Plan Review Details - Permit 03010326
Plan Review Stops For Permit 03010326
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-01-15 Cont ID  
Sent By lsmith Date 2003-01-13 Time 16:10 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
2003-01-13 00:00:00*******PROVISO*******
 1.) NEED PROD APP FOR EXT STEEL DOOR
 REFERENCED IN A-1, DOOR 110B
 2.) DOOR 106 - CHANGE DOOR TO OBTAIN
 MANEUVERING CLEARANCE AT DOORS OF
 MIN 18" AS PER FBC 11.71, FIGURE 25
  
 ANY QUESTIONS PLEASE CALL
 LEA SMITH, BUILDING PLANS EXAMINER
 659-8096EXT 8394

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-01-21 Cont ID  
Sent By dpalmer Date 2003-01-21 Time 06:38 Rev Time 0.33
Received By dpalmer Date 2003-01-21 Time 06:38 Sent To  
Notes
2003-01-21 00:00:00REDLINED PLANS FOR REQ`D SIGN CIRCUIT.
 600-5, NEW OR EXISTING.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-01-09 Cont ID  
Sent By btrobaug Date 2003-01-17 Time 18:39 Rev Time 0.33
Received By dpalmer Date 2003-01-09 Time 06:19 Sent To  
Notes
2003-01-09 00:00:00************ UNSAT **********
  
 1)NOTE: PLEASE CLARIFY LOAD SUMMARY AND
 PANEL SCHEDULE SHOWING TWO DIIFERENT
 KVA LOADS? PLEASE SHOW CONTINUOUS LOADS
 AT 125%.
  
 2)NOTE: PLEASE CLARIFY MISSING FEEDERS
 FOR NEW PANEL?PLEASE
 SIZE PER 310-16.
  
 3)NOTE: PLEASE CLARIFY METHOD OF EQUIP-
 -MENT GROUND BETWEEN MAIN DISC/METER
 AND NEW PANEL "LL"> PLEASE NOTE, IF
 NMC, PLEASE SIZE PER 250-122.
  
 4)NOTE: PLEASE CLARFIY IF THERE IS NEW
 OR EXISTING SIGN CIRCUIT PER 600-5.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-01-15 Cont ID  
Sent By nmccray Date 2003-01-15 Time 14:51 Rev Time 0.00
Received By nmccray Date 2003-01-14 Time 14:51 Sent To  
Notes
2003-01-15 00:00:00PROVISO:
 1) DOOR 106 CAN NOT OBSTRUCT DOOR 104 OR
 DOOR 107.
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT. 8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-17 Cont ID  
Sent By btrobaug Date 2003-01-17 Time 18:39 Rev Time 0.00
Received By btrobaug Date 2003-01-16 Time 18:39 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-09 Cont ID  
Sent By dpalmer Date 2003-01-09 Time 06:18 Rev Time 0.00
Received By dpalmer Date 2003-01-09 Time 06:18 Sent To  
Notes
2003-01-09 00:00:00TO COMMM BOARD #25, BP

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-01-13 Cont ID  
Sent By pkrauss Date 2003-01-13 Time 14:14 Rev Time 0.25
Received By pkrauss Date 2003-01-13 Time 14:14 Sent To  
Notes
2003-01-13 00:00:00PROVISO ON PLAN

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-01-11 Cont ID  
Sent By jleech Date 2003-01-11 Time 13:17 Rev Time 0.75
Received By jleech Date 2003-01-11 Time 13:17 Sent To  
Notes
***NONE***