Plan Review Details - Permit 02120180
Plan Review Stops For Permit 02120180
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-12-31 Cont ID  
Sent By hmoser Date 2002-12-28 Time 08:05 Rev Time 0.25
Received By dpalmer Date 2002-12-31 Time 07:06 Sent To B
Notes
2002-12-31 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE SEE PLANS, REDLINED,
 CORRELATE OCP/AWG FOR SUB PANEL.
 SHOWN AS #10 W/ 40OCP.
  
 PLEASE REVISE AND SUBMIT FOR REVIEW
 BEFORE ROUGH ELECTRICAL INSPECTION IS
 CALLED IN. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-02 Cont ID  
Sent By shernand Date 2003-05-02 Time 18:06 Rev Time 0.00
Received By shernand Date 2003-05-02 Time 18:06 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-04 Cont ID  
Sent By btrobaug Date 2002-12-04 Time 16:05 Rev Time 0.00
Received By btrobaug Date 2002-12-04 Time 16:05 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-05-08 Cont ID  
Sent By pkrauss Date 2003-05-08 Time 08:59 Rev Time 0.25
Received By pkrauss Date 2003-05-08 Time 08:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-12-28 Cont ID  
Sent By shernand Date 2003-05-02 Time 18:06 Rev Time 0.25
Received By hmoser Date 2002-12-28 Time 08:05 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-12-16 Cont ID  
Sent By sgraham Date 2002-12-12 Time 10:07 Rev Time 0.25
Received By jleech Date 2002-12-16 Time 18:43 Sent To M
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2003-01-13 Cont ID  
Sent By jgomez Date 2003-01-13 Time 08:19 Rev Time 2.00
Received By jgomez Date 2003-01-13 Time 08:19 Sent To PC
Notes
2003-01-13 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-PROVIDE SOIL TEST REPORT.
 3-FLOOD ZONE A8: WILL NEED THE ELEVATION
 CERTIFICATE.
 4-CLARIFY DETAIL S21 FOR COLUMN LOCATED
 BETWEEN GARAGE AND STAIRWAY SHOWING
 HOW IS THE STRAP HOLDING THE 2 GIRDER
 TRUSSES. SEC. 104.2.1.2 CITY AMENDMENT
 5-REVISE CONNECTOR TC-1 SPECIFIED ON
 ROOF FRAMING PLAN AT FRONT ELEVATION.
 NEED WOOD TO WOOD CONNECTOR FOR FRAMED
 WALL. SEC. 104.2.1.2 CITY AMENDMENTS.
 6-REVISE STAIR TOP DETAIL ON SHEET A-4
 TO MATCH 2ND FLOOR FRAMING PLAN AND
 SPECIFY FIREBLOCKING AS REQUIRED BY
 SEC. 2305.1.4 FBC 2001.
 7-34SH WINDOW DOESN'T PROVIDE THE 24"
 MIN. CLEAR HEIGHT. ALSO, VERIFY THAT
 24+5 SH WINDOW PROVIDE THE 5.7 S.F.
 MIN. CLEAR OPENING. SEC. 1005.4.4 FBC

Review Stop Z ZONING
Rev No 1 Status P Date 2002-12-12 Cont ID  
Sent By btrobaug Date 2002-12-04 Time 16:05 Rev Time 0.25
Received By sgraham Date   Time   Sent To P
Notes
***NONE***