2003-01-09 00:00:00 | BUILDING REVIEW PROVISO: |
| 1-PROVIDE COMPLETE INFORMATION FOR STORM |
| SHUTTERS UNDER A SEPARATE PERMIT. |
| 2-FLOOD ZONE A8. NEED TO PROVIDE THE |
| ELEVATION CERTIFICATE. |
| 3-SHEET A-1: REVISENOTE #24. SEE SEC. |
| 1007.5.1 FBC 2001 FOR HANDRAIL HEIGHT. |
| NOTE: HANDRAILS AND GUARDRAILS ARE |
| NOT THE SAME. |
| 4-GLASS BLOCK TO BE SAFETY GLASS IF FACE |
| THICKNESS IS LESS THAN 0.25". AS REQ'D |
| BY SEC. 2405.2.2 FBC 2001. |
| 5-SHEET A-4: REVISE NOTE #1. SEE SECTION |
| 1007.5.1 FBC 2001 FOR HANDRAIL HEIGHT. |
| 6-PROVIDE GENERAL SPECS FOR FIREBLOCKING |
| AT ALL CONCEALED SPACES AS REQUIRED |
| BY SEC. 2305.1.4 FBC 2001. |
| 7-PROVIDE COMPLETE DETAIL/SECTION AT |
| TOP OF COLUMN LOCATED BETWEEN GARAGE |
| AND KITCHEN TO SHOW HOW ARE THE TWO |
| GIRDER TRUSSES ATTACHED WITH AN STRAP |
| AND NOT A BUCKET CONNECTOR. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 8-SHEET S-3: PROVIDE SPECS ON STRUCTURAL |
| WALL SECTIONS FOR FIRECUT REQUIREMENTS |
| SEC. 2305.4 FBC 2001. |
| 9-DETAIL R19: CLEARLY SPECIFY ALL CONNEC |
| TORS. ROOF FRAMING PLAN DOESN'T SHOW |
| THEM. SEC. 104.2.1.2 CITY AMENDMENTS. |
| 10-SPECIFY SIZE OF ANCHOR BOLT & WASHER |
| FOR GARAGE DOOR STRUCTURAL BUCK DETAIL |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |