Plan Review Stops For Permit 02120720 |
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2002-12-24 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2002-12-24 |
Time |
06:31 |
Rev Time |
0.75 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
REV |
|
Notes |
2002-12-24 00:00:00 | REVISION, APPR PES. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2002-12-17 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2002-12-17 |
Time |
10:10 |
Rev Time |
1.00 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2002-12-17 00:00:00 | GAS PLAN REVIWED FBC 2001, DENIED,PES | | (1) SUBMIT MANUFACTURE SHEETS FOR ALL | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND FBC-2001 | | FUEL GAS CODE SEC. 402.2 | | (2) BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | FBC-2001 FUEL GAS CODE SECS 401.8 THRU | | 402.5.2 & TABLES 402(1) THRU 402(34). | | (3) SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE BEING USED. | | (4) SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2001 | | GAS CODE. | | END OF COMMENTSPAUL SCHMITZ | | QUESTIONS 561-659-8096X 8233 |
|
|
|