Plan Review Details - Permit 02120996
Plan Review Stops For Permit 02120996
Review Stop P PLUMBING
Rev No 2 Status P Date 2003-01-08 Cont ID  
Sent By kstevens Date 2003-01-08 Time 09:58 Rev Time 0.10
Received By kstevens Date 2003-01-08 Time 09:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-01-07 Cont ID  
Sent By kstevens Date 2003-01-07 Time 18:00 Rev Time 0.33
Received By kstevens Date 2003-01-07 Time 17:58 Sent To  
Notes
2003-01-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) ALL PLANS THAT HAVE A TITLE BLOCK
 SHALL BE SIGNED AND SEALED. 61G1-16.003
 2) A SANITARY RISER DIAGRAM AND A WATER
 RISER DIGARAM ARE REQUIRED. PLEASE SHOW
 ALL PIPE SIZES AND WHERE NEW PIPES TIE
 IN AND WHERE VENTS TERMINATE.
 3) ALL DEMO'ED PIPES TO BE CAPPED OFF
 SHALL BE INSPECTED PRIOR TO COVERING.
 4) TWO COPIES OF PLANS SHALL BE SUBMITT-
 ED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377