Review Stop E ELECTRICAL
Rev No 5 Status P Date 2003-06-11 Cont ID  
Sent By btrobaug Date 2003-06-11 Time 13:30 Rev Time 0.33
Received By btrobaug Date 2003-06-11 Time 13:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-05-29 Cont ID  
Sent By btrobaug Date 2003-05-29 Time 12:59 Rev Time 0.50
Received By btrobaug Date 2003-05-29 Time 12:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-02-13 Cont ID  
Sent By shernand Date 2003-05-28 Time 09:18 Rev Time 0.33
Received By dpalmer Date 2003-02-13 Time 10:23 Sent To B
Notes
2003-02-13 00:00:00TO LOU HATTEN FOR ORGANIZING LETTERS
 AND PRODUCT APPROVALS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-02-06 Cont ID  
Sent By dpalmer Date 2003-02-06 Time 09:23 Rev Time 0.33
Received By dpalmer Date 2003-02-06 Time 09:08 Sent To  
Notes
2003-02-06 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE SEE FS/ FAC, 481.221
 PLANS HAVE ORIG SIGNATURE BY ARCH OF
 RECORD.ALL TRADES, ALL SHEETS.
  
 PLEASE TAKE OUT OLD SHEETS AND INSERT
 NEW SHEETS FOR TWO COMPLETE SETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-01-08 Cont ID  
Sent By hmoser Date 2003-01-04 Time 13:09 Rev Time 0.50
Received By dpalmer Date 2003-01-08 Time 08:00 Sent To B
Notes
2003-01-08 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE SEE MISSING RECEPT FOR
 KITCHEN COUNTERSPACE.210-52C1
  
 2)NOTE: PLEASE SEE LOAD CALCULATIONS,
 PLEASE SEE 4-SM APPL AND WASHER AT 1500W
 SHOWN AT 6KW,, PLEASE SEE 5@1500W = 7500
  
 3)NOTE: PLEASE ALSO NOTE ONLY TWO SMALL
 APPL CIRCUITS SHOWN ON PANEL SCHEDULE?
 210-52/210-11C-1
  
 4)NOTE: PLEASE SEE LOAD CALCS, RANGE
 SHOWN AT 12KW W/ 2P50A OCP. PLEASE
 ADJUST OCP TO MEET LOAD OF RANGE.
 12KW EXCEEDS RATING OF 50A BRKR.
  
 5)NOTE: PLEASE SEE 2P-25A BRKR ON 10KW
 HEAT/AHU #2. PLEASE SEE 424-3B FOR
 SIZING OF OCP. MIN 125%.
 AHU#1 SHOWN W/ 60A OCP FOR SAME SIZE
 UNIT.
  
 6)NOTE: PLEASE SEE PLANS, ALL DISC`S TO
 MEET 110-26. PLEASE NOTE.
  
 7)NOTE: PLEASE SEE FS/FAC FOR ALL PLANS
 REQ`D TO HAVE ORIGINAL SIGNATURE, DATE
 AND SEAL. 471.025 AND 481.22 FOR ARCH
 AND ENGINEERS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-28 Cont ID  
Sent By shernand Date 2003-05-28 Time 09:18 Rev Time 0.00
Received By shernand Date 2003-05-28 Time 09:18 Sent To E
Notes
2003-05-28 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-19 Cont ID  
Sent By dpalmer Date 2002-12-19 Time 11:20 Rev Time 0.00
Received By dpalmer Date 2002-12-19 Time 11:20 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-01-04 Cont ID  
Sent By jleech Date 2003-01-04 Time 07:29 Rev Time 0.50
Received By hmoser Date 2003-01-04 Time 13:08 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-01-04 Cont ID  
Sent By sgraham Date 2002-12-23 Time 13:02 Rev Time 0.33
Received By jleech Date 2003-01-04 Time 07:29 Sent To M
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2003-06-24 Cont ID  
Sent By jgomez Date 2003-06-24 Time 14:32 Rev Time 0.25
Received By jgomez Date 2003-06-24 Time 14:32 Sent To  
Notes
2003-06-24 00:00:00GARAGE BOLLARD DETAIL.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2003-01-28 Cont ID  
Sent By lhatten Date 2003-01-28 Time 18:20 Rev Time 2.50
Received By lhatten Date 2003-01-26 Time 18:19 Sent To  
Notes
2003-01-28 00:00:00REVIEW & STAMPED PLANS 01/26/2003
 PRINT CARD 01/28/2003

Review Stop Z ZONING
Rev No 1 Status P Date 2002-12-23 Cont ID  
Sent By dpalmer Date 2002-12-19 Time 11:20 Rev Time 0.25
Received By sgraham Date   Time   Sent To P
Notes
***NONE***