Plan Review Details - Permit 03010216
Plan Review Stops For Permit 03010216
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-22 Cont ID  
Sent By shernand Date 2003-05-22 Time 10:04 Rev Time 0.00
Received By shernand Date 2003-05-22 Time 10:04 Sent To P
Notes
2003-05-22 00:00:00KS DESK, REVISION.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-05-24 Cont ID  
Sent By kstevens Date 2003-05-24 Time 14:47 Rev Time 0.75
Received By kstevens Date 2003-05-24 Time 14:47 Sent To  
Notes
2003-05-24 00:00:00PASSED/PROVISO
 -VALVES REQUIRED BEFORE REGULATOR
 - DRYER IN CONFINED SPACE, OPENINGS RE-
 QUIRED PER SEC 304.3.1 OR 304.3.2
 - MANUF INSTALLATION SHEETS REQUIRED AT
 FINAL FOR GENERATOR.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-01-17 Cont ID  
Sent By shernand Date 2003-05-22 Time 10:04 Rev Time 1.00
Received By kstevens Date 2003-01-17 Time 10:10 Sent To  
Notes
2003-01-17 00:00:00PASSED/PROVISO
  
 VALVES REQUIRED PRIOR TO REGULATORS.
 DRYER IN CONFINED - SECTION 304.3 TWO
 OPENINGS REQUIRED.
 MANUFACTURE INSTALLATION INSTRUCTIONS
 REQUIRED AT FINAL FOR GENERATOR.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 PASSED/PROVISO
  
 - VALVES ARE REQUIRED PRIOR TO REGULATOR
 - DRYER IN CONFINED SPACE, TWO OPENINGS
 ARE REQUIRED PER SECTION 304.3.1
 - MANUFACTURE INSTALLATION SHEETS ARE
 REQUIRED AT FINAL FOR GENERATOR.
  
  
 PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING.