  
Sent By btrobaug Date 2003-01-14 Time 10:51 Rev Time 0.00
Received By sgraham Date   Time   Sent To B
Notes
***NONE***