Plan Review Details - Permit 02120407
Plan Review Stops For Permit 02120407
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-04-01 Cont ID  
Sent By jwitmer Date 2003-04-01 Time 07:42 Rev Time 0.55
Received By jwitmer Date 2003-04-01 Time 07:39 Sent To  
Notes
2003-04-01 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02120407
 ADD: 1225 OMAR RD
 CONT: LCI CONSTRUCTION
 TEL: (561)307-4934
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION:PROVISO
  
 1) ADDITIONAL INFORMATION WILL BE RE-
 QUIRED FOR THE VERTICAL LIFT. MANUFACT-
 URES SPECS & SHOP DRAWINGS.
  
 2) AS PER THE DISCUSSION WITH THE BUILD-
 ING OFFICIAL INDICATE WHAT WORK WILL BE
 DONE FOR THE 20% DISPROPORTIONATE COST.
 (2ND FLOOR BATHROOM).
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-03-28 Cont ID  
Sent By jwitmer Date 2003-03-04 Time 13:18 Rev Time 1.55
Received By jwitmer Date 2003-03-04 Time 13:18 Sent To  
Notes
2003-03-04 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02120407
 ADD: 1225 OMAR ROAD
 CONT: LCI CONSTRUCTION OF S FLORIDA
 TEL: (561)659-5111
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 VERTICAL ACCESSIBILITY:11-4.1.6(1)(F)
 NOTHING IN THIS CODE SHALL BE CONSTRUED
 TO RELIEVE THE OWNER OF ANY BUILDING,
 STRUCTURE OR FACILITY FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL
 LEVELS REGARDLESS OF WETHER THE CODE
 REQUIRES AN ELEVATOR TO BE INSTALLED.
 THIS BUILDING DOES NOT FALL INTO THE
 EXCEPTION CATOGORY.
  
 11-4.1.6(1)(K)(I) THIS CODE SECTION INDI
 CATES THAT 3000 SQ FT IS REQUIRED FOR AN
 ELEVATOR,TRUE. THE CODE STILL REQUIRES
 VERTICAL ACCESSIBILITY, 11-4.1.3EXCEP-
 TION 4, PLATFORM LIFTS OR RAMPS.
  
 THIS BUILDING IS A TRUE ALTERATION, NO
 ADDITION IS BEING COMPLETED IN THIS
 PROJECT. IN DISCUSSING YOUR PROJECT WITH
 NEIL MELICK (BUILDING OFFICIAL) HE
 BROUGHT UP THAT THIS CAN BE CONSIDERED
 ALTERATIONS TO AN AREA CONTAINING A
 PRIMARY FUNCTION (11-4.1.6(2). AN ALTERA
 TION THAT AFFECTS OR COULD AFFECT THE
 USABILITY OF OR ACCESS TO AN AREA CON-
 TANING A PRIMARY FUNCTION SHALL BE MADE
 SO AS TO ENSURE THAT, TO THE MAXIMUM EXT
 ENT FEASIBLE, THE PATH OF TRAVEL TO
 THE ALTERED AREA AND THE RESTROOMS,
 TELEPHONES, AND DRINKING FOUNTINS SERV-
 ING THE ALTERED AREAS.THE DISPROPORTIONA
 TE COST DOES NOT INCLUDE VERTICAL ACCESS
 IBILITY.
  
 COPIES OF REQUEST FOR WAIVER FROM
 ACCESSIBILITY REQUIREMENTS OF CHAPTER
 553 PART V, FLORIDA STATUTES IS ATTACHED
 TO THE PLAN REVIEW COMMENTS.
  
 PRODUCT TESTING REPORTS: MISSING
 REPORTS FOR (3) OVERHEAD GARAGE DOORS.
  
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-03-04 Cont ID  
Sent By btrobaug Date 2002-12-10 Time 12:31 Rev Time 0.75
Received By jwitmer Date 2003-01-02 Time 08:11 Sent To  
Notes
2003-01-02 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02120407
 ADD: 1225 OMAR RD
 CONT: LCI CONSTRUCTION
 TEL: (561)659-5111
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)ALL INFORMATION, DRAWINGS, SPECIF-
 ICATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 CITY AMENDMENTS 104.2.1
  
 2) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 FL S.S.481.229 LICENSURE WHEN REQUIRED
 (C) COMMERCIAL BUILDINGS WITH A BUILDING
 VALUE GREATER THAN $25,000.00.
  
 3)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 MISSING FLOOR PLAN OF REMODELED BUIULD-
 ING SHOWING USAGE OF ROOMS, EGRESS ETC.
  
 4) IS THIS A SINGLE TENANT OCCUPANCY?
 TABLE 704.1 OCCUPANCY SEPERATION
 REQUIREMENTS;
  
 5) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 6)11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENETRANCES WITH ALL ACCESSIBLE SPACES
 AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY. SHOW HANDICAPPED RESTROOMS.
  
 7)11-4.1.2 VERTICAL ACCESSIBILITY,
 NOTHING IN THIS CODE SHALL BE CONSTRUED
 TO RELIEVE THE OWNER OF ANY BUILDING,
 SSTRUCTURE OR FACILITY FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL
 LEVELS ABOVE OR BELOW THE OCCUPIAABLE
 GRADE LEVEL.
  
 8)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 9)11.4.3.11AREAS OF RESCUE ASSISTANCE
 INDICATE LOCATION AND CONSTRUCTION TYPE
 FOR AREAS OF REFUGE, INDICATE ON PLAN
 WHICH CASE USED (1-7).SPRINKLER BUILD?
  
 10) FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS.
  
 11) FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 11)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 121)L BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.MISSING REPORTS:
 A) WINDOWS
 B)MULLIONS?
  
 13)PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 15) 1606.4.4 ANCHOR METHODS. PROVIDE
 INFORMATION FOR INSTALLATION OF DOOR
 AND WINDOW BUCKS.
  
 16)1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED. IF EXTERIOR DOORS OTHER
 THAN GLAZED DOORS ARE REPLACED!
  
 17) 1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
  
 19) PLANS ARE NOT AS BUILTS THE TERM"AS
 BUILTS" REFERS TO A PERMITED JOB WITH
 REVISIONS SUBMITTED, THE FINAL PLAN WITH
 ALL REVISIONS SHOWN ON ONE PLAN " AS
 BUILT".
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2003-04-03 Cont ID  
Sent By dpalmer Date 2003-04-03 Time 19:06 Rev Time 0.33
Received By dpalmer Date 2003-04-03 Time 18:44 Sent To  
Notes
2003-04-03 00:00:00**********NOTE *******************
  
 PLEASE SEE PLANS, NOTES FROM LAST REVIEW
 WERE NOTE ADDRESSED. SAME PLANS WERE
 SUBMITTED BACK.
 BLDG PERMIT MAY BE PRINTED, HOWEVER
 NO ELECTRICAL WORK FROM THIS PLAN MAY
 BE DONE.
 PLEASE SUBMIT SEPARATE PLANS AND PERMITS
 FOR ANY FUTURE WORK/ ADDITION OF EXIT
 LTS?
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-03-18 Cont ID  
Sent By dpalmer Date 2003-03-18 Time 09:14 Rev Time 0.25
Received By dpalmer Date 2003-03-18 Time 09:14 Sent To  
Notes
2003-03-18 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE NOTE, PLANS HAVE NOW
 COME BACK IN W/ ELECTRICAL ITEMS ADDED.
 PLEASE SHOW CIRCUITS IF INSTALLING NEW?
 700-12E
  
 2)NOTE: PLEASE ALSO SEE FS/FAC481.221
 HAND WRITTEN CHANGES MUST BE SIGNED,
 DATED BY ARCH OF RECORD AT EACH CHANGE/
 REDLINE.
  
 PLEASE REVISE SHEET AND SUBMIT FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2002-12-11 Cont ID  
Sent By dpalmer Date 2002-12-11 Time 11:45 Rev Time 0.00
Received By dpalmer Date 2002-12-11 Time 11:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2003-04-04 Cont ID  
Sent By mcarsill Date 2003-04-04 Time 10:39 Rev Time 0.00
Received By mcarsill Date 2003-04-04 Time 10:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2003-03-19 Cont ID  
Sent By mcarsill Date 2003-03-19 Time 13:26 Rev Time 0.00
Received By mcarsill Date 2003-03-19 Time 13:26 Sent To  
Notes
2003-03-19 00:00:00PLANS DO NOT INDICATE ANY EXISTING OR
 NEW EMERGENCY LIGHTING EQUIPMENT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2003-02-28 Cont ID  
Sent By mcarsill Date 2003-02-28 Time 09:17 Rev Time 0.00
Received By mcarsill Date 2003-02-28 Time 09:17 Sent To  
Notes
2003-02-28 00:00:001) PLANS AGAIN DO NOT INDICATE EXISTING
 EXIT SIGNS OR EMERGENCY LIGHTING
 EQUIPMENT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-12-19 Cont ID  
Sent By mcarsill Date 2002-12-19 Time 12:52 Rev Time 0.00
Received By mcarsill Date 2002-12-19 Time 12:52 Sent To  
Notes
2002-12-19 00:00:001) PLANS DO NOT REFLECT ANY EXISTING
 OR NEW EXIT SIGNS OR EMERGENCY LIGHTING.
  
 2) NO INTERIOR FINISH CLASSIFICATION
 INFORMATION FOR WALLS AND CEILINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 689-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-03-11 Cont ID  
Sent By sthyng Date 2003-03-11 Time 09:21 Rev Time 0.00
Received By sthyng Date 2003-03-11 Time 09:21 Sent To  
Notes
2003-03-11 00:00:00COMM BOARD #5

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-02-27 Cont ID  
Sent By dpalmer Date 2003-02-27 Time 17:29 Rev Time 0.00
Received By dpalmer Date 2003-02-27 Time 17:29 Sent To  
Notes
2003-02-27 00:00:00TO COMM BORAD #21 B& FIRE.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2002-12-11 Cont ID  
Sent By dpalmer Date 2002-12-11 Time 11:43 Rev Time 0.00
Received By dpalmer Date 2002-12-11 Time 11:42 Sent To  
Notes
2002-12-11 00:00:00PLACED ON COMM BOARD #8.
 B

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-12-11 Cont ID  
Sent By dpalmer Date 2002-12-11 Time 09:09 Rev Time 0.50
Received By dpalmer Date 2002-12-11 Time 09:09 Sent To  
Notes
2002-12-11 00:00:00PLANS PUT OUTFRONT UNDER "L" FOR PU.
 CALLED CONT 3 TIMES, NO RETURN CALL.
 ONLY PLAN SUBMITTED WAS THE SAME
 "AS-BUILTS" THAT WERE SUBMITTED WITH
 THE INTERIOR DEMO APPLICATION.
  
 SCOPE OF WORK ON APPLICATION NEEDS PLANS
 TO GO THROUGH REVIEW PROCESS.
  
  
 DEWEY PALMER
 INCOMING/PROCESSING.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-10 Cont ID  
Sent By btrobaug Date 2002-12-10 Time 12:31 Rev Time 0.00
Received By btrobaug Date 2002-12-10 Time 12:31 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-12-27 Cont ID  
Sent By pkrauss Date 2002-12-27 Time 11:46 Rev Time 0.20
Received By pkrauss Date 2002-12-27 Time 11:44 Sent To  
Notes
2002-12-27 00:00:00MECHANICAL PERMIT REQUIRED.PLEASE
 PROVIDE THE FOLLOWING INFORMATION WITH
 MECHANICAL PERMIT APPLICATION.
  
 PERMIT APPLICATION INDICATES REPLACEMENT
 OF 2 AC UNITS & DAMAGED DUCTWORK.
  
 PROVIDE NEW EQUIPMENT INFORMATION,
 INDICATE IF EQUIPMENT WILL BE AN EXACT
 CHANGEOUT.
  
 PROVIDE LAYOUT OF DUCTWORK, IDENTIFY
 NEW & EXISTING.SHOULD RETURN AIR BE
 BE MEANS OF A PLENUM, NO COMBUSTIBLES
 ALLOWED AS PER 2001 FBC(M) 602.2.1.
  
 PROVIDE OUTSIDE AIR CALCULATIONS AS PER
 2001 FBC(M) TABLE 403.3 OR ASHRAE 62-89.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-03-22 Cont ID  
Sent By kstevens Date 2003-03-22 Time 08:03 Rev Time 0.50
Received By kstevens Date 2003-03-22 Time 08:03 Sent To  
Notes
2003-03-22 00:00:00PASSED - PROVISO
  
 SUSBMIT SANITARY RISER DIAGRAM AND WATER
 RISER DIAGRAM PRIOR TO INSPECTION.
 SECTION 104.3.1.1 MINIMUM PLAN REVIEW
 CRITERIA FOR BUILDINGS PLUMBING.