Plan Review Details - Permit 02120175
Plan Review Stops For Permit 02120175
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-12-31 Cont ID  
Sent By hmoser Date 2002-12-28 Time 08:13 Rev Time 0.25
Received By dpalmer Date 2002-12-31 Time 06:55 Sent To B
Notes
2002-12-31 00:00:00********** NOTES REDLINED ********
  
 1)NOTE: PLEASE SEE PANEL SCHEDULE,
 SHOWS 40A OCP ON #10 FOR SUB PANEL.
 CORRELATE W/ RISER,
  
 PLEASE REVISE PLAN AND SUBMIT FOR REVIEW
 BEFORE ROUGH INSPECTION. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-29 Cont ID  
Sent By shernand Date 2003-05-29 Time 11:58 Rev Time 0.00
Received By shernand Date 2003-05-29 Time 11:58 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-04 Cont ID  
Sent By dpalmer Date 2002-12-04 Time 17:13 Rev Time 0.00
Received By dpalmer Date 2002-12-04 Time 17:13 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-06-05 Cont ID  
Sent By pkrauss Date 2003-06-05 Time 09:00 Rev Time 0.25
Received By pkrauss Date 2003-06-05 Time 08:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-12-28 Cont ID  
Sent By shernand Date 2003-05-29 Time 11:58 Rev Time 0.25
Received By hmoser Date 2002-12-28 Time 08:13 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-12-16 Cont ID  
Sent By sgraham Date 2002-12-12 Time 09:49 Rev Time 0.25
Received By jleech Date 2002-12-16 Time 18:14 Sent To M
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2003-01-10 Cont ID  
Sent By jgomez Date 2003-01-10 Time 16:27 Rev Time 2.00
Received By jgomez Date 2003-01-10 Time 16:27 Sent To  
Notes
2003-01-10 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-FLOOD ZONE A8: NEED TO PROVIDE THE
 ELEVATION CERTIFICATE.
 3-CLARIFY DETAIL S21 FOR COLUMN LOCATED
 BETWEEN GARAGE AND STAIR WAY SHOWING
 HOW ARE THE TWO GIRDER TRUSSES CONNEC-
 TED TO COLUMN WITH THE STRAP. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 4-REVISE STAIR ENLARGED TOP AREA DETAIL
 ON SHEET A-4 TO MATCH FRAMING PLAN AND
 SPECIFY FIREBLOCKING. SEE SECTION
 2305.1.4 FBC 2001.
 5-REVISE/CLARIFY SIZE OF BEDROOM EGRESS
 WINDOWS. 34SH WINDOW DOESN'T PROVIDE
 THE 24" MIN. CLEAR HT. ALSO, VERIFY
 THAT 24+5 SH WINDOW PROVIDE 5.7 S.F.
 MIN. CLEAR OPENING. SEC. 1005.4.4 FBC.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-12-12 Cont ID  
Sent By dpalmer Date 2002-12-04 Time 17:13 Rev Time 0.25
Received By sgraham Date   Time   Sent To P
Notes
***NONE***