Plan Review Details - Permit 02120179
Plan Review Stops For Permit 02120179
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-12-30 Cont ID  
Sent By hmoser Date 2002-12-28 Time 06:54 Rev Time 0.25
Received By dpalmer Date 2002-12-30 Time 18:41 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-05-05 Time 10:10 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 10:10 Sent To M
Notes
2003-05-05 00:00:00MECH REVISION

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-04 Cont ID  
Sent By dpalmer Date 2002-12-04 Time 17:16 Rev Time 0.00
Received By dpalmer Date 2002-12-04 Time 17:15 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-05-12 Cont ID  
Sent By pkrauss Date 2003-05-12 Time 14:01 Rev Time 0.25
Received By pkrauss Date 2003-05-12 Time 14:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-12-28 Cont ID  
Sent By shernand Date 2003-05-05 Time 10:10 Rev Time 0.25
Received By hmoser Date 2002-12-28 Time 06:54 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-12-17 Cont ID  
Sent By sgraham Date 2002-12-12 Time 09:59 Rev Time 0.25
Received By jleech Date 2002-12-17 Time 17:09 Sent To M
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2003-01-02 Cont ID  
Sent By jgomez Date 2003-01-02 Time 16:52 Rev Time 2.50
Received By jgomez Date 2003-01-02 Time 16:52 Sent To  
Notes
2003-01-02 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-FLOOD ZONE A8. NEED TO PROVIDE THE
 ELEVATION CERTIFICATE.
 3-SHEET A-1: REVISE NOTE #24. SEE SEC.
 1007.5.1 FBC 2001 FOR HANDRAIL HEIGHT.
 **NOTE: HANDRAIL AND GUARDRAILS ARE NOT
 THE SAME THING.
 4-GLASS BLOCK TO BE SAFETY GLASS IF FACE
 THICKNESS IS LESS THAN 0.25". SECTION
 2405.2.2 FBC 2001.
 5-SHEET A-4: REVISE NOTE #1. SEE SECTION
 1007.5.1 FBC 2001 FOR HANDRAIL HEIGHT.
 NOTE: HANDRAIL AND GUARDRAIL ARE NOT
 THE SAME THING.
 6-PROVIDE GENERAL SPECS FOR FIREBLOCKING
 AT ALL CONCEALED SPACES AS REQUIRED BY
 SEC. 2305.1.4 FBC 2001.
 7-PROVIDE COMPLETE DETAIL/SECTION FOR
 CONNECTION AT TOP OF COLUMN BETWEEN
 GARAGE AND KITCHEN. CLARIFY HOW IS
 COLUMN TOP CONNECTOR RECEIVING THE TWO
 GIRDER TRUSSES COMING FROM DIFFERENT
 POINTS. SEC. 104.2.1.2 CITY AMENDMENTS
 8-SHEET S-3: PROVIDE SPECS ON STRUCTURAL
 WALL SECTIONS FOR FIRECUT REQUIREMENTS
 SEC. 2305.4 FBC 2001.
 9-DETAIL R19: CLEARLY SPECIFY ALL CONNEC
 TORS. ROOF FRAMING PLAN DOESN'T SPEC
 THEM. SEC. 104.2.1.2 CITY AMENDMENTS.
 10-SPECIFY SIZE OF ANCHOR BOLT & WASHER
 FOR GARAGE DOOR STRUCTURAL BUCK DETAIL
 SE. 104.2.1.2 CITY AMENDMENTS TO FBC.
 11-PROVIDE SOIL TEST REPORT.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-12-12 Cont ID  
Sent By dpalmer Date 2002-12-04 Time 17:16 Rev Time 0.25
Received By sgraham Date   Time   Sent To P
Notes
***NONE***