Plan Review Details - Permit 02120161
Plan Review Stops For Permit 02120161
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-12-31 Cont ID  
Sent By dpalmer Date 2002-12-31 Time 06:37 Rev Time 0.25
Received By dpalmer Date 2002-12-31 Time 06:37 Sent To B
Notes
2002-12-31 00:00:00************** NOTES REDLINED ********
  
 1)NOTE: PLEASE CORRELATE OCP/AWG, SUB-
 -PANEL IS SHOWN W/ 40OCP ON #10AWG,
 RISER SHOWS #6`S??
  
 PLEASE SUBMIT THE ABOVE REVISED FOR
 REVIEW BEFORE ROUGH INSPECTION IS CALLED
 IN. IF THERE ARE ANY QUESTIONS,PLEASE
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-02 Cont ID  
Sent By shernand Date 2003-05-02 Time 18:06 Rev Time 0.00
Received By shernand Date 2003-05-02 Time 18:06 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-04 Cont ID  
Sent By btrobaug Date 2002-12-04 Time 17:18 Rev Time 0.00
Received By btrobaug Date 2002-12-04 Time 17:18 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-05-07 Cont ID  
Sent By pkrauss Date 2003-05-07 Time 16:29 Rev Time 0.30
Received By pkrauss Date 2003-05-07 Time 16:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-12-28 Cont ID  
Sent By shernand Date 2003-05-02 Time 18:06 Rev Time 0.33
Received By jleech Date 2002-12-28 Time 08:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-12-17 Cont ID  
Sent By sgraham Date 2002-12-12 Time 09:58 Rev Time 0.25
Received By jleech Date 2002-12-17 Time 17:55 Sent To M
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2003-01-10 Cont ID  
Sent By jgomez Date 2003-01-10 Time 12:09 Rev Time 2.00
Received By jgomez Date 2003-01-10 Time 12:07 Sent To  
Notes
2003-01-10 00:00:00BUILDING REVIEW PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-FLOOD ZONE A8. NEED TO PROVIDE THE
 ELEVATION CERTIFICATE.
 3-CLARIFY DETAIL S21 FOR COLUMN LOCATED
 BETWEEN GARAGE AND STAIRWAY SHOWING
 HOW IS THE STRAP SUPPORTING THE TWO
 GIRDER TRUSSES. SETION 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 4-REVISE CONNECTOR TC-1 SPECIFIED AT
 FRONT ELEVATION ON ROOF FRAMING PLAN.
 NEED WOOD TO WOOD CONNECTOR FOR FRAMED
 WALL. SEC. 104.2.1.2 CITY AMENDMENTS.
 5-REVISE STAIR TOP DETAIL ON SHEET A-4
 TO MATCH FRAMING PLAN AND SPECIFY
 FIREBLOCKING. SEC. 2305.1.4 FBC 2001.
 6-34 SH WINDOW DOESN'T PROVIDE THE 24"
 MIN. CLEAR HEIGHT. ALSO, VERIFY IF
 24+5 SH WINDOW PROVIDE 5.7 S.F. MIN.
 CLEAR OPENING. SEC. 1005.4.4 FBC 2001.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-12-12 Cont ID  
Sent By btrobaug Date 2002-12-04 Time 17:18 Rev Time 0.25
Received By sgraham Date   Time   Sent To P
Notes
***NONE***