Plan Review Details - Permit 02120132
Plan Review Stops For Permit 02120132
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2003-08-11 Cont ID  
Sent By rbrown Date 2003-08-11 Time 08:59 Rev Time 0.00
Received By rbrown Date 2003-08-11 Time 08:58 Sent To  
Notes
2003-08-11 00:00:00REVISION SUBMITTED 7/28/03 INCREASING
 SCOPE TO INCLUDE SECOND FLOOR BUILD-OUT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2003-07-10 Cont ID  
Sent By rbrown Date 2003-07-10 Time 18:18 Rev Time 0.00
Received By rbrown Date 2003-07-10 Time 18:18 Sent To  
Notes
2003-07-10 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 REVISION SUBMITTED 6/17/03.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC* 104.1.5THE PROPOSED REVISIONS
 INCREASE THE SCOPE OF THE WORK.THE
 VALUE OF THE ADDITIONAL WORK SHALL BE
 DECLARED AND JUSTIFIED (E.G. WITH COPIES
 OF CONTRACTS) SO THAT THE ADDITIONAL
 PERMIT FEES DUE MAY BE DETERMINED.
  
 2) FBC 11-4.24BREAK ROOM #3.REVISED
 SHEET A9 DOES NOT SHOW ANY DETAILS TO
 DEMONSTRATE THE ACCESSIBILITY OF THE
 SINK IN BREAK ROOM #3.AMEND THE PLANS.
  
 3) FBC 2405.2THE FOLLOWING GLAZING IS
 IN A 'HAZARDOUS LOCATION' AND IS
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201):
 - THE GLAZING IN REVISED DOORS 2A & 2B
 - THE GLAZING IN THE TWO NEW DOORS #25
 - THE GLAZED SIDELITE PANELS ADJACENT
 EACH OF THE TWO NEW DOORS #25
 AMEND/ANNOTATE THE DOOR AND WINDOW
 SCHEDULES TO DEMONSTRATE COMPLIANCE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-03-25 Cont ID  
Sent By rbrown Date 2003-03-25 Time 11:20 Rev Time 0.00
Received By rbrown Date 2003-03-25 Time 11:20 Sent To  
Notes
2003-03-25 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 --PROVISO--
 THE SUBMITTED STORE FRONT DOOR PRODUCT
 APPROVAL NOA# 01-0919.02 IS FOR SINGLE
 UNIT APPLICATIONS ONLY, AND SO DOES NOT
 COVER THE MULLED SIDELITES ADJACENT
 DOOR #1.STRUCTURAL MULLIONS ARE
 REQUIRED. ALSO, THE SIDELITES EXCEED THE
 96" MAX. HEIGHT COVERED BY THE WINDOW
 WALL SYSTEM PRODUCT APPROVAL
 NOA# 01-0329.02, SO A HORIZONTAL MULLION
 IS REQUIRED.SUBMIT AN APPROPRIATE
 STRUCTURAL MULLION PRODUCT APPROVAL OR
 SITE SPECIFIC ENGINEERING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-03-19 Cont ID  
Sent By kstevens Date 2003-03-22 Time 15:42 Rev Time 0.00
Received By rbrown Date 2003-03-19 Time 14:46 Sent To  
Notes
2003-03-19 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 1/16/03:
  
 2) JMS DESIGN RESPONSE DATED 2/25/03 IS
 NOTED.IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 5) THE SUBMITTED STORE FRONT DOOR
 PRODUCT APPROVAL NOA# 01-0919.02 IS FOR
 SINGLE UNIT APPLICATIONS ONLY, AND SO
 DOES NOT COVER THE MULLED SIDELITES
 ADJACENT DOOR #1.SUBMIT AN APPROPRIATE
 STRUCTURAL MULLION PRODUCT APPROVAL OR
 SITE SPECIFIC ENGINEERING.
  
 17) FBC* 104.2.2SHEETS S.1, S.2, S.6
 AND S.8.POST SEAL AMENDMENTS TO THE
 STRUCTURAL PLANS SHALL BE SIGNED AND
 DATED BY THE ENGINEER OF RECORD.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-01-16 Cont ID  
Sent By sgraham Date 2002-12-17 Time 10:14 Rev Time 0.00
Received By rbrown Date 2003-01-16 Time 16:41 Sent To  
Notes
2003-01-16 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) FBC* 1804.2.2SUBMIT A GEOTECHNICAL
 REPORT.
  
 4) FBC* 104.1.1A SEPARATE PERMIT
 APPLICATION WILL BE REQUIRED FOR THE
 DUMPSTER ENCLOSURE.
  
 5) SUBMIT PRODUCT APPROVALS FOR THE
 EXTERIOR DOORS, WINDOWS AND ROOFING.
  
 6) FBC 13-103.1.2BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHITECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
 ***NOTE: ADD THE FULL STREET ADDRESS,
 2130 CENTREPARK DRIVE W, TO THE PROJECT
 INFORMATION SECTION OF EACH COPY OF THE
 COMPLIANCE FORM BEFORE RESUBMITTING.
  
 7) FBC 1004.1.4ARRANGEMENT OF EXITS.
 THE STRAIGHT LINE DISTANCE BETWEEN THE
 SECOND FLOOR EXIT DOORS SHALL NOT BE
 LESS THAN 1/2 THE LENGTH OF THE MAXIMUM
 DIAGONAL DIMENSION OF THE BUILDING,
 WHICH IS APPROX. 155 FT.AMEND THE
 PLANS TO ACHIEVE COMPLIANCE.
  
 8) FBC 11-4.1.3(9)AREAS OF RESCUE
 ASSISTANCE ARE REQUIRED BECAUSE THE
 BUILDING IS NOT SPRINKLERED.AMEND THE
 PLANS TO IDENTIFY LOCATIONS.ONE OPTION
 IS TO PROVIDE DETAILS TO SHOW THAT THE
 STAIR #2 LANDING AND THE ELEVATOR
 LOBBY #2, ADJACENT STAIR #1, COMPLY WITH
 THE REQUIREMENTS OF FBC 11-4.3.11.1.
 NOTE: IF STAIR #1 IS REVERSED, THEN THAT
 LANDING COULD BE USED INSTEAD OF HAVING
 TO UPGRADE THE ELEVATOR LOBBY TO MEET
 THE REQUIREMENTS FOR AN AREA OF RESCUE
 ASSISTANCE.
  
 9) FBC 4.3.11.3STAIRWAY WIDTH. AS PART
 OF THE REQUIREMENTS FOR AREAS OF RESCUE
 ASSISTANCE IN A NON-SPRINKLERED
 BUILDING, THE STAIRWAYS SHALL HAVE A
 CLEAR WIDTH OF 48" BETWEEN HANDRAILS.
  
 10) FBC 4.3.11.4TWO-WAY COMMUNICATION
 IS REQUIRED BETWEEN THE AREAS OF RESCUE
 ASSISTANCE AND THE PRIMARY ENTRANCE.
  
 11) FBC 705.1.2EXIT DOORS.THE DOORS
 TO THE STAIR #1 AND #2 ENCLOSURES AND TO
 THE FIRST FLOOR LOBBY (SHEET A.6DOOR
 SCHEDULE MARKS 2, 4 AND 19) ARE REQUIRED
 TO PROVIDE 1 HOUR FIRE RESISTANCE.
 AMEND THE DOOR SCHEDULE TO SHOW THIS
 REQUIREMENT.
  
 12) FBC 11-4.13.6 MANEUVERING CLEARANCES
 AT DOORS.THE LEADING EDGE OF THE DOORS
 TO 'OFFICE 4' (DOOR 9) AND 'BREAK 1'
 (DOOR 7) AND 'CUSTOMER AREA' (DOOR 7) ON
 THE FIRST FLOOR SHALL NOT BE LESS THAN
 18" FROM THE ADJACENT WALL ON THE PULL
 SIDE OF THE DOOR.
  
 13) FBC 11.4.9.4(2)SHEET A.4, TYPICAL
 STAIR DETAILS.THE STAIR HANDRAIL SHALL
 EXTEND AT LEAST 12" HORIZONTALLY BEYOND
 THE TOP RISER, AND SHALL CONTINUE TO
 SLOPE PAST THE BOTTOM RISER , FOR A
 DISTANCE EQUAL TO THE WIDTH OF ONE
 TREAD, AND THEN EXTEND A FURTHER 12"
 HORIZONTALLY AT THE BOTTOM.
  
 14) FBC 11-4.15DRINKING FOUNTAINS.
 THE ELEVATIONS ON SHEET A.7 DO NOT SHOW
 THE HEIGHT AND THE LEG CLEARANCES FOR
 DRINKING FOUNTAINS.AMEND/SUBMIT PLANS,
 FOR THE FIRST AND SECOND FLOOR DRINKING
 FOUNTAINS, TO DEMONSTRATE COMPLIANCE
 WITH THE REQUIREMENTS OF FIG. 27.
  
 15) FBC 11-4.16.3 & 4W.C. HEIGHT AND
 GRAB BARS.THE ELEVATIONS ON SHEET A.7
 DO NOT SHOW THE W.C. HEIGHT AND GRAB BAR
 PLACEMENT.AMEND/SUBMIT PLANS TO
 DEMONSTRATE COMPLIANCE WITH THE FIG. 29
 REQUIREMENTS FOR ACCESSIBLE W.C'S.
  
 16) SHEET A.5, FIRST FLOOR WINDOWS.THE
 NORTH END OF THE WEST ELEVATION SHOWS
 TWO FIRST FLOOR WINDOWS WHICH ARE NOT
 SHOWN ON THE FIRST FLOOR PLAN.
  
 17) SHEET S.6, SECTION 3, WOOD GABLE END
 TRUSS ANCHORING.FROM SIMPSON PRODUCT
 LITERATURE IT APPEARS THAT THE PROPOSED
 HUC26 ANCHORS MAY NOT HAVE SUFFICIENT
 CAPACITY FOR A 24 FT SPAN TRUSS WITH
 THIS TRIBUTARY WIDTH (APPROX. 1'-4" PLUS
 THE DEPTH OF THE PROFILE 3 PARAPET CAP).
 ADD THE CALCULATED UPLIFT TO THE PLANS
 FOR CROSS REFERENCE AGAINST THE PROPOSED
 ANCHOR.
  
 18) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2003-08-26 Cont ID  
Sent By csiegber Date 2003-11-03 Time 10:57 Rev Time 0.50
Received By dpalmer Date 2003-08-26 Time 19:05 Sent To  
Notes
2003-08-26 00:00:00REV FOR BLD OUT OK.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2003-08-05 Cont ID  
Sent By dpalmer Date 2003-08-05 Time 15:01 Rev Time 0.50
Received By dpalmer Date 2003-08-05 Time 15:01 Sent To  
Notes
2003-08-05 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE SEE NOTES FROM LAST
 REVIEW. PLEASE SEE THAT REVISED LOAD
 CALCULATIONS AND PANEL SCHEDULES HAVE
 NOT BEEN SUBMITTEDTO CORRELATE WITH
 NEW SCOPE OF WORK ADDED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-07-07 Cont ID  
Sent By alange Date 2003-07-28 Time 15:05 Rev Time 0.50
Received By dpalmer Date 2003-07-07 Time 07:04 Sent To  
Notes
2003-07-07 00:00:00*** NOTE ****
  
 SEE BLDG PLAN REVIEW NOTES, BLD OUT OF
 2ND FLOOR NOT ON ORIG VALUE/SCOPE.
  
 PLANS NEED TO BE REVISED TO INCLUDE ANY
 PANEL SCHEDULES TO CORRELATE WITH
 ELECTRICAL FLOOR PLAN SUBMITTED.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW
 BEFORE FINAL. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-03-13 Cont ID  
Sent By dpalmer Date 2003-03-13 Time 17:44 Rev Time 1.00
Received By dpalmer Date 2003-03-13 Time 17:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-12-26 Cont ID  
Sent By dpalmer Date 2002-12-26 Time 07:03 Rev Time 2.00
Received By dpalmer Date 2002-12-26 Time 07:03 Sent To  
Notes
2002-12-26 00:00:00**************** UNSAT **************
  
 1)NOTE:PLEASE SEE E2.1, SOME CIRCUITS
 MISSING CIRCUIT
 DESIGNATION.
  
 2)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 THAT WILL AHVE AN AFFECT ON ELECTRICAL
 SHEETS.
  
 3)NOTE: PLEASE NOTE/CLARIFY LTS FIXTURES
 IN ELEV /ELEC ROOMS TO MEET 700-16
  
  
  
  
  
  
  
  
  
  
  
 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPENT. 110-9/215-5
  
 7)NOTE: PLEASE SHOW SIZE OF METERCAN
 "H1A".?
  
 8)NOTE: PLEASE NOTE ALL CONTINUOUS LOADS
 ARE TO BE SHOWN AT 125%. 215-3/230-42 ET
 C.
  
 9)NOTE: PLEASE SEE WATER HEATER ON H2A
 2P-30A W/ #12`S, PLEASE SIZE WIRE PER
 310-16
  
 10)NOTE: PLEASE NOTE "L2B" IS REQ`D TO
 HAVE A MCB ON LOAD SIDE OF TRANSFORMER
 384-16,240-21
  
 11)NOTE: PLEASE SHOW MIN LOAD FOR
 FUTURE TENANT SPACE AND HOW LOAD WAS
 FIGURED.
  
 12)NOTE: PLEASE CLARIFY WHERE LPA PANEL
 SCHEDULE IS SHOWN?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2003-04-01 Cont ID  
Sent By mmclean Date 2003-04-01 Time 12:31 Rev Time 1.00
Received By mmclean Date   Time   Sent To  
Notes
2003-04-01 00:00:00PROVISO :
  
 BUILDING PERMIT ISSSUED BY L. MARTINEZ
 UNDER THE AGREEMENT WITH RON NETTLES
 THAT UNDERGROUND PERMIT WILL BE ISSUED
 BEFORE VERTICLE CONSTRUCTION
  
  
 L. MARTINEZ

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2003-03-03 Cont ID  
Sent By mamini Date 2003-03-03 Time 13:26 Rev Time 1.00
Received By mamini Date 2003-03-03 Time 13:26 Sent To  
Notes
2003-03-03 00:00:00FAILED:
 1. PLEASE NOTE THAT A SEPARATE PERMIT
 APPLICATION AND FEES FOR UNDERGROUND
 UTILITIES AND CIVIL SITE WORK IS
 REQUIRED, PLEASE SUBMIT TWO SETS OF
 CIVIL PLANS ONLY.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2003-01-16 Cont ID  
Sent By mamini Date 2003-01-16 Time 08:41 Rev Time 3.00
Received By mamini Date 2003-01-16 Time 08:41 Sent To  
Notes
2003-01-16 00:00:00FAILED:
 1. PLEASE NOTE THAT A SEPARATE PERMIT
 APPLICATION AND FEES FOR UNDERGROUND
 UTILITIES AND CIVIL SITE WORKS WILL BE
 REQUIRED.
 2. ALL BACKFLOW PREVENTERS MUST BE
 COMPLETELY HIDDEN FROM VIEW WITH SHRUBS
 PRIOR TO ACTIVATION.
 3. DRIVEWAYS APPROACHES MUST BE
 CONSTRUCTED AT MIN. PER THE CITY OF WPB
 STANDARD AND REQUIREMENT.
 4. POLLUTION/ EROSION PLANS MUST BE
 INSTALLED IN FIELD PRIOR TO ANY EARTH
 WORK/ CONSTRUCTION.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2003-09-02 Cont ID  
Sent By mcarsill Date 2003-09-02 Time 16:27 Rev Time 0.00
Received By mcarsill Date 2003-09-02 Time 16:27 Sent To  
Notes
2003-09-02 00:00:00APPROVED PROVISO
  
 ARE THE DOORS AT LOBBY 2B, 25 AND THE
 DOOR 18 AT THE EXECUTIVE SECRETARY AREA
 SWINGING IN THE RIGHT DIRECTION.
 REMEMBER IF 50 OR MORE PERSONS ARE
 EXPECTED TO USE THESE DOORS FOR EXIT
 ACCESS, THEN THEY SHOULD SWING IN THE
 DIRECTION OF EXIT TRAVEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-07-15 Cont ID  
Sent By alange Date 2003-08-21 Time 12:43 Rev Time 0.00
Received By nmccray Date 2003-07-15 Time 10:02 Sent To  
Notes
2003-07-15 00:00:00**************PROVISO*******************
 SEPARATE SHOP DRAWINGS AND PERMITS
 APPLICATIONS ARE REQUIRED FOR FIRE ALARM
 AND FIRE SPRINKLER SYSTEMS REVISION OR
 REMODEL.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-03-07 Cont ID  
Sent By mcarsill Date 2003-03-07 Time 09:26 Rev Time 0.00
Received By mcarsill Date 2003-03-07 Time 09:26 Sent To  
Notes
2003-03-07 00:00:00COULD NOT LOCATE NOTE 24 ON FAO.1.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-12-19 Cont ID  
Sent By mcarsill Date 2002-12-19 Time 09:11 Rev Time 0.00
Received By mcarsill Date 2002-12-19 Time 09:11 Sent To  
Notes
2002-12-19 00:00:001) THE PROPOSED FIRE HYDRANT IS TO MEET
 UTILITY AND FIRE RESCUE STANDARDS.
 TYPICALLY, THE CITY DOES NOT USE THE
 COLOR RED FOR FIRE HYDRANTS.
  
 2) ELECTRONIC SWITCHES WILL BE REQUIRED
 ON BACKFLOW DEVICES THAT CONTROL FIRE
 LINE SERVICE.
  
 3) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
  
 4) PLEASE PROVIDE A LIFE SAFETY PLAN
 INDICATING OCCUPANT LOADS AND TRAVEL
 DISTANCES. ALSO PLEASE DEMONSTRATE
 COMPLIANCE WITH EXIT SEPARATION
 REQUIREMENTS OF AT LEAST 1/2 THE
 DIAGONAL DISTANCE SINCE NO FIRE
 SPRINKLER SYSTEM IS PLANNED.
  
 5) A REMOTE FIRE ALARM ANNUNCIATOR
 APPEARS TO BE REQUIRED AT THE FRONT
 ENTRYWAY.
  
 6) SINCE NO FIRE SPRINKLERS ARE PLANNED,
 ALL ELECTRICAL,MECHANICAL, AND STORAGE
 ROOMS ARE TO BE AT LEAST ONE HOUR
 FIRE RATED WITH RATED OPENING
 PROTECTIVE DEVICES.
  
 7) AN EXIT SIGN IS MISSING INFRONT OF
 STAIR # 2, FIRST FLOOR.
  
 8) A KNOX-BOX WILL BE REQUIRED FOR
 THE BUILDING.
  
 9) NO BUILDING ELEVATION DRAWINGS
 PROVIDED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-11-03 Cont ID  
Sent By csiegber Date 2003-11-03 Time 10:56 Rev Time 0.00
Received By csiegber Date 2003-11-03 Time 10:56 Sent To E
Notes
2003-11-03 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-08-21 Cont ID  
Sent By alange Date 2003-08-21 Time 12:43 Rev Time 0.00
Received By alange Date 2003-08-21 Time 12:42 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-08-14 Cont ID  
Sent By dbaxter Date 2003-08-14 Time 16:43 Rev Time 0.00
Received By dbaxter Date 2003-08-14 Time 16:43 Sent To  
Notes
2003-08-14 00:00:00TO COMM BD. #20

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-08-05 Cont ID  
Sent By alange Date 2003-07-28 Time 15:05 Rev Time 0.00
Received By alange Date 2003-07-28 Time 15:05 Sent To  
Notes
2003-07-28 00:00:00TO COMM BD #14

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-06-17 Cont ID  
Sent By shernand Date 2003-06-17 Time 16:30 Rev Time 0.00
Received By shernand Date 2003-06-17 Time 16:30 Sent To  
Notes
2003-06-17 00:00:00COMM BOARD #49

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-12-18 Cont ID  
Sent By btrobaug Date 2002-12-18 Time 09:32 Rev Time 0.00
Received By btrobaug Date 2002-12-17 Time 09:32 Sent To  
Notes
2002-12-18 00:00:00TO COM BOARD #37./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-03 Cont ID  
Sent By btrobaug Date 2002-12-03 Time 16:55 Rev Time 0.00
Received By btrobaug Date 2002-12-03 Time 16:55 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2003-08-29 Cont ID  
Sent By pkrauss Date 2003-08-29 Time 10:49 Rev Time 0.30
Received By pkrauss Date 2003-08-29 Time 10:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-07-08 Cont ID  
Sent By pkrauss Date 2003-07-08 Time 07:19 Rev Time 0.40
Received By pkrauss Date 2003-07-08 Time 07:09 Sent To  
Notes
2003-07-08 00:00:00PROVISO:
  
 PLAN SHEET M2.2, THE WALL BETWEEN THE
 BREAK ROOM AND STORAGE ROOM HAS A 1 HR
 RATING, AS PER 2001 FBC(M) 607.1.3
 EXCEPTIONS - FIRE DAMPERS ARE NOT
 REQUIRED UNDER THE FOLLOWING CONDITIONS:
 #3 ITEMS 1 THROUGH 4 AS FOLLOWS
 1. DUCTS DO NOT EXCEED 100 SQ INCHES
 2. DUCT SHALL BE A MINIMUM OF .0217 INCH
 STEEL
 3. DUCT SHALL CONTINUE WITH NO DUCT
 OPENINGS FOR NOT LESS THAN 5 FT FROM
 THE RATED WALL
 4. THE DUCT SHALL BE ISNTALLED ABOVE THE
 CEILING
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-03-14 Cont ID  
Sent By pkrauss Date 2003-03-14 Time 08:01 Rev Time 0.55
Received By pkrauss Date 2003-03-10 Time 13:53 Sent To  
Notes
2003-03-14 00:00:00MECHANICAL PERMIT 02120134 - PROVISO
 ON PLAN

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-12-28 Cont ID  
Sent By pkrauss Date 2002-12-27 Time 13:37 Rev Time 1.45
Received By hmoser Date 2002-12-27 Time 11:59 Sent To  
Notes
2002-12-28 00:00:003.NO DUCT SIZE OR SCHEDULE FOR
 FLEX DUCT
2002-12-27 00:00:00DENIED:
  
 1.PROVIDE DETAIL FOR FIRE DAMPER IN A
 HORIZONTAL APPLICATION.
  
 2.PLEASE CLARIFY NOTE 1 ON PLAN SHEET
 M2-3, "SHAFT RISER" REF. M6.1, ARE DUCTS
 IN A 1 HR SHAFT?

Review Stop P PLUMBING
Rev No 5 Status P Date 2003-09-03 Cont ID  
Sent By kstevens Date 2003-09-03 Time 16:31 Rev Time 0.33
Received By kstevens Date 2003-09-03 Time 16:31 Sent To  
Notes
2003-09-03 00:00:00REVISION OK - SANT. RISER DIAGRAM/WATER
 RISER DIAGRAM.

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-07-02 Cont ID  
Sent By kstevens Date 2003-07-02 Time 16:11 Rev Time 1.50
Received By kstevens Date 2003-07-02 Time 14:36 Sent To  
Notes
2003-07-02 00:00:00REVISION OK - FUTURE TENANT BUILD-OUT ON
 SECOND FLOOR - SANT. AND WATER RISER
 DIAGRAMS SHALL BE REVISED TO REFLECT
 CHANGES ON SHTS P2.2 & P3.2

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-03-22 Cont ID  
Sent By kstevens Date 2003-03-22 Time 15:42 Rev Time 0.20
Received By kstevens Date 2003-03-22 Time 15:41 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-03-20 Cont ID  
Sent By kstevens Date 2003-03-20 Time 11:47 Rev Time 1.00
Received By kstevens Date 2003-03-20 Time 11:47 Sent To  
Notes
2003-03-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEW, SHT PO.1 THERM-
 AL EXPANSION CONTROL REQUIRED PER SEC.
 607.3.2. PLEASE SHOW ON W/H'S #1 & #2.
 SHEETS WERE NOT CHANGED.
 2) FROM PREVIOUS REVIEW, SHT P6.1 WATER
 RISER DIAGRAM, WATER HAMMER ARRESTORS
 REQUIRED BY SEC 604.9 SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE RANGE
 NOT AT THE TOP OF DROPS IN THE CEILING
 AS SHOWN. PDI-WH 201 AND MANUF. INSTALL-
 ATION INSTRUCTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-12-31 Cont ID  
Sent By kstevens Date 2002-12-30 Time 16:11 Rev Time 1.50
Received By kstevens Date 2002-12-30 Time 16:10 Sent To  
Notes
2002-12-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) STH A.7 PRIVATE TOILET ROOM FOR EXEC.
 SHALL BE ADAPTABLE PER 11-4.1.3(11).
 SHOW DETAIL FOR GRAB BAR BACKING, OPEN-
 ING FOR W/C, LAV HEIGHT (34") ECT.
 2) SHT A.9 BREAK ROOM ELEVATIONS #'S 1 &
 2. SINKS SHALL COMPLY WITH 11-4.24 AND
 ALL SUBSECTIONS. PLEASE SHOW DETAILS.
 3) SHT P0.1 THERMAL EXPANSION CONTROL
 REQUIRED PER SEC 607.3.2. PLEASE SHOW
 ON WATER HEATER DETAIL EWH #1 & EWH #2.
 4) SHT P2.1 - RELIEF VENT REQUIRED ON
 CONDENSATE LINE AS IT EXITS BLDG.
 5) SHT P6.1 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS REQUIRED BY 604.9 SHALL
 BE LOCATED NEAR THE FIXTURES IN AN
 "EFFICTIVE RANGE" NOT AT TOP OF DROPS IN
 CEILING AS SHOWN.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-12-17 Cont ID  
Sent By btrobaug Date 2002-12-03 Time 16:56 Rev Time 0.25
Received By sgraham Date   Time   Sent To B
Notes
***NONE***