Plan Review Details - Permit 02120162
Plan Review Stops For Permit 02120162
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-12-31 Cont ID  
Sent By dpalmer Date 2002-12-31 Time 06:22 Rev Time 0.25
Received By dpalmer Date 2002-12-31 Time 06:22 Sent To B
Notes
2002-12-31 00:00:00*********** NOTES ****************
  
 1)NOTE: PLEASE SEE PLANS FOR REDLINED
 NOTES, SHOWS 40A OCP ON #10 AWG FOR
 SUB-PANEL.
  
 PLEASE REVISE PLAN AND SUBMIT FOR REVIEW
 BEFORE ROUGH INSPECTION. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-29 Cont ID  
Sent By shernand Date 2003-05-29 Time 11:55 Rev Time 0.00
Received By shernand Date 2003-05-29 Time 11:54 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-04 Cont ID  
Sent By btrobaug Date 2002-12-04 Time 17:18 Rev Time 0.00
Received By btrobaug Date 2002-12-04 Time 17:18 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-06-05 Cont ID  
Sent By pkrauss Date 2003-06-05 Time 08:34 Rev Time 0.25
Received By pkrauss Date 2003-06-05 Time 08:23 Sent To  
Notes
2003-06-05 00:00:00MECH REV PERMIT 02120325

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-12-28 Cont ID  
Sent By shernand Date 2003-05-29 Time 11:55 Rev Time 0.33
Received By jleech Date 2002-12-28 Time 08:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-12-16 Cont ID  
Sent By sgraham Date 2002-12-12 Time 09:47 Rev Time 0.25
Received By jleech Date 2002-12-16 Time 19:09 Sent To M
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2003-01-10 Cont ID  
Sent By jgomez Date 2003-01-10 Time 08:57 Rev Time 2.00
Received By jgomez Date 2003-01-10 Time 08:57 Sent To  
Notes
2003-01-10 00:00:00BUILDING REVIEW PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-FLOOD ZONE A8. NEED TO PROVIDE THE
 ELEVATION CERTIFICATE.
 3-CLARIFY DETAIL S21 FOR COLUMN LOCATED
 BETWEEN GARAGE AND STAIRWAY SHOWING
 HOW IS SPECIFIED STRAP SUPPORTING THE
 TWO GIRDER TRUSSES. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 4-REVISE CONNECTOR TC-1 SPECIFIED AT
 FRONT ELEVATION. NEED WOOD TO WOOD
 CONNECTOR FOR FRAMED WALL. SEC. 104.2.
 1.2 CITY AMENDMENTS TO FBC 2001.
 5-PROVIDE SPECIFICATIONS ON STRUCTURAL
 WALL SECTIONS FOR FIRECUT REQUIREMENTS
 THAT COMPLY WITH SEC. 2305.4 FBC 2001.
 6-REVISE STAIR TOP DETAIL ON SHEET A-4
 TO MATCH FRAMING PLAN AND SPECIFY
 FIREBLOCKING. SEC. 2305.1.4 FBC 2001.
 7-34 SH WINDOW DOESN'T PROVIDE THE 24"
 MIN. CLEAR HEIGHT. ALSO, VERIFY THAT
 24+5 SH WINDOW PROVIDE THE 5.7 S.F.
 MIN. CLEAR OPENING. SEC. 1005.4.4
 FBC 2001.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-12-12 Cont ID  
Sent By btrobaug Date 2002-12-04 Time 17:18 Rev Time 0.25
Received By sgraham Date   Time   Sent To P
Notes
***NONE***