Plan Review Details - Permit 02120590
Plan Review Stops For Permit 02120590
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-01-07 Cont ID  
Sent By dpalmer Date 2003-01-21 Time 10:07 Rev Time 0.00
Received By lsmith Date   Time   Sent To E
Notes
2003-01-07 00:00:00*****************FAILED****************
  
 1. THE FOLLOWING WORK WAS STARTED
 WITHOUT A PERMIT:
 1. INTERIOR DEMO FRAMING
 2. NEW CONCRETE SLAB
 3. NEW ROOF RAFTERS & ROOF.
 4. NEW WINDOWS & DOORS.
 2. DRAWINGS SUBMITTED DO NOT SHOW
 EXISTING CONDITIONS OR WHAT WAS DONE
 WITHOUT A PERMIT.
 3. NEED ENGINEERING LETTER VERIFYING ALL
 EXISTING WORK THAT WAS COMPLETED WITHOUT
 A PERMIT MEETS WPB AND FBC 2001.
 4. WINDOWS MUST BE PROTECTED & PRODUCT
 APPROVALS MUST BE SUBMITTED WITH
 PERMIT APPLICATION.
 5. PLUMBING & ELECTRICAL PERMITS MUST BE
 APPLIED FOR WITH PROPER PLANS BY
 LICENSED CONTRACTORS.
 6. PER TOM MOORE: A4X FEE IS DUE
 BECAUSE WORK WAS DONE WITHOUT A PERMIT.
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 659-8096 EXT. 8394

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2003-01-21 Cont ID  
Sent By lsmith Date 2003-01-23 Time 14:02 Rev Time 0.25
Received By dpalmer Date 2003-01-21 Time 10:06 Sent To B
Notes
2003-01-21 00:00:00NO ELECTRICAL PLANS SUBMITTED FOR REVIEW
 SEPARATE PERMIT /PLANS AT LATER DATE.

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2003-01-08 Cont ID  
Sent By lsmith Date 2003-01-08 Time 08:43 Rev Time 0.75
Received By btrobaug Date 2003-01-07 Time 14:03 Sent To P
Notes
2003-01-07 00:00:00TO TOM MOORE, ON DEMO LIST./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-01-17 Cont ID  
Sent By btrobaug Date 2003-01-17 Time 15:07 Rev Time 0.00
Received By btrobaug Date 2003-01-17 Time 15:07 Sent To P
Notes
2003-01-17 00:00:00IN BOX./WRT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-06 Cont ID  
Sent By dpalmer Date 2003-01-06 Time 14:11 Rev Time 0.00
Received By dpalmer Date 2003-01-06 Time 14:11 Sent To B
Notes
2003-01-06 00:00:00TO LEA SMITH'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-09 Cont ID  
Sent By btrobaug Date 2002-12-09 Time 17:55 Rev Time 0.00
Received By btrobaug Date 2002-12-09 Time 17:55 Sent To B
Notes
2002-12-09 00:00:00MISC BOX./WRT

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-01-11 Cont ID  
Sent By jleech Date 2003-01-11 Time 11:50 Rev Time 0.33
Received By jleech Date 2003-01-11 Time 11:50 Sent To  
Notes
2003-01-11 00:00:00DENIED;
 1. 4" DRYER VENT REQUIRED. MUST VENT TO
 OUTSIDE.
 2.EXHAUST FANS ARE REQUIRED IN BATHROOMS
 VENTED TO THE OUTSIDE. SEE SEC.502.3
 PLAN REVIEW BY;
 JOHN LEECH

Review Stop P PLUMBING
Rev No 2 Status N Date 2003-01-18 Cont ID  
Sent By kstevens Date 2003-01-18 Time 09:13 Rev Time 0.33
Received By kstevens Date 2003-01-18 Time 09:13 Sent To B
Notes
2003-01-18 00:00:00NO PLUMBING WORK SHOWN - RISER DIAGRAM
 IS FOR EXISTING BATHROOM

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-01-11 Cont ID  
Sent By btrobaug Date 2003-01-17 Time 15:07 Rev Time 0.75
Received By jleech Date 2003-01-11 Time 11:38 Sent To  
Notes
2003-01-11 00:00:00DENIED;
 1.PAGE A-1 KITCHEN SINK NOT SHOWN ON
 DRAWING.
 2.DWELLING IS REQUIRED TO HAVE HOT
 WATER. WHERE IS WATER HEATER?
 3.PAGE A-2 RISER DIAGRAM SHOWS ONE
 BATHROOM WITH A SHOWER. WHERE IS THIS
 BATHROOM LOCATED? EXISTING BATHROOMS
 HAVE TUBS.
 4.PLEASE SHOW COMPLETE RISER DIAGRAM OF
 PLUMBING SYSTEM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369