2003-01-07 00:00:00 | |
| BUILDING PLAN REVIEW |
| PERMIT: 02111908 |
| ADD: 1805 OKEECHOBEE ROAD |
| CONT:GLOBAL CONSTRUCTION |
| TEL: (954)971-9500 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1) THE CORRECT ADDRESS FOR THIS BUILDING |
| IS 1805 OKEECHOBEE ROAD, THERE IS NO |
| OLD OKEECHOBEE RD IN THE CITY, THIS IS |
| NAME OF THE SAME ROAD LOCATED IN THE |
| COUNTY. IF GIVEN THIS TO 911 RESPONCE |
| THEY MAY RESPOND IN THE COUNTY! |
| |
| 2) 105.3 ADMINISTRATIVE CODE- RESIDENT |
| INSPECTOR PROGRAM REQUIRED. (5) FOR |
| BUILDINGS GREATER THAN 20,000 SQ FT. |
| CONTACT DON NEELY DIRECTOR OF RESIDENT |
| INSPECTOR PROGRAM. |
| WHEN SUBMITTING DOCUMENTS FOR PUBLIC |
| RECORD, 3 DOCUMENTS WILL BE REQUIRED. |
| PLANS, ENGINEERING REPORTS, PRODUCT |
| APPROVALS, SHOP DRAWINGS OR SUBMITTALS, |
| ETC... |
| |
| 3) PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| 4) FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| |
| |
| 5) SITE STATISTICS: COMMENT: 503.4 VS |
| TABLE 600. 503.4 UNLIMITED AREA WHEN AN |
| AUTOMATIC EXTINGUISHING SYSTEM IS USED |
| & ACCOMPANIED BY 60' OPEN SPACE AROUND |
| BUILDING, THIS BUILDING DOESN'T QUALIFY |
| UNDER THE 60' OPEN SPACE. THE BUILDING |
| FRONTAGE CAN ONLY BE TAKEN TO THE CENTER |
| LINE OF THE ROAD! |
| TABLE 500 FOR A TYPE IV BLDG. 1HR. |
| PRO. FULLY SPRINKLERED DOES QUALIFY THE |
| BLDG TO : |
| A) FACTORY/ INDUSTRIAL94,500 SQ FT |
| B) STORAGE 72,000 W/ AREA INCREASES |
| 100% UNSPR AREA= 96,000 SQ FT. |
| |
| THE PLANS HAVE NO INFORMATION FOR THE |
| FIRE SPRINKLER SYSTEM, IS THERE GOING TO |
| BE ONE? PLEASE PROVIDE ADD INFORMATION. |
| FIRE SPRINKLER PLANS TO BE ENGINEERED, |
| SIGNED,SEALED & DATED. 3 SETS PRIOR TO |
| ISSUANCE OF THIS PERMIT. 903.1. |
| |
| 6)11-4.1.3(1) AT LEAST ONE ACCESSIBLE |
| ROUTTE COMPLYING WITH 11-4.3 SHALL |
| CONNECT ACCESSIBLE BUILDING OR FACILITY |
| ENETRANCES WITH ALL ACCESSIBLE SPACES |
| AND ELEMENTS WITHIN THE BUILDING OR |
| FACILITY. |
| PLANS INDICATE MULTIPLE TENANTS SUCH |
| AS 1873, 1877, 1889 & 1893 WITHOUT |
| ACCESSIBLE ENTRANCES? |
| |
| 7) 1007.5.5 HANDRAILS SHALL EXTEND @ |
| LEAST 12" HORIZONTALLY BEYOND THE TOP |
| RISER OF A FLIGHT OF STAIRS. SEE A-10, |
| DETAIL 3. |
| |
| 8) SHEET A-9 DETAIL 2 CURRENTLY MEETS |
| CODE SINCE IT IS NOT A REQUIRED MEANS OF |
| EGRESS. IF AT TENANT FIT UP THIS IS THE |
| ONLY MEANS OF EGRESS THEN THE EXCEPTION |
| #1 WILL NOT COMPLY. |
| |
| 9) PLEASE PROVIDE DETAILS FOR 1 HR RAT- |
| ING FOR BEAMS, GIRDERS, ROOF FRAMING |
| (BAR JOIST) TABLE 600- 1 HR PROTECTED. |
| |
| 10) FIRE DISTRICT 102.2.4 ROOF COVERINGS |
| MUST BE A "A OR B" ROOF COVERING SUMIT |
| MANUFACTURES SPEC. |
| |
| 11)1606.1.4(1) IN WIND BORNE DEBRIS |
| REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| ASSUMED TO BE OPENINGS UNLESS SUCH |
| GLAZING IS IMPACT RESISTANT OR PROTECTED |
| WITH AN IMPACT RESISTANT COVERING MEET- |
| ING THE REQUIREMENTS OF SSTD 12, ASTM |
| E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| 1) GLAZED OPENINGS LOCATED WITHIN 30 FT |
| OF GRADE SHALL MEET THE REQUIREMENTS OF |
| LARGE MISSLE TEST. |
| |
| 12)FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORT, SBCCI OR DADE COUNTY |
| REPORT ARE ACCEPTED. MISSING REPORTS: |
| A) SWING DOORS, GLAZED, SOLID & LOUVERS |
| B) OVERHEAD GARAGE DOORS |
| C) WINDOWS |
| D) VERTICAL & HORIZONTAL MULLIONS |
| E) ROOFING ASSEMBLIES |
| F) SKYLIGHTS |
| |
| 13)1707.4.3 EACH EXTERIOR DOOR |
| ASSEMBLY NOT COVERED BY 1707.4.2 |
| (GLAZED DOORS) SHALL BE LISTED AND TEST- |
| ED FOR A PERIOD EQUAL TO THE QUANITY |
| 3600/ V WHERE THE TIME PERIOD IS IN |
| SECTIONS AND V IS IN MILES PER HR TAKEN |
| FROM FIGURE 1606. THE TIME PERIOD SHALL |
| ALSO INCLUDE A 10 SECOND PERIOD AT A |
| LOAD EQUAL TO 1.5 TIMES THE DESIGN |
| PRESSURE. DADE COUNTY & SBCCI REPORTS |
| ARE ACCEPTED. |
| |
| 13) 1707.4.5.1 MULLIONS OCCURRING |
| BETWEEN INDIVIDUAL WINDOW AND GLASS |
| DOOR ASSEMBLIES. TESTING REPORTS ARE |
| REQUIRED BY AN APPROVED TESTING |
| LABORATORY OR BE ENGINEERED. |
| |
| 14) 1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| TO THE ROUGH OPENING SUBTRATE. |
| |
| 15)PROVIDE STORM PANEL INFORMATION WITH |
| INSTALLATION SCHEDULE AND KEY PLAN WITH |
| SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| FOR ALL NON-IMPACT GLAZING. |
| FBC 1606.1.4. |
| |
| 16)FL BLD CODE 2001 SECTION 103.6, |
| 1606.1.4, 1707.4 & 3401.7.2.4. |
| PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| SCHEDULE SUMMARIZING & IDENTIFYING |
| OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| BAR REINFORCING REQUIREMENTS, WALL PRES- |
| SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| SUBMITTED AT TIME OF PERMIT APPLICATION |
| TO FACILITATE PLAN REVIEW AND PERMIT |
| ISSUANCE. |
| |
| 17) 103.6 COUNTY ADMINISTRATIVE CODE: |
| 1606.1.4 & 1707.1.4, CITY STANDARD(13) |
| IN ORDER TO ASSURE THE SECURING OF SHUT- |
| TERS ON LARGE BUILDINGS, A PRE-STORM |
| PREPARATION PLANS MUST BE SUBMITTED BY |
| THE PROPERTY OWNER OR MANAGING AGENTS |
| FOR REVIEW BY THE CONSTRUCTION SERVICES |
| DEPARTMENT. ANY SUCH PLAN SHALL INCLUDE |
| AT A MINIMUM, ON SITE LOCATION FOR |
| STORM SHUTTERS, PARTY RESPONSIBLE FOR |
| THE SECURING THE SHUTTERS (SAID PARTIES |
| MUST BE LOCATED IN PALM BEACH COUNTY), |
| TOTAL NUMBER OF OPENINGS TO BE PROTECTED |
| AND THE TOTAL TIME REQUIRED TO SECURE |
| ALL OPENINGS. PROTECTION OF OPENINGS |
| SHALL BE ACCOMPLISHED WITHIN 12 HRS. |
| OR LESS OF THE OFFICIAL NOTIFICATION BY |
| THE NATIONAL WEATHER SERVICE OF A |
| HURRICANE WATCH. |
| |
| 18) 1504.1 ROOFING: INSULATION/ FASTEN- |
| ING SCHEDULE WILL REQUIRE WINDLOADS/ |
| WIND REISTANCE TESTING FOR WIND ZONE. |
| |
| 19) STRUCTURAL STEEL SHOP DRAWINGS ARE |
| TO BE REVIEWED BY THE ENGINEER OF RECORD |
| BEFORE THE SUBMITTAL TO THE BUILDING |
| DEPARTMENT. |
| |
| 20) FL BLDG 1909.3 (EXEPTION# 2) |
| CONCRETE SLABS ON GRADE CONTAINING 6X6/ |
| W1.4XW1.4 WELDED WIRE REINFORCEMENT |
| FABRIC LOCATED IN THE MIDDLE TO THE |
| UPPER 1/3RD OF THE SLAB SHALL BE SUP- |
| PORTED BY APPROVED MATERIALS OR SUPPORTS |
| AT SPACING NOT TO EXCEED 3 FT OR IN |
| ACCORDANCE WITH MANUFACTURER'S SPEC. |
| |
| 21)2504.2.2 INSTALLATION OF EXTERIOR |
| LATHING AND FRAMING SHALL COMPLY WITH |
| ASTM C-1063. |
| |
| 22)BEFORE A PERMIT TO CONSTRUCT, MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| DESCRIPTION OF THE REVISION MADE, IDEN- |
| TIFYING THE SHEET OR SPECIFICATION PAGE |
| WHERE THE CHANGES CAN BE FOUND, WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| FOR YOUR ANTICIPATED COOPERATION. |
| JIM WITMER |
| PLAN REVIEW |
| TEL: (561)659-8096 EX.8412 |
| FAX: (561)659-8026 |