Plan Review Details - Permit 02120137
Plan Review Stops For Permit 02120137
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-04-02 Cont ID  
Sent By jwitmer Date 2004-04-02 Time 13:14 Rev Time 0.55
Received By jwitmer Date 2004-04-02 Time 13:14 Sent To  
Notes
2004-04-02 00:00:00REVISION DATED MARCH 10, 2004JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-05-29 Cont ID  
Sent By csiegber Date 2004-03-26 Time 16:24 Rev Time 2.00
Received By jwitmer Date 2003-05-29 Time 08:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-05-15 Cont ID  
Sent By jwitmer Date 2003-05-15 Time 08:14 Rev Time 1.50
Received By jwitmer Date 2003-05-15 Time 08:14 Sent To  
Notes
2003-05-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02120137
 ADD: 3400 N FLAGLER
 CONT:(PLAN REVIEW 3RD REVIEW)
 SANDERSON, MARK & FREDI
 CONTACT: LYNNE GILLIS
 TEL: (561)346-4249
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 PROVIDE TOTAL SQ. FT.AREA BOTH:
 A/C AREA
 NON A/C AREA, GARAGES PORCHES ETC
  
 ACTION: DENIED
  
 1) PROVIDE (2) COPIES OF SOILS REPORT
  
 2)PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 2001 FLORIDA ENERGY
 EFFICIENTCY CODE FOR BUILDING CONSTRUC-
 TION.
  
 3) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.
  
 WINDOWS: FIXED AND CASEMENT( ONLY 1
 REPORT FOR EACH)
 NO REPORT FOR LEADED GLASS
  
 4) STORM SHUTTERS NO SCHEDULE NOR
 KEY PLAN. SAMPLE ATTACHED
  
 5)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-04-03 Cont ID  
Sent By shernand Date 2003-05-05 Time 08:05 Rev Time 4.00
Received By jwitmer Date 2003-04-02 Time 15:47 Sent To ENG
Notes
2003-04-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02120137
 ADD: 3400 N FLAGLER DR
 CONT:(PLAN REVIEW/ 2ND REVIEW)
 SANDERSON, MARK & FREDI
 CONTACT: LYNNE GILLIS
 TEL: (561)346-4249
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 NOTES:
 1) FLOOD ZONE A5 MINIMUM ELEVATION 7.5'
 FOR FINISH FLOOR, A/C PADS AND POOL
 EQUIPMENT PADS (ELEC MOTORS). A FLOOD
 ZONE ELEVATION CERTIFICATE IS REQUIRED
 TO THIS DEPARTMENT BEFORE A C/O WILL BE
 ISSUED.
  
 2) NO BUILDING IN THE EASEMENTS SOUTH
 PROPERTY LINE INDICATES A 10' SEWER &
 DRAINAGE EASEMENT W / A 60" RCP PIPE.
  
  
 REVIEW:
 1) 1803.1.3 EXCAVATION FOR ANY PURPOSE S
 HALL NOT EXTEND WITHIN 1 FT OF THE
 ANGLE OF REPOSE OR NATURAL SLOPE OF THE
 SOIL UNDER ANY FOOTING OR FOUNDATION,
 UNLESS SUCH FOOTING OR FOUNDATION IS
 FIRST PROPERLY UNDERPINNED OR PROTECTED
 AGAINST SETTLEMENT.
  
 THE DETAIL PROVIDED BY BOTKIN ON
 SHEET S-5 DETAIL 13 DOESN'T INCLUDE THE
 1'=0" BEFORE THE ANGLE OF REPOSE, WHEN
 THE 1'-0" IS INCLUDED THE PIPE IS 1'-0"
 HIGHER IN THE TRENCH!
  
 2) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 3)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 DISCREPANCIES: ARCH PLAN, THE FAMILY
 ROOM FLOOR ELEVATION, HALL 117 & CABANA
 ARE INDICATED AS A 10'-0" F.F. DOORS
 6,7 & 8 INDICATE A SIX INCH DROP BUT
 DOOR # 10 IS MISSING THIS 6" DROP.
  
 THE SECOND ISSUE BETWEEN IN THIS SAME
 TERRACE FLOOR, ARCH PLANS INDICATE A
 6" DROP WHERE AS THE STRUCTURAL PLAN
 INDICATE A 4" DROP W/ 2" SLOPE?
  
 4) SHEET A-8 & A-11 EAST ELEVATION
 RE: GUARDRAILS 1026.5.1 TRUE GUARDRAILS
 FOR DWELLINGS, WITHIN INDIVIDUAL DWELL-
 ING UNITS OR GUEST ROOMS,AND IN RESIDENT
 IAL CARE/ ASSISTED LIVING OCCUPANCIES
 SHALL BE A MINIMUM OF 36" IN HEIGTH.
  
 1015.1 GUARDRAILS SHALL FORM A VERTICAL
 PROTECTIVE BARRIER NOT LESS THAN 42"
 HIGH.
  
 GUARDRAILS ON THE EXTERIOR OF THE BUILD-
 ING DO NOT HAVE THE EXCEPTION THAT MAY
 BE TAKEN IN 1026.5.1.
  
 5) 1606.5 COMPONENTS & CLADDING:
 INDICATE PRESSURE ZONES POSITIVE &
 NEGATIVE FOR (INTERIOR & END ZONES).
 INDICATE PRESSURES ON ELEVATIONS.
  
 BECAUSE THIS COMMENT WAS NOT ANSWERED
 THE PRODUCT TESTING REPORTS CAN NOT BE
 EVALUATED!!!!!
  
 PROVIDE (2) COPIES OF ALL PRODUCT TEST-
 ING REPORTS.
  
 6)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 7) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. THIS INFORMATION IS
 SUPPLIED BY THE CONTRACTOR USUALLY!
 MISSING REPORTS:
 A) GARAGE DOORS OVERHEAD, HIGHLIGHT AS
 TO WHICH DOOR THAT WILL BE SELECTED
 WITH THE APPROPRIATE DESIGN LOADS.
 B) SWING DOORS GLAZED & SOLID
 MISSINGTHE SOLID EXTERIOR DOOR
 REPORTS. EXAMPLE DOOR 15 OR 18
 C) WINDOWS, CASEMENT, FIXED, OR THE
 LEADED GLASS.
 A SEPERATE SHEET IS PROVIDED WITH
 ALL OF THE MARVIN WINDOWS & DOORS.
 SEPERATE NOA (NOTICE OF ACCEPTANCE)
 WILL BE REQUIRED FOR EACH APPLICA-
 TION, PROVIDE (2) COPIES PLEASE.
 D) MULLION: BOTH VERTICAL AND HORIZON-
 TAL APPLICATIONS REQUIRED.
 E) STORM SHUTTERS IF THE PRODUCT TEST-
 ING REPORTS HAVEN'T RECEIVED APPROV-
 AL FOR LARGE MISSLE IMPACT TESTING.
  
 8)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 9)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 10)PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 11)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE. SEE ATTACHMENT IF REQUIRED.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-01-23 Cont ID  
Sent By pkrauss Date 2003-03-31 Time 11:09 Rev Time 4.25
Received By jwitmer Date 2003-01-23 Time 09:59 Sent To  
Notes
2003-01-23 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02120137
 ADD: 3400 N FLAGLER DR
 CONT: (PLAN REVIEW)
 SANDERSON, MARK & FREDI
 CONTACT LYNNE GILLIS
 TEL: (561)346-4249
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 NOTES:
 1) FLOOD ZONE A5 MINIMUM ELEVATION 7.5'
 FOR FINISH FLOOR, A/C PADS AND POOL
 EQUIPMENT PADS (ELEC MOTORS). A FLOOD
 ZONE ELEVATION CERTIFICATE IS REQUIRED
 TO THIS DEPT BEFORE A C/O WILL BE ISSUED
  
 2) NO BUILDING IN EASEMENTS, SOUTH PROP
 LINE INDICATES 10' SEWER & DRAINAGE
 EASEMENT W/ A 60" RCP PIPE.
  
 3) THE SITE PLAN ISNOT CLEAR AS IF
 THE EXTERIOR LINE OF THE BUILD IS THE
 WALL LINE OR ROOF OVERHANG? IN EITHER
 CASE THE FOUNDATION (F2) SHALL NOT
 ENCHROUCH INTO THE 10' EASEMENT.
 1803.1.3 EXCAVATION FOR ANY PURPOSE
 SHALL NOT EXTEND WITHIN 1 FT OF THE
 ANGLE OF REPOSE OR NARURAL SLOPE OF THE
 SOIL UNDER ANY FOOTING OR FOUNDATION,
 UNLESS SUCH FOOTING OR FOUNDATION IS
 FIRST PROPERLY UNDERPINNED OR PROTECTED
 AGAINST SETTLEMENT.
 PLEASE PROVIDE INFORMATION FOR SECTION
 1803.2.2 FOR EXCAVATION OF EXISTING
 60" DRAINAGE SEWERAND REPLACEMENT?
  
 4) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 5) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 ARCH PLAN MISSING DATE STAMP ON SEAL
  
 6) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 PROVIDE A GEOTECH REPORT GIVING WHAT
 THE MINIMUM SAFE BEARING VALUE IS?
  
 7)FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 8)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 DISCREPANCY: THE FAMILY ROOM FLOOR ELEVA
 TION, HALL 117 AND CABANA ARE INDICATED
 AS 10'-0" DOOR OPENING #9 MISSING THE
 STEP DOWN. DISCREPANCY IS THE AMOUNT OF
 STEP DOWN ARCH PLAN (6") VS ENG PLAN
 (4")?
  
 9) GARAGE# 1 IS THERE OPENINGS ON THE
 SIDE WALLS DIRECTLY BEHIND THE FRONT
 ENTRY WALLS? SEE STRUCTURAL PLAN?
  
 10) BAYWINDOW AT MASTER BEDROOM, PLEASE
 PROVIDE ADD INFO AS TO HOW THE THE
 DOUBLE 2X12 HEADER WILL ATTACH BACK TO
 THE CMU'S SECTION 8/S6 IS NOT CLEAR.
  
 11) S-2 ROOF FRAMING PLAN: (4) USP-SGP2
 I BELIEVE THIS ANCHOR WAS MISREAD, THE
 SGP-2 HAS NAIL HOLES FOR 14 NAILS NOT
 24 AND THE DESIGNER IS TO SPECIFY THE
 TYPE OF ANCHOR TO BE USED. THE SGP-3
 DOES HAVE NAIL HOLES FOR 24 NAILS AS RE-
 QUIRED BY THE ENGINEER, AND A ALLOWABLE
 LOAD OF 2405 AT 160%.
  
 12) GARAGE 1 & 2,8" RISERS SEE 1007.3.1
 (1) RISERS SHALL NOT EXCEED 7 3/4".
  
 13) GUARDRAILS DESIGN AS PER LOCAL CODE!
 1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
  
 14)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 15)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) GARAGE DOORS SINGLE/ DOUBLE WIDE
 B) SWING DOORS BOTH GLAZED/ SOLID
 C) WINDOWS CASEMENT, FIXED,LEADED GLASS
 D) MULLIONS: VERETICAL/ HORIZONTAL
 E) ROOFING ASSEMBLIES
 F) STORM SHUTTERS
  
 16)1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 17) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 181707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 19)PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 20)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 21) 1606.1.5 COMPONENTS & CLADDING:
 INDICATE PRESSURE ZONES POSITIVE & NEG-
 ATIVE FOR OPENINGS IN WALLS, ON ELEVA-
 TIONS PLEASE.
  
 22) TABLE 500 PROVIDE MINIMUM BLDG TYPE,
 AND SQ. FOOTAGE A/C AND NON PER FLOOR
 FOR MAIN HOUSE AND OUT BLDG.
  
 23)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By btrobaug Date 2009-07-17 Time 13:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-05-08 Cont ID  
Sent By pkrauss Date 2003-05-12 Time 15:56 Rev Time 1.00
Received By btrobaug Date 2003-05-06 Time 12:18 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-03-24 Cont ID  
Sent By shernand Date 2003-05-05 Time 16:36 Rev Time 1.00
Received By btrobaug Date 2003-03-24 Time 06:49 Sent To M
Notes
2003-03-24 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 1} THERE ARE NO SMOKE DETECTORS ON
 SHEET E-4.PLEASE SHOW COMPLIANCE WITH
 8-1.4.1.6 NFPA-72.
  
 2} PLEASE NOTE THAT THE PANELS SHOWN IN
 THE CLOSET ON SHEET E-3(A,B,C,SB,AND
 LV'S) MUST COMPLY WITH110-26.
  
 3} THE SMOKE DETECTOR @ THE DOORWAY
 OF THE MASTER BEDROOM JUST AT THE
 HALL APPEARS TO BE INSIDE THE AREA OF
 THE MASTER BEDROOM AND WOULD THEREFORE
 NOT BE IN COMPLIANCE WITH 8-1.4.2
 NFPA-72,AS BEING LOCATED "OUTSIDE".
  
 THESE THREE COMMENTS WERE ON THE LAST
 REVIEW,IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096.EXT 8392.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-01-21 Cont ID  
Sent By sthyng Date 2003-03-19 Time 15:51 Rev Time 3.00
Received By btrobaug Date 2003-01-09 Time 18:28 Sent To  
Notes
2003-01-21 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGE
 ON PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE NOTE THAT ALL PLANS
 THAT ARE SIGNED AND SEALED BY ARCH/ OR
 ENGINEER ARE REQ`D PER 61G15-23.002 FOR
 ENGINEER AND 61G1-16.004 FOR ARCH.
 SHALL HAVE A TITLE BLOCK.
  
 2} PLEASE INDICATE THE AMPERE RATING OF
 THE METER ENCLOSURE.
  
 3} PLEASE INDICATE THE CONDUCTOR AND
 WIRE SIZE FROM THE METER TO THE M.D.P.
  
 4} THE FEEDER CONDUCTORS TO PANEL "N"
 ARE SHOWN AS NUMBER 1 ON MDP SCHEDULE
 AND 2/0'S ON THE RISER DIAGRAM.PLEASE
 CLARIFY.
  
 5} THE FEEDER CONDUCTORS TO PANEL "C"
 ARE SHOWN AS 3/0'S ON THE PANEL
 SCHEDULE AND 2/0 ON THE RISER
 DIAGRAM,PLEASE CLARIFY.
  
 6} THERE ARE NO SMOKE DETECTORS ON
 SHEET E4.PLEASE SHOW COMPLIANCE WITH
 8-1.4.1.6 NFPA-72.
  
 7} PLEASE NOTE THAT THE PANELS SHOWN IN
 THE CLOSET ON SHEET E3(A,B,C,SB AND LV'S
 MUST COMPLY WITH 110-26.
  
 8} THE SMOKE DETECTOR @ THE DOORWAY OF
 THE MASTER BEDROOM JUST AT THE
 HALL,APPEARS TO BE INSIDE THE AREA OF
 THE MASTER BEDROOM AND WOULD THEREFORE
 NOT BE IN COMPLIANCE 8-1.4.2 NFPA-72,AS
 BEING LOCATED "OUTSIDE".
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2003-05-13 Cont ID  
Sent By mamini Date 2003-05-13 Time 10:50 Rev Time 1.00
Received By mamini Date 2003-05-13 Time 10:50 Sent To P
Notes
2003-05-13 00:00:00PASSED WITH PROVISOS:
 1. SUBJECT TO THE CONDITIONS;
 A. NO CONSTRUCTION, TEMPORARY OR
 PERMANENT IN 10.0' DRAINAGE AREA, ANY
 CONSTRUCTION, TEMPORARY OR PERMANENT IN
 THE SAID AREA SHALL BE REMOVED AT THE
 OWNER'S EXPENSE AT THE TIME OF REPLACING
 THE DRAINAGE SYSTEM BY THE CITY.
 B. PROPOSED AUGER CAST-IN-PLACE PILE
 TIPS AT SOUTHSIDE SUPPORTING THE
 STRUCTURE MUST BE LOCATED AT MINIMUM
 22.0' BELOW THE FINISHED GROUND.
  
 IF ANY QUESTIONS PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2003-04-03 Cont ID  
Sent By pkrauss Date 2003-05-12 Time 16:09 Rev Time 2.00
Received By mamini Date 2003-04-03 Time 16:23 Sent To  
Notes
2003-04-03 00:00:00FAILED:
 1. WECONCUR WITH MR. JIM WITMER'S
 COMMENTSNO. 2 UNDER "NOTES" AND NO. 1
 UNDER "REVIEW" DATED 04-02-03.
 2. PER MY PHONE CONVERSATION ON 04-03-03
 AT 4:00 PM WITH MR. SANDERSON THE
 PROPERTY OWNER, PLEASE SUBMIT REVISED
 PLAN SHOWING THE PROPOSE CHANGES FOR THE
 SOUTHSIDE FOUNDATION ALONG THE EXISTING
 DRAINAGE EASEMENT AND FOR THE PRIVACY
 WALL.
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-03-26 Cont ID  
Sent By csiegber Date 2004-03-26 Time 16:24 Rev Time 0.00
Received By csiegber Date 2004-03-26 Time 16:24 Sent To B
Notes
2004-03-26 00:00:00TO JW DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-05-28 Cont ID  
Sent By shernand Date 2003-05-20 Time 16:57 Rev Time 0.00
Received By shernand Date 2003-05-20 Time 16:57 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-05-08 Cont ID  
Sent By shernand Date 2003-05-08 Time 14:36 Rev Time 0.00
Received By shernand Date 2003-05-08 Time 14:35 Sent To E
Notes
2003-05-08 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-05 Cont ID  
Sent By shernand Date 2003-05-05 Time 08:05 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 08:05 Sent To E
Notes
2003-05-05 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-19 Cont ID  
Sent By sgraham Date 2003-04-04 Time 10:08 Rev Time 0.00
Received By sthyng Date 2003-03-19 Time 15:51 Sent To E
Notes
2003-03-19 00:00:00TO BT DESK

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2003-06-06 Cont ID  
Sent By pkrauss Date 2003-06-06 Time 15:55 Rev Time 0.35
Received By pkrauss Date 2003-06-06 Time 15:55 Sent To  
Notes
2003-06-06 00:00:00PROVISO:
  
 1.AHU SHALL HAVE OVERFLOW PROTECTION
 BY MEANS OF AN AUXILIARY DRAIN PAN WITH
 A SECONDARY DRAIN TO TERMINATE AT A
 CONSPICUOUS POINT OR FLOAT SWITCH.
  
 2.AHU UNITS SHALL HAVE SUFFICIENT
 CLEARANCE FOR ACCESS & MAINTENANCE AS
 PER 2001 FBC CHAPTER 13 610.A.ABC.3.5.2.
  
 3.CONDENSATE LINES ARE NOT SHOWN ON
 THE MECHANICAL OR PLUMBING. TERMINATION
 SHALL COMPLY WITH 2001 FBC(M) 306.2.1 &
 SHALL DISCHARGE A MINIMUM OF 12" AWAY
 FROM THE BUILDING STRUCTURE 2001 FBC
 1503.4.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2003-05-28 Cont ID  
Sent By pkrauss Date 2003-05-28 Time 13:00 Rev Time 0.35
Received By pkrauss Date 2003-05-28 Time 13:00 Sent To P
Notes
2003-05-28 00:00:00DENIED:
  
 1.MANUAL J CALCULATIONS WERE NOT
 SUMITTED AS PER 2001 FBC CHAPTER 13
 SECTION 607.1.ABC.1, EQUIPMENT SIZING.
 THIS WILL BE THE 4TH REQUEST FOR THIS
 INFORMATION.
  
 PROVISO:
 2.PLEASE NOTE, AHU SHALL HAVE OVERFLOW
 PROTECTION BY MEANS OF AN AUXILIARY
 DRAIN PAN WITH A SECONDARY DRAIN TO
 TERMINATE AT A CONSPICUOUS POINT OR
 FLOAT SWITCH.
  
 3.AHU UNITS SHALL HAVE A SUFFICIENT
 CLEARANCE FOR ACCESS & MAINTENANCE AS
 PER 2001 FBC CHAPTER 13 610.1.ABC.3.5.2.
  
 4.CONDENSATE LINES ARE NOT SHOWN ON
 THE MECHANICAL OR PLUMBING.TERMINATION
 SHALL COMPLY WITH 2001 FBC(M) 306.2.1 &
 SHALL DISCHARGE A MINIMUM OF 12" AWAY
 FROM THE BUILDING STRUCTURE 2001 FBC
 1503.4.4.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2003-05-12 Cont ID  
Sent By shernand Date 2003-05-28 Time 10:35 Rev Time 0.40
Received By pkrauss Date 2003-05-10 Time 09:08 Sent To ENG
Notes
2003-05-10 00:00:00DENIED:
  
 3RD REQUEST - SUBMITT ENERGY & MANUAL J
 CALCS AS PER 2001 FBC CHAPTER 13 SECTION
 607.1.ABC.1, EQUIPMENT SIZING. AS PER
 FLORIDA STATUTE 553.80(2)(B), AFTER
 THIRD REVIEW THE PLANS ARE REJECTED FOR
 THE SAME CODE VIOLATION A FEE OF FOUR
 TIMES THE AMOUNT OF THE PORTION OF THE
 PERMIT FEE.
  
 AS PER 2001 FBC(M) TABLE 403.3, GARAGE
 SHALL HAVE A MINIMUM OF 100 CFM OUTSIDE
 AIR PER VEHICLE.PLAN SHEET M-3 THE
 EQUIPMENT SCHEDULE INDICATES
 A PROGRAMMBLE THERMOSTAT TO BE INSTALLED
 AS PER FBC CHAPTER 13, BUILDINGS(GARAGE)
 DESIGNED FOR PURPOSES OTHER THAN GENERAL
 SPACE COMFORT CONDITIONING SHALL BE
 CONTROLLED BY A HUMIDISTAT.
  
 NOTE #6, PROVIDE FRESH AIR TO EACH AHU
 GARAGES DO NOT SHOW ANY DUCT SIZE OR
 LAYOUT FOR FRSH AIR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-03-31 Cont ID  
Sent By btrobaug Date 2003-05-08 Time 14:39 Rev Time 0.45
Received By pkrauss Date 2003-03-27 Time 15:36 Sent To B
Notes
2003-03-31 00:00:00DENIED:
  
 COMMENTS FROM 1ST REVIEW NOT ADDRESSED.
 PROVIDE MANUAL J CALCS AS PER 2001 FBC
 CHAPTER 13 SECTION 607.1.ABC.1,
 EQUIPMENT SIZING.PROVIDE INFORMATION
 OF HVAC EQUIPMENT (MAKE, MODEL, BTU OF
 THE AHU & SEER OF THE CONDENSING UNIT).
  
 NO MECHANICAL PLANS INDICATING DUCT LAY-
 OUT OF LOCATION OF AHU'S OR CONDENSING
 UNITS SUBMITTED FOR REVIEW.
  
 SMOKE DETECTORS SHALL BE INSTALLED
 SUPPLY SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM, IN THE SUPPLY
 AIR DUCT. 2001 FBC(M) 606.2.1OR
 UPON ACTIVATION, THE SMOKE DETECTORS
 SHALL SHUTDOWN THE AIR DISTRIBUTION
 SYSTEM. 2001 FBC(M) 606.4
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-01-22 Cont ID  
Sent By btrobaug Date 2003-03-24 Time 06:56 Rev Time 0.25
Received By pkrauss Date 2003-01-22 Time 08:51 Sent To B
Notes
2003-01-22 00:00:00DENIED:
  
 NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PROVIDE MANUAL J CALCS AS PER
 2001 FBC CHAPTER 13 SECTION
 607.1.ABC.1, EQUIPMENT SIZING.PROVIDE
 INFORMATION ON HVACEQUIPMENT (MAKE,
 MODEL, BTU OF THE AHU & SEER OF THE
 CONDENSER UNIT).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-01-21 Cont ID  
Sent By pkrauss Date 2003-05-28 Time 13:12 Rev Time 0.50
Received By kstevens Date 2003-01-21 Time 18:07 Sent To M
Notes
2003-01-21 00:00:00PASSED/PROVISO
  
 NO HORIZONTAL DRY VENTS. (SEE BIDET)

Review Stop Z ZONING
Rev No 2 Status P Date 2003-04-04 Cont ID  
Sent By sgraham Date 2003-04-04 Time 10:08 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
2003-04-04 00:00:00APPROVED WITH THE FOLLOWING CONDITIONS:
 1.SEPARATE PERMITS REQUIRED FOR THE
 WALL AND POOL
 2.EASEMENT RELEASES REQUIRED FROM ALL
 FIVE UTILITY COMPANIES(MAX HEIGHT 6')
 3. D/W AND PARKING AREAS MUST BE A
 SMOOTH NON-DUSTING SURFACE.(PAVERS
 CONCRETE OR ASPHALT

Review Stop Z ZONING
Rev No 1 Status F Date 2002-12-10 Cont ID  
Sent By sgraham Date 2002-12-10 Time 13:38 Rev Time 0.25
Received By sgraham Date   Time   Sent To B
Notes
2002-12-10 00:00:00DENIED, 1. TOTAL HEIGHT OF BLDG & TOWER
 MUST BE 33'
 2.SEPARATE PERMIT REQUIRE FOR WALLS,
 NEED EASEMENT RELEASES FROM ALL FIVE
 UTILITY COMPANIES.
 3. HEIGHT OF WALL IN FRONT SETBACK IS
 4', THE SIDE & REAR MAX HEIGHT 6'