Plan Review Stops For Permit 03010434 |
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2003-01-31 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-01-31 |
Time |
14:28 |
Rev Time |
1.25 |
Received By |
kstevens |
Date |
2003-01-31 |
Time |
14:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2003-01-16 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-01-16 |
Time |
15:37 |
Rev Time |
1.50 |
Received By |
kstevens |
Date |
2003-01-16 |
Time |
15:37 |
Sent To |
|
|
Notes |
2003-01-16 00:00:00 | DENIED | | REFERENCE: FBC-2001 FUEL GAS | | | | 1) PLANS SHALL BE SIGNED AND SEALED BY | | THE ENGINEER OF RECORD. | | 2) ALL CUT SHEETS BTU RATINGS SHALL | | MATCH UP WITH BUT'S SHOWN ON GAS RISER. | | 3. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2001 | | FUEL GAS CODE. SHOW ALL MEASUREMENTS FOR | | DROPS AND LENGTH OF HEADER AT OVENS. | | 4. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE BEING USED. | | PE CHART SHOWN BUT NO PE PIPE SHOWN. | | 5. EMERGENCY HOOD SHUT DOWN SHUT OFF | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | DOWN STREAM OF MANUAL VALVE. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|
|