Plan Review Details - Permit 02111907
Plan Review Stops For Permit 02111907
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2003-06-03 Cont ID  
Sent By jwitmer Date 2003-06-03 Time 10:04 Rev Time 0.55
Received By jwitmer Date   Time   Sent To  
Notes
2003-06-03 00:00:00INTERIOR OFFICE REVISION OK6/3/03

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-05-22 Cont ID  
Sent By jwitmer Date 2003-05-22 Time 11:51 Rev Time 0.50
Received By jwitmer Date 2003-05-22 Time 11:51 Sent To  
Notes
2003-05-22 00:00:00REVISION: RAMP OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-05-08 Cont ID  
Sent By bstaples Date 2003-05-08 Time 14:16 Rev Time 0.77
Received By jwitmer Date   Time   Sent To  
Notes
2003-05-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02111907
 ADD:1701 OKEECHOBEE RD STE 1743
 CONT:GLOBAL CONSTRUCTION
 CONTACT : GARY TALTON
 TEL: (561)351-4134
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 *****BUILDING PROVISO*******
 1) THE AREA ABOVE "THE AREA OF REFUGE"
 SIGN INDICATING "NOT TO BE USED AS A
 STORAGE AREA"!!!! NOT INTENDED FOR THAT
 USE, THE MINIMUM LOADING WOULD HAVE TO
 BE 125 LBS.
 ******OR*******
 IF THIS AREA IS ENTENDED FOR STORAGE:
 106.4.2 STORAGE & FACTORY- INDUS-
 TRIAL OCCUPANCIES. IT SHALL BE THE
 RESPONSIBILITY OF THE OWNER, AGENT,
 PROPIETOR OR OCCUPANT OF GROUP S AND
 GROUP F OCCUPANCIES, OR ANY OCCUPANCY
 WHERE EXCESSIVE FLOOR LOADING IS LIKELY
 TO OCCUR, TO EMPLOY A COMPETENT ARCHI-
 TECT OR ENGINEER IN COMPUTING THE SAFE
 FLOOR LOAD CAPACITY. ALL SUCH COMPUTA-
 TIONS SHALL BE ACCOMPANIED BY AN AFFA-
 DAVIT FROM THE ARCHITECT OR ENGINEER
 STATING THE SAFE ALLOWABLE FLOOR LOADS
 ON EACH FLOOR IN POUNDS PER SQ FT.THE
 COMPUTATIONS & AFFADAVIT SHALL BE FILED
 AS A PERMANENT RECORD OF THE BLDG DEPT.
  
 106.4.3.SIGNS REQUIRED. IN EVERY
 BUILDING OR PART OF A BUILDING USED FOR
 STORAGE, INDUSTRIAL OR HAZARDOUS PUR-
 POSES, THE SAFE FLOOR LOADS, AS REVIEWED
 BY THE BUILDING OFFICIAL ON THE PLAN,
 SHALL BE MARKED ON PLATES OF APPROVED DE
 SIGN WHICH SHALL BE SUPPLIED & SECURELY
 AFFIXED BY THE OWNER OF THE BUILDING IN
 A CONSPICUOUS PLACE IN EACH STORY TO
 WHICH THEY RELATE. SUCH PLATES SHALL NOT
 BE REMOVEDOR DEFACED, & IF LOST,
 REMOVED THE OWNER OF THE BUILDING SHALL
 REPLACE THEM.
  
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-04-29 Cont ID  
Sent By jwitmer Date 2003-04-29 Time 12:51 Rev Time 0.75
Received By jwitmer Date 2003-04-29 Time 12:29 Sent To  
Notes
2003-04-29 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02111907
 ADD: 1701 OKEECHOBEE RD
 CONT:(PLAN REVIEW)
 GLOBAL CONSTRUCTION ASSOC
 TEL: (954)971-9500
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) 11.4.1.3 ACCESSIBLE BUILDINGS:
 NEW CONSTRUCTION,(9) IN BUILDINGS OR FAC
 ILITIES, OR PORTIONS OF BUILDINGS OR FAC
 ILITIES, REQUIRED TO BE ACCESSIBLE,
 ACCESSIBLE MEANS OF EGRESS SHALL BE PROV
 IDED IN THE SAME NUMBER AS REQUIRED FOR
 EXITS BY THE LOCAL BUILDING / LIFE
 SAFETY REGULATIONS. WHERE A REQUIRED
 EXIT FROM AN OCCUPIABLE LEVEL ABOVE OR B
 ELOW A LEVEL OF ACCESSIBLE EXIT DIS-
 CHARGE IS NOT ACCESSIBLE, AN AREA OF RES
 CUE ASSISTANCE SHALL BE PROVIDED ON EACH
 LEVEL ( IN A NUMBER EQUAL TO THAT OF INA
 CCESSIBLE REQUIRED EXITS).
 15,500 SF OPEN TO PUBLIC/60 MERCANTILE=
 258 OCC LOAD.
  
 1004.1.2 REQUIRES (2) REMOTE MEANS OF
 EGRESS, SINCE THE BACK EGRESS DOORS ARE
 NOT ACCESSIBLE THEY WILL REQUIRE AN AREA
 OF RESCUE ASSISTANCE COMPLYING WITH
 11-4.3.11
 1.LOCATION & CONSTRUCTION (5)
 2.SIZE
 3.STAIRWAY WIDTH
 4.TWO WAY COMMUNICATION
 5.IDENIFICATION
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-01-06 Cont ID  
Sent By jwitmer Date 2003-01-06 Time 07:11 Rev Time 3.25
Received By jwitmer Date 2003-01-03 Time 14:56 Sent To  
Notes
2003-01-06 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02111907
 ADD: 1701 OKEECHOBEE ROAD
 CONT: GLOBAL CONSTRUCTION ASSOC
 TEL: (954)971-9500
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) PERMIT APPLICATION HAS THE ADDRESS
 FOR BUILDING # 2 THAT IS NOT BUILT.
  
 SITE ADDRESS;
 1801 OKEECHOBEE ROAD
  
 BUILDING # 1;
 1701 OKEECHOBEE ROAD
 THE TENANT (SUITE #) TO BE BETWEEN 1701
 AND 1803.THE CITY MASTER STREET GUIDE
 DOES NOT HAVE LISTED A OLD OKEECHOBEE
 ROAD. THE CITY NAME FOR THIS STREET IS
 "OKEECHOBEE ROAD". WHEN YOU CROSS INTO
 THE COUNTY UNINCORPORATED AREAS THE
 STREET NAME IN THE COUNTY IS "OLD OKEE-
 CHOBEE ROAD".
  
 2)MEANS OF EGRESS: A CONTINUOUS AND
 UNOBSTRUCTED WAY OF TRAVEL FROM ANY
 POINT IN A BUILDING OR STRUCTURE TO A
 PUBLIC WAY, CONSISTING OF THREE SEPERATE
 AND DISTINCT PARTS: (1) THE WAY OF THE
 EXIT ACCESS, (2) THE EXIT, AND (3) THE
 THE WAY OF OF THE EXIT DISCHARGE.
 A MEANS OF EGRESS COMPRISES THE VERTICAL
 AND HORIZONTAL WAYS OF TRAVEL AND
 INCLUDE THE INTERVENING ROOM SPACE,DOORS
 CORRIDORS,PASSAGEWAYS,BALCONIES, STAIRS,
 RAMPS, ENCLOSURES, LOBBIES, HORIZONTAL
 EXITS, COURTS AND YARDS.1001.1.3
 THE PLAN INDICATES THE BUSINESS OCCUPAN-
 CY HAVING TO EXIT THROUGH THE WAREHOUSE
 CLASSIFIED AS S2 STORAGE. THE CODE DOES
 ALLOW FOR RETAIL TO EXIT THROUGH A STOR-
 AGE ROOM WELL MARKED BUT NOT THROUGH A
 S2 WAREHOSE WITHOUT 2 HR SEPERATION!
  
 3)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2003-06-09 Cont ID  
Sent By dpalmer Date 2003-06-09 Time 06:41 Rev Time 0.33
Received By dpalmer Date 2003-06-09 Time 06:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-05-07 Cont ID  
Sent By dpalmer Date 2003-05-07 Time 09:50 Rev Time 0.25
Received By dpalmer Date 2003-05-07 Time 09:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-05-06 Cont ID  
Sent By dpalmer Date 2003-05-06 Time 07:36 Rev Time 0.50
Received By dpalmer Date 2003-05-06 Time 07:36 Sent To  
Notes
2003-05-06 00:00:00************ UNSAT *************
  
 RESUB HAS NO ORIG PACKAGE, PERMIT APPL-
 -CATION ETC.
  
 PLEASE RESUB W. ORIG PACKAGE, TAKE OUT
 OLD SHEETS AND INSERT NEW SHEETS TO
 MAKE TWO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE SUBMIT FOR REVIEW AT THAT TIME.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-04-28 Cont ID  
Sent By dpalmer Date 2003-04-28 Time 11:18 Rev Time 0.50
Received By dpalmer Date 2003-04-28 Time 11:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-12-06 Cont ID  
Sent By dpalmer Date 2002-12-05 Time 0546 Rev Time 1.00
Received By dpalmer Date 2002-12-05 Time 15:07 Sent To  
Notes
2002-12-05 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE CLARIFY DIRECTION OF
 PANELS. PANELS SEEM TO BE FACING RM
 112 AND NOT IN THE SAME LOCATION OF
 TRANSFORMER?
  
 2)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN PANEL "H1"
 TRANSFORMER AND PANELS "L1 AND "L".
 250-122/250-24/250-30
 PLEASE ALSO SHOW EQUIPMENT GROUNDING
 MEANS BETWEEN
  
 3)NOTE: PLEASE CLARIFY/ NEW OR EXSITNG
 SHOW WINDOW RECEPTS PER 210-62
  
 4)NOTE: PLEASE CLARIFY CIRCUITING FOR
 EM LT/ EXT LTS SHOWN PER 700-12E.
  
 PLEASE SUBMIT THE ABOVE INFOMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-06-18 Cont ID  
Sent By nmccray Date 2003-06-18 Time 11:38 Rev Time 0.00
Received By nmccray Date 2003-06-18 Time 11:38 Sent To  
Notes
2003-06-18 00:00:00************PROVISO*********************
 SEPARATE "SHOP DRAWING" AND PERMIT
 APPLICATION IS REQUIRED FOR FIRE ALARM
 SYSTEM REMODEL.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-04-25 Cont ID  
Sent By mcarsill Date 2003-04-25 Time 12:52 Rev Time 0.00
Received By mcarsill Date 2003-04-25 Time 12:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-12-12 Cont ID  
Sent By mcarsill Date 2002-12-12 Time 13:33 Rev Time 0.00
Received By mcarsill Date 2002-12-12 Time 13:33 Sent To  
Notes
2002-12-12 00:00:001) IT APPEARS THAT SOME EXIT ACCESS
 OCCURS WITHIN SPACE 130 FROM THE
 OFFICES. IS IT NOT TRUE THAT SPACE 130
 CAN BE CONSIDERED MORE HAZARDOUS THAN
 THE OFFICE AREA. PLEASE SEE NFPA 101,
 THE LIFE SAFETY CODE, 2000 EDITION,
 SECTION 7.5.2.1, IMPEDIMENTS TO EXITS.
  
 2) SEPARATE PLANS AND PERMITS
 REQUIRED FOR THE PLANNED REMODEL OF
 THE FIRE ALARM SYSTEM.
  
 3) NO FIRE SPRINKLER SYSTEM DRAWINGS
 AS NOTED ON TITLE PAGE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-05-28 Cont ID  
Sent By shernand Date 2003-05-28 Time 13:44 Rev Time 0.00
Received By shernand Date 2003-05-28 Time 13:44 Sent To  
Notes
2003-05-28 00:00:00COMM BOARD #61

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-05-02 Cont ID  
Sent By shernand Date 2003-05-02 Time 17:35 Rev Time 0.00
Received By shernand Date 2003-05-02 Time 17:35 Sent To  
Notes
2003-05-02 00:00:00COMM BOARD #7

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-16 Cont ID  
Sent By shernand Date 2003-04-16 Time 10:21 Rev Time 0.00
Received By shernand Date 2003-04-16 Time 10:21 Sent To  
Notes
2003-04-16 00:00:00COMM BOARD #27

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-02 Cont ID  
Sent By btrobaug Date 2002-12-02 Time 08:22 Rev Time 0.00
Received By btrobaug Date 2002-11-27 Time 08:22 Sent To  
Notes
2002-12-02 00:00:00TO COMM BOARD #5./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-06-18 Cont ID  
Sent By pkrauss Date 2003-06-18 Time 09:56 Rev Time 0.30
Received By pkrauss Date 2003-06-18 Time 09:56 Sent To  
Notes
2003-06-18 00:00:00PROVISO:
  
 PROVIDE OUTSIDE AIR CALCS AT ROUGH
 INSPECTION.
  
 AS PER CONVERSATION WITH PETE RUSSO -
 RETURN AIR JUMPERS FROM OFFICE AREAS TO
 BE THE SAME SIZE AS SUPPLY.DUCT IN
 WAREHOUSE AREA DELETED.DUCT IS
 DROPPING OUT OF RTU - NO RUN OUTS AT
 THIS TIME.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-04-25 Cont ID  
Sent By pkrauss Date 2003-04-25 Time 14:16 Rev Time 0.35
Received By pkrauss Date 2003-04-25 Time 13:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-12-27 Cont ID  
Sent By pkrauss Date 2002-12-27 Time 09:10 Rev Time 0.55
Received By pkrauss Date 2002-12-27 Time 09:02 Sent To  
Notes
2002-12-27 00:00:00DENIED:
  
 PLAN SHEET 3.2 INDICATES OUTSIDE AIR
 CALCULATION (#4) 2437 SQ FT @ .3 CFM PER
 FT.IS THIS CALCULATION FOR THE SPACE
 MARKED 130 OR 129 ON SHEET 1.0?PLEASE
 PROVIDE OUTSIDE AIR CALCULATIONS FOR ALL
 AREAS.
  
 EXHAUST FAN #2 IS NOT LISTED ON THE
 FAN SCHEDULE.PLEASE IDENTIFY.
  
 PROVIDE INFORMATION ON THE CONDENSATE.
 INDICATE TERMINATION LOCATIONS.UNITS
 LARGER THAN 6 TONS SHALL DICHARGE TO
 STORM DRAIN OR DRY WELL.
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 SHALL HAVE:
 ACTIVATION OF ANY AIR DISTRIBUTION
 SYSTEM SMOKE DETECTOR CAUSES A
 SUPERVISORY SIGNAL TO BE INDICATED AT
 A CONSTANTLY ATTENDED LOCATION OR SHALL
 HAVE AN ALARM/STROBE IN NORMALLY
 OCCUPIED AREA.NFPA 90A 4-4.4.2 OR
 4-4.4.3 (A).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-06-18 Cont ID  
Sent By kstevens Date 2003-06-18 Time 09:35 Rev Time 0.50
Received By kstevens Date 2003-06-18 Time 09:35 Sent To  
Notes
2003-06-18 00:00:00REVISION OK - CHANGED KITCHEN LAYOUT AND
 LOCATION OF D.F. & WATER COOLER.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-05-08 Cont ID  
Sent By bstaples Date 2003-05-08 Time 14:16 Rev Time 0.50
Received By bstaples Date   Time   Sent To B
Notes
2003-05-08 00:00:00PLUMBER SHALL COMPLY WITH REQUIREMENTS
 OF PLAN REVIEW ATTACHED.

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-04-26 Cont ID  
Sent By kstevens Date 2003-04-26 Time 11:30 Rev Time 0.33
Received By kstevens Date 2003-04-26 Time 11:29 Sent To  
Notes
2003-04-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT 1.0 KITCHEN SINK SHALL COMPLY
 WITH 11-4.24 AND ALL SUBSECTIONS. PLEASE
 PROVIDE DETAILS.
 2) SHT 3.1 CLEANOUTS SHALL BE INSTALLED
 AT EACH CHANGE OF DIRECTION OF THE BLDG
 DRAIN OR HORIZONTAL WASTE OR SOIL LINES
 GREATER THAN 45 DEGREES. SEC. 708.3.3
 3) SHT 3.1 A SECOND DRINKING FOUNTAIN IS
 REQUIRED PER TABLE 403.1. THE HIGH/LOW
 IS CONSIDERED A SINGLE FIXTURE. ALSO SEE
 SECTION 410.1
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-12-26 Cont ID  
Sent By kstevens Date 2002-12-26 Time 15:47 Rev Time 1.00
Received By kstevens Date 2002-12-26 Time 15:46 Sent To  
Notes
2002-12-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) PER TABLE 403.1 MINIMUM OF 2 DRINKING
 FOUNTAINS ARE REQUIRED. 1 FOR WAREHOUSE
 AND 1 FOR BUSINESS/SHOWROOM AREA. ALSO
 SEE SECTION 410.1
 2) PLEASE PROVIDE A SANITARY RISER DIA-
 GRAM AND A WATER RISER DIAGRAM.
 3) WILL THERE BE ANY FOOD COOKED OR
 SERVED AT THE DEMO KITCHEN?
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377