Plan Review Details - Permit 02120531
Plan Review Stops For Permit 02120531
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-01-13 Cont ID  
Sent By lsmith Date 2003-01-13 Time 13:52 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
2003-01-13 00:00:00********PROVISO*********
 PROVISO - NEED PRODUCT APPROVALS FOR
 1.) ROOF ASSEMBLY
 2.) DOUBLE LOUVERED DOORS (SEE A-1 7)
 3.) DOUBLE STORE FRONT DOORS (SEE A-1 5)
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 659-8096 EXT 8394

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-12-10 Cont ID  
Sent By dpalmer Date 2002-12-10 Time 05:48 Rev Time 0.30
Received By dpalmer Date 2002-12-10 Time 05:48 Sent To  
Notes
2002-12-10 00:00:00*********** NOTE ********
  
 PLANS REDLINED FOR THE CORRECT NEC AND
 NFPA-72 YEARS. PLANS REF. 1993.
 99 NFPA-70 AND 2001 NFPA-72.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-12-12 Cont ID  
Sent By mcarsill Date 2002-12-12 Time 14:21 Rev Time 0.00
Received By mcarsill Date 2002-12-12 Time 14:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-06 Cont ID  
Sent By btrobaug Date 2002-12-06 Time 17:34 Rev Time 0.00
Received By btrobaug Date 2002-12-06 Time 17:34 Sent To  
Notes
2002-12-06 00:00:00COMM BOARD #27./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2003-01-13 Cont ID  
Sent By pkrauss Date 2003-01-13 Time 13:59 Rev Time 0.05
Received By pkrauss Date 2003-01-13 Time 13:59 Sent To  
Notes
2003-01-13 00:00:00NO MECHANICAL PLANS SUBMITTED FOR REVIEW
 PLEASE PROVIDE PLANS WITH MECHANICAL
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-01-02 Cont ID  
Sent By hmoser Date 2003-01-02 Time 14:06 Rev Time 0.50
Received By hmoser Date 2003-01-02 Time 14:06 Sent To  
Notes
2003-01-02 00:00:00PLAN DENIED
 NO MECHANICAL PLANS
 HAROLD MOSER 1/2/03

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-01-14 Cont ID  
Sent By kstevens Date 2003-01-14 Time 09:50 Rev Time 0.75
Received By kstevens Date 2003-01-14 Time 09:50 Sent To  
Notes
2003-01-14 00:00:00PASSED/PROVISO
  
 VACUMM RELIEF VALVE REQUIRED FOR BOTTOM
 FED WATER HEATERS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-12-31 Cont ID  
Sent By kstevens Date 2002-12-31 Time 10:08 Rev Time 1.75
Received By kstevens Date 2002-12-31 Time 10:07 Sent To  
Notes
2002-12-31 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) SHT M-1 GENERAL NOTES #1, CODE REFER-
 ENCE TO READ FBC-2001 PLUMBING & FUEL
 GAS.
 2) SHT M-1 WATER HEATER DETAIL, VACUUM
 RELIEF VALVE REQUIRED FOR ALL BOTTOM FED
 WATER HEATERSSEC 504.2.
 3) SEPARATE PERMIT REQUIRED FOR GAS:
 FOLLOWING INFORMATION REQUIRED FOR GAS
 APPLICATION.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. TYPE OF GAS, (LP OR NATURAL)
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 F. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 G. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2003-01-14 Cont ID  
Sent By tjonseck Date 2003-01-14 Time 11:04 Rev Time 0.00
Received By tjonseck Date   Time   Sent To  
Notes
***NONE***