Plan Review Details - Permit 02120009
Plan Review Stops For Permit 02120009
Review Stop E ELECTRICAL
Rev No 5 Status P Date 2003-09-09 Cont ID  
Sent By dpalmer Date 2003-09-09 Time 11:59 Rev Time 1.00
Received By dpalmer Date 2003-09-09 Time 11:59 Sent To  
Notes
2003-09-09 00:00:00OCP FOR A/C COND UNITS TO BE VERIFIED
 IN FIELD ALONG WITH MIN CIRCUIT AMPACITY
 ELEC CONT SUBMITTED INFORMATION OVER THE
 PHONE THAT MIN A'SON UNITS ARE 20 AND 25
 A'S.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-08-22 Cont ID  
Sent By dpalmer Date 2003-08-22 Time 11:17 Rev Time 0.50
Received By dpalmer Date 2003-08-22 Time 11:17 Sent To  
Notes
2003-08-22 00:00:00************PROVISO/NOTE **********
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND ALL PANELS. A/C SUB PANEL NOT SHOWN
 ON RISER.
  
 2)NOTE: PLEASE SHOW CONDUITS FROM METER
 TO PANELS AS INSTALLED IN SLAB.
 210.70
  
 3)NOTE: PLEASE VERIFY KW RATINGS FOR
 AHU'S, SHOWS 5KW UNIT ON 2P60A? IF 10KW
 UNIT, REVISE LOAD CALCUALTIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE FINAL ELEC/CO. PARTIAL
 FINAL ELECTRICAL IS OK.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-06-16 Cont ID  
Sent By dpalmer Date 2003-06-16 Time 15:30 Rev Time 0.25
Received By dpalmer Date 2003-06-16 Time 15:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-01-23 Cont ID  
Sent By shernand Date 2003-06-13 Time 16:05 Rev Time 0.55
Received By btrobaug Date   Time   Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-01-03 Cont ID  
Sent By btrobaug Date 2003-01-03 Time 12:06 Rev Time 0.75
Received By btrobaug Date 2003-01-03 Time 11:29 Sent To P
Notes
2003-01-03 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THE FOLLOWING DISCREPANCIES
 MAKE ANY NECESSARY CORRECTIONS ON THE
 PLANS AND RESUBMIT FOR REVIEW.
  
 1} THE DISCONNECT ON THE RISER DIAGRAM
 IS 300 AMPS,BEING FED WITH #2/0(200AMP)
 CONDUCTORS. THE LOAD CALCULATION IS IN
 EXCESS OF 200 AMPS. PLEASE CORRELATE
 OCP,CONDUCTORS,LOAD CALCULATION AND
 EQUIPMENT GROUND TO REFLECT WHAT IS TO
 BE INSTALLED.
  
 2} THE CABANA BATH NEEDS A RECEPTACLE TO
 COMPLY WITH 210-11(C)(3),MUST BE GFI.
  
 3} MASTER & BATH #2 NEEDS A RECEPTACLE
 ADDED TO COMPLY WITH 210-52(D).
  
 4} BEDROOM #5 NEEDS TO HAVE SMOKE
 DETECTORS TO COMPLY 8-1.4.1.6.2(1) &
 (2).
  
 5} AHU & WATER HEATER DISCONNECTS IN THE
 GARAGE MUST COMPLY WITH 110-26.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-13 Cont ID  
Sent By shernand Date 2003-06-13 Time 16:03 Rev Time 0.00
Received By shernand Date 2003-06-13 Time 16:03 Sent To E
Notes
2003-06-13 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-02 Cont ID  
Sent By btrobaug Date 2002-12-02 Time 17:03 Rev Time 0.00
Received By btrobaug Date 2002-12-02 Time 17:03 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-01-30 Cont ID  
Sent By pkrauss Date 2003-01-30 Time 10:20 Rev Time 0.40
Received By pkrauss Date 2003-01-30 Time 10:20 Sent To  
Notes
2003-01-30 00:00:00MECHANICAL 02120027

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-01-11 Cont ID  
Sent By btrobaug Date 2003-01-23 Time 09:34 Rev Time 0.50
Received By hmoser Date 2003-01-11 Time 06:45 Sent To R
Notes
2003-01-11 00:00:00PLAN DENIED
 ENERGY CALCULATIONS AND MANUAL (J) DO
 NOT MATCH
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8221

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-08-12 Cont ID  
Sent By kstevens Date 2003-08-12 Time 14:30 Rev Time 0.50
Received By kstevens Date 2003-08-12 Time 14:30 Sent To  
Notes
2003-08-12 00:00:00REVISION OK - SANT. RISER DIAGRAM

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-01-11 Cont ID  
Sent By btrobaug Date 2003-01-03 Time 12:06 Rev Time 0.33
Received By jleech Date 2003-01-11 Time 06:29 Sent To M
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2003-01-30 Cont ID  
Sent By hmoser Date 2003-01-11 Time 06:45 Rev Time 0.10
Received By pkrauss Date 2003-01-30 Time 10:26 Sent To  
Notes
2003-01-30 00:00:00LOU HATTEN SIGNED OFF ON PLAN/DID NOT
 SIGN OFF IN COMPUTER.PLANS OKAY
 PER LOU HATTEN

Review Stop Z ZONING
Rev No 1 Status P Date 2003-01-02 Cont ID  
Sent By btrobaug Date 2002-12-02 Time 17:03 Rev Time 0.00
Received By sgraham Date   Time   Sent To P
Notes
***NONE***