Plan Review Details - Permit 02120827
Plan Review Stops For Permit 02120827
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-12-26 Cont ID  
Sent By dpalmer Date 2002-12-23 Time 20:21 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2002-12-26 00:00:00PLUMBING FAILED; ELEC. NOT REGISTERED WI
 TH WPB.NEEDS SEPARATE PERMIT FOR ELEC
 FOR POOL.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-12-23 Cont ID  
Sent By kstevens Date 2002-12-21 Time 04:30 Rev Time 0.25
Received By dpalmer Date 2002-12-23 Time 20:21 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-06 Cont ID  
Sent By dpalmer Date 2003-01-06 Time 17:14 Rev Time 0.00
Received By dpalmer Date 2003-01-06 Time 17:14 Sent To P
Notes
2003-01-06 00:00:00TO PLUMB INBOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-12 Cont ID  
Sent By btrobaug Date 2002-12-12 Time 19:09 Rev Time 0.00
Received By btrobaug Date 2002-12-12 Time 19:09 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-01-15 Cont ID  
Sent By kstevens Date 2003-01-15 Time 13:22 Rev Time 0.75
Received By kstevens Date 2003-01-15 Time 13:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-12-21 Cont ID  
Sent By dpalmer Date 2003-01-06 Time 17:14 Rev Time 0.50
Received By kstevens Date 2002-12-21 Time 04:21 Sent To E
Notes
2002-12-21 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) COMPLY WITH FBC-2001 SEC 424.2
 PRIVATE SWIMMING POOLS. (ADD TO NOTES)
 2) FBC-2001424.2.6.6.3 (1,2,3) ENTRAP-
 MENT AVOIDANCE. (DETAIL) THIS DETAIL NOT
 CLEAR (SECTION 104.2.1 FBC CHAPTER 1)
 3) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER. (DETAIL) THIS DETAIL IS NOT
 CLEAR (SECTION 104.2.1 FBC CHAPTER 1)
 4) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 5) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 19) FBC-2001 104.2 BUILDING DRAWINGS, &
 SPECIFICATIONS. TOO MANY SWIMMING POOL
 PIPING SCHEMATICS ON THE PLANS. THIS IS
 VERY CONFUSING. SHOW INDIVIDUAL PIPING
 SCHEMATIC FOR POOL BEING BUILT,W/SPA.
 SHOW PIPING FOR THE ENTIRE SYSTEM, PIPE
 SIZES, VENTS, SUCTION AND DISCHARGE PIP-
 ING EXT. DELETE ALL OTHER SCHEMATICS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-12-18 Cont ID  
Sent By btrobaug Date 2002-12-12 Time 19:09 Rev Time 0.25
Received By sgraham Date   Time   Sent To P
Notes
***NONE***