Plan Review Details - Permit 03010597
Plan Review Stops For Permit 03010597
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-09-21 Cont ID  
Sent By jgomez Date 2004-09-21 Time 13:59 Rev Time 0.50
Received By jgomez Date 2004-09-21 Time 13:59 Sent To PC
Notes
2004-09-21 00:00:00REVISION CHECKLIST:
 1-INFORMATION SUBMITTED IS NOT A
 REVISION. THIS IS NEW SCOPE OF WORK.
 NEED TO APPLY FOR A SEPARATE PERMIT
 FOR MASONRY WALLS. ALSO, NEED TO GET
 UTILITIES RELEASE PRIOR TO SUBMITTING
 APPLICATION FOR MASONRY WALLS BUILDING
 PERMIT. SEE ATTACHED PUBLIC UTILITIES
 EASEMENT CONSENT FORM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-04-02 Cont ID  
Sent By csiegber Date 2004-08-31 Time 14:44 Rev Time 2.00
Received By jgomez Date 2003-04-02 Time 12:13 Sent To  
Notes
2003-04-02 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE SOIL TEST REPORT.
 2-SEE COMMENTS ON PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-03-06 Cont ID  
Sent By sthyng Date 2003-03-31 Time 13:37 Rev Time 2.50
Received By jgomez Date 2003-03-06 Time 14:57 Sent To  
Notes
2003-03-06 00:00:001-DRAWINGS ARE STILL MISSING INFORMATION
 REQUIRED BY SEC. 1606.1.7 FBC 2001.
 SEE THIS SECTION FOR REQUIRED FIVE (5)
 ITEMS TO BE INCLUDED IN DRAWINGS.
 2-CLARIFY WHAT ARE THE DESIGN WIND
 PRESSURES WRITTEN BY HAND ON THE SITE
 PLAN. ARE THESE FOR COMPONENT AND
 CLADING?. AND, PLEASE DON'T WRITE INFO
 BY HAND. REVISE/UPDATE ORIGINAL DWGS.
 3-CLARIFY WHY WINDOWS ON BEDROOMS 1 & 2
 HAVE SAFETY GLASS?. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 4-DIMENSIONS GIVEN ON SITE PLAN DON'T
 ADD UP CORRECTLY. THEY EXCEED THE 50'
 OF LOT WIDTH. SEE DIMENSIONS GIVEN ON
 FRONT OF HOUSE AND REVISE AS REQUIRED.
 5-PROVIDE DETAIL/SPECIFICATIONS FOR
 CEILING INSTALLATION AT FRONT AND REAR
 PORCHES. CLEARLY SPECIFY ALL FASTENERS
 AND SPACING AS REQUIRED BY ASTM C926
 AND ASTM C1063. SEC. 2504.2 FBC 2001.
 6-STORM SHUTTERS INFORMATION SUBMITTED:
 A)DRAWINGS DON'T MATCH PRODUCT APPROVAL
 REPORT.
 B)ONLY ONE SET OF DRAWINGS SUBMITTED.
 PLEASE, PROVIDE 2 SETS WHEN RE-SUBMI-
 TTING CORRECT DRAWINGS.
  
 7-IMPACT FEES: NEED DRAWINGS STAMPED BY
 PALM BEACH COUNTY. SHOWING EITHER NO
 FEES DUE OR CREDIT FOR EXISTING HOUSE.
 8-ALL NEW DRAWINGS NEED TO BE RE-STAMPED
 BY HISTORIC PRIOR TO SUBMITTAL TO THIS
 OFFICE.
 9-NEED PRODUCT APPROVAL FOR ENTRY DOOR.
 SEE EXTERIOR ELEVATION FOR TYPE SHOWN.
 **NOTE: CLARIFY WHY ENTRY DOOR DOESN'T
 HAVE STORM SHUTTERS IF DOOR SHOWN ON
 EXTERIOR ELEVATION SHOWS GLASS IN IT.
 10-REVISE STRUCTURAL BUCK DETAIL. SEE
 SECTION 1707.4.4 FBC 2001 FOR SPECIFIC
 REQUIREMENTS FOR 2X BUCKS AND REVISE
 DETAIL ACCORDINGLY. ALSO, DRAW DETAIL
 AT A LARGER SCALE IN ORDER TO SEE IT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-02-04 Cont ID  
Sent By kstevens Date 2003-02-28 Time 18:24 Rev Time 3.00
Received By jgomez Date 2003-02-03 Time 16:34 Sent To  
Notes
2003-02-04 00:00:00BUILDING REVIEW CHECKLIST:
 1-SITE PLAN SHEET:
 A)PROVIDE SITE PLAN DRAWN TO SCALE.
 B)SPECIFY BUILDING SETBACKS.
 C)WHAT'S FSC SHOWN ON CODE EDITION USED.
 WE USE FLORIDA BUILDING CODE (FBC)2001
 D)BUILDING CODE/WIND LOAD DESIGN CERTI-
 FICATION IS MISSING SOME INFORMATION.
 SEE SEC. 1606.1.7 FBC 2001 FOR ALL
 FIVE ITEMS REQUIRED ON EVERY PROJECT.
  
 2-PROVIDE SURVEY WITH ORIGINAL SIGNATURE
 AND SEAL AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.
 3-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS AND SEC. 2405.2 FBC 2001.
 4-SPECIFY SIZE OF ATTIC ACCESS. SECTION
 2309.6 FBC 2001.
 5-SPECIFY SIZE OF ATTIC VENTS. SECTION
 2309.7 FBC 2001.
 6-PROVIDE DETAILS/SPECIFICATIONS FOR
 CEILING INSTALLATION AT FRONT AND REAR
 PORCHES. AND, SPECIFY FASTENERS SIZE &
 SPACING AS REQUIRED BY ASTM C926 AND
 ASTM C1063. SEC. 2504.2 FBC 2001.
 7-CLARIFY WHAT IS SIMPSON LSTA24-4?.
 HOW IS THIS STRAP TIE USED TO CONNECT
 WOOD COLUMN TO THE BEAM. PROVIDE
 DETAIL FOR INTERMEDIATE AND CORNER
 COLUMNS SHOWING INSTALLATION. SEE
 SIMPSON CATALOGUE FOR INTENDED USE OF
 CONNECTOR. CLARIFY HOW ARE LATERAL
 LOADS TAKEN CARE OF. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 8-SHEET S-1:
 A)SPECIFY SUPPORTS AND SPACING FOR WWM
 IN CNCRETE SLAB. SEE SEC. 1909.3 FBC.
 B)SPECIFY SIZE OF VAPOR BARRIER. SEE
 SEC. 1909.2 FBC 2001.
 C)TYPICAL WALL SECTION: SPECIFY REQUIRED
 FIREBLOCKING. SEE SEC. 2305.1.4 FBC.
  
 9-FOOTING SIZE SPECIFIED ON FOUNDATION
 PLAN DOESN'T MATCH SIZE SHOWN ON WALL
 SECTION. REVISE AS REQUIRED.
 10-PROVIDE ROOF FRAMING PLAN SHOWING
 CALCULATED UPLIFT LOADS AND PROVIDE
 TRUSS ANCHOR SCHEDULE. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 11-A/C AREA AND UNDER ATTIC AREA SHOWN
 ON THE ENERGY CALCULATIONS DON'T MATCH
 PLANS. REVISE AS REQUIRED. ALSO, NEED
 SPECIFIC ADDRESS AS REQ'D BY CHAPTER
 13 FBC 2001.
 12-PROVIDE APPROVAL FOR EXTERIOR DOORS
 IS EXPIRED. ALSO, CLARIFY IF THIS IS
 THE SAME DOOR FOR ENTRY DOOR, REAR
 DOOR & STORAGE DOOR. OTHERWISE, NEED
 PRODUCT APPROVAL FOR EACH TYPE OF DOOR
 13-STORM SHUTTERS:
 A)PROVIDE KEY PLAN AND COMPLETE INSTA-
 LLATION SCHEDULE. SEE CITY SAMPLE.
 B)CLEARLY MARK ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE &
 SPACING TO BE USED ACCORDING TO THE
 MEAN ROOF HEIGHT, DESIGN PRESSURES,
 EDGE DISTANCE, CONNECTION TYPE, PANEL
 SPAN AND STRUCTURE TO BE ATTACHED TO.
 **NOTE: IF INFORMATION IS INCOMPLETE THE
 SUB-CONTRACTOR MAY APPLY FOR SEPARATE
 PERMIT. CITY IMPLEMENTATION STANDARD
 FOR HURRICANE MISSILE IMPACT PROTECT'N
 14-SHEET A-1: REVISE GENERAL NOTE #1.
 USE FLORIDA BUILDING CODE 2001, NOT
 STANDARD BUILDING CODE.
 15-PAY IMPACT FEES TO PALM BEACH COUNTY
 AND BRING BACK STAMPED DRAWINGS AND
 PAID RECEIPT.
 16-NEED RECORDED NOTICE OF COMMENCEMENT.
 17-PROVIDE STRUCTURAL BUCK DETAIL FOR
 DOORS & WINDOWS. SEE SECTION 1707.4.4
 FBC 2001 FOR SPECIFIC REQUIREMENTS
 ACCORDING TO BUCK SIZE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-02-20 Cont ID  
Sent By btrobaug Date 2003-02-20 Time 16:24 Rev Time 0.50
Received By btrobaug Date 2003-02-20 Time 15:58 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-01-17 Cont ID  
Sent By btrobaug Date 2003-02-12 Time 15:31 Rev Time 1.17
Received By btrobaug Date   Time   Sent To P
Notes
2003-01-17 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THE FOLLOWING,MAKE
 CORRECTIONS,AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 ELECTRICAL CONTRACTOR TO PROVIDE SAME
 WHEN APPLYING FOR A PERMIT.
  
 2} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 3} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STAIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 4} THE GROUNDING ELECTRODE SYSTEM MUST
 COMPLY WITH 250-50(A)(B)&(C),CWP IF
 AVAILABLE.
  
 5} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE PER 210-12.
  
 6} NOTE ALL KITCHEN COUNTERTOP
 RECEPTACLES SHALL BE GFCI'S PER
 210-8(A)(6).
  
 7} PROVIDE AN OUTLET FOR THE A/C
 EQUIPMENT PER210-63.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT, 8392

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-08-31 Cont ID  
Sent By csiegber Date 2004-08-31 Time 14:44 Rev Time 0.00
Received By csiegber Date 2004-08-31 Time 14:44 Sent To B
Notes
2004-08-31 00:00:00TO JG DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-03-31 Cont ID  
Sent By sthyng Date 2003-03-31 Time 13:37 Rev Time 0.00
Received By sthyng Date 2003-03-31 Time 13:37 Sent To B
Notes
2003-03-31 00:00:00TO JG DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-03-18 Cont ID  
Sent By sthyng Date 2003-03-18 Time 08:13 Rev Time 0.00
Received By sthyng Date 2003-03-18 Time 08:13 Sent To B
Notes
2003-03-18 00:00:00TO JG DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-02-12 Cont ID  
Sent By btrobaug Date 2003-02-12 Time 15:31 Rev Time 0.00
Received By btrobaug Date 2003-02-12 Time 15:31 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-14 Cont ID  
Sent By btrobaug Date 2003-01-14 Time 11:38 Rev Time 0.00
Received By btrobaug Date 2003-01-13 Time 11:38 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-01-18 Cont ID  
Sent By kstevens Date 2003-01-17 Time 18:03 Rev Time 0.50
Received By hmoser Date 2003-01-18 Time 10:30 Sent To B
Notes
2003-01-18 00:00:00NO PLANS H.M.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-02-28 Cont ID  
Sent By kstevens Date 2003-02-28 Time 18:24 Rev Time 0.25
Received By kstevens Date 2003-02-28 Time 18:24 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-01-17 Cont ID  
Sent By btrobaug Date 2003-02-20 Time 16:25 Rev Time 0.25
Received By kstevens Date 2003-01-17 Time 17:58 Sent To M
Notes
2003-01-17 00:00:00DENIED
  
 SANITARY RISER DIAGRAM SHALL BE AN ISO-
 METRIC TYPE. SEE EXAMPLE SHOWN ON PERMIT
 #03010600 FOR CORRECT ISOMETRIC.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2003-01-17 Cont ID  
Sent By btrobaug Date 2003-01-14 Time 11:38 Rev Time 0.00
Received By sgraham Date   Time   Sent To B
Notes
***NONE***