Plan Review Details - Permit 02121111
Plan Review Stops For Permit 02121111
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-07-08 Cont ID  
Sent By btrobaug Date 2003-07-08 Time 12:16 Rev Time 0.50
Received By btrobaug Date 2003-07-08 Time 12:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-02-13 Cont ID  
Sent By dpalmer Date 2003-02-13 Time 09:49 Rev Time 0.50
Received By dpalmer Date 2003-02-13 Time 09:49 Sent To B
Notes
2003-02-13 00:00:00SENT TO LOU HATTEN FOR ORGANIZING
 LETTERS AND PRODUCT APPROVALS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-02-06 Cont ID  
Sent By dpalmer Date 2003-02-06 Time 08:30 Rev Time 0.50
Received By dpalmer Date 2003-02-06 Time 08:30 Sent To  
Notes
2003-02-06 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE SEE NOTE FROM FIRST
 REVIEW PER FS/FAC. ALL PLANS MUST
 CONTAIN AN ORIG SIGNATURE BY ARCH OF
 RECORD FOR ALL SHEETS. 481.221.
 ALL TRADES,,,,,,,,,,
 PLEASE TAKE OUT OLD SHEETS AND INSERT
 NEW SHEETS INTO TWO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-01-08 Cont ID  
Sent By hmoser Date 2003-01-04 Time 12:32 Rev Time 0.50
Received By dpalmer Date 2003-01-08 Time 06:25 Sent To B
Notes
2003-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SEE MISSING RECEPT FOR
 KITCHEN COUNTERSPACE AS PER 210-52C-1
  
 2)NOTE: PLEASE SEE LOAD CALCULATIONS,
 SHOWS 4 SM APPL AND WASHER AT 6KW, ??
 PLEASE SEE 5 AT 1500 KW MIN IS 7500W?
 PLEASE ADJUST.
  
 3)NOTE: PLEASE NOTE ONLY TWO SMALL APPL
 IS SHOWN ON PANEL SCHEDULE AND THOSE
 ARE THE SHARED W/ DIN/NOOK. PLEASE NOTE
 OTHER TWO MUST ONLY BE FOR KITCHEN
 210-11C-1
  
 4)NOTE: PLEASE SEE LOAD CALCS, RANGE
 SHOWN AT 12KW AND PANEL SCHEDULE SHOWS
 ONLY 2P50A OCP. PLEASE ADJUST OCP TO
 MEET LOAD.
  
 5)NOTE: PLEASE SEE 2P-25A OCP FOR AHU #2
 PLEASE SEE 424-3B 10KW? 60A OCP. PLEASE
 ADJUST.
  
 6)NOTE: PLEASE NOTE, ALL DISC`S FOR A/C
 UNITS TO MEET 110-26.
  
 7)NOTE: PLEASE NOTE, ALL PLANS MUST
 CONTAIN ORIGINAL SIGNATURE, DATE, SEAL
 PER FS/FAC. 471.025 AND 481.221 FOR ARCH
 AND ENGINEERS. THIS IS FOR ALL SHEETS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-19 Cont ID  
Sent By dpalmer Date 2002-12-19 Time 11:20 Rev Time 0.00
Received By dpalmer Date 2002-12-19 Time 11:20 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-01-04 Cont ID  
Sent By jleech Date 2003-01-04 Time 08:31 Rev Time 0.50
Received By hmoser Date 2003-01-04 Time 12:32 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-01-04 Cont ID  
Sent By sgraham Date 2002-12-23 Time 13:00 Rev Time 0.33
Received By jleech Date 2003-01-04 Time 08:31 Sent To M
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2003-01-28 Cont ID  
Sent By lhatten Date 2003-01-28 Time 18:38 Rev Time 2.50
Received By lhatten Date 2003-01-25 Time 18:37 Sent To  
Notes
2003-01-28 00:00:00REVIEW & STAMPED PLANS 01/25/2003

Review Stop Z ZONING
Rev No 1 Status P Date 2002-12-23 Cont ID  
Sent By dpalmer Date 2002-12-19 Time 11:20 Rev Time 0.25
Received By sgraham Date   Time   Sent To P
Notes
***NONE***