Plan Review Details - Permit 02120171
Plan Review Stops For Permit 02120171
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-12-31 Cont ID  
Sent By hmoser Date 2002-12-28 Time 09:52 Rev Time 0.25
Received By dpalmer Date 2002-12-31 Time 06:09 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-05-05 Time 10:09 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 10:09 Sent To M
Notes
2003-05-05 00:00:00MECH REVISION

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-04 Cont ID  
Sent By btrobaug Date 2002-12-04 Time 17:14 Rev Time 0.00
Received By btrobaug Date 2002-12-04 Time 17:14 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-05-12 Cont ID  
Sent By pkrauss Date 2003-05-12 Time 13:43 Rev Time 0.25
Received By pkrauss Date 2003-05-12 Time 13:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-12-28 Cont ID  
Sent By shernand Date 2003-05-05 Time 10:09 Rev Time 0.50
Received By hmoser Date 2002-12-28 Time 09:51 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-12-17 Cont ID  
Sent By sgraham Date 2002-12-12 Time 09:56 Rev Time 0.25
Received By jleech Date 2002-12-17 Time 18:58 Sent To M
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2003-01-09 Cont ID  
Sent By jgomez Date 2003-01-09 Time 15:25 Rev Time 2.00
Received By jgomez Date 2003-01-09 Time 15:25 Sent To  
Notes
2003-01-09 00:00:00BUILDING REVIEW PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-FLOOD ZONE A8. NEED TO PROVIDE THE
 ELEVATION CERTIFICATE.
 3-SHEET A-1: REVISENOTE #24. SEE SEC.
 1007.5.1 FBC 2001 FOR HANDRAIL HEIGHT.
 NOTE: HANDRAILS AND GUARDRAILS ARE
 NOT THE SAME.
 4-GLASS BLOCK TO BE SAFETY GLASS IF FACE
 THICKNESS IS LESS THAN 0.25". AS REQ'D
 BY SEC. 2405.2.2 FBC 2001.
 5-SHEET A-4: REVISE NOTE #1. SEE SECTION
 1007.5.1 FBC 2001 FOR HANDRAIL HEIGHT.
 6-PROVIDE GENERAL SPECS FOR FIREBLOCKING
 AT ALL CONCEALED SPACES AS REQUIRED
 BY SEC. 2305.1.4 FBC 2001.
 7-PROVIDE COMPLETE DETAIL/SECTION AT
 TOP OF COLUMN LOCATED BETWEEN GARAGE
 AND KITCHEN TO SHOW HOW ARE THE TWO
 GIRDER TRUSSES ATTACHED WITH AN STRAP
 AND NOT A BUCKET CONNECTOR. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 8-SHEET S-3: PROVIDE SPECS ON STRUCTURAL
 WALL SECTIONS FOR FIRECUT REQUIREMENTS
 SEC. 2305.4 FBC 2001.
 9-DETAIL R19: CLEARLY SPECIFY ALL CONNEC
 TORS. ROOF FRAMING PLAN DOESN'T SHOW
 THEM. SEC. 104.2.1.2 CITY AMENDMENTS.
 10-SPECIFY SIZE OF ANCHOR BOLT & WASHER
 FOR GARAGE DOOR STRUCTURAL BUCK DETAIL
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-12-12 Cont ID  
Sent By btrobaug Date 2002-12-04 Time 17:14 Rev Time 0.25
Received By sgraham Date   Time   Sent To P
Notes
***NONE***