Plan Review Stops For Permit 02111907 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2003-06-03 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2003-06-03 |
Time |
10:04 |
Rev Time |
0.55 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2003-06-03 00:00:00 | INTERIOR OFFICE REVISION OK6/3/03 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2003-05-22 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2003-05-22 |
Time |
11:51 |
Rev Time |
0.50 |
Received By |
jwitmer |
Date |
2003-05-22 |
Time |
11:51 |
Sent To |
|
|
Notes |
2003-05-22 00:00:00 | REVISION: RAMP OK |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2003-05-08 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2003-05-08 |
Time |
14:16 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2003-05-06 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 02111907 | | ADD:1701 OKEECHOBEE RD STE 1743 | | CONT:GLOBAL CONSTRUCTION | | CONTACT : GARY TALTON | | TEL: (561)351-4134 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | *****BUILDING PROVISO******* | | 1) THE AREA ABOVE "THE AREA OF REFUGE" | | SIGN INDICATING "NOT TO BE USED AS A | | STORAGE AREA"!!!! NOT INTENDED FOR THAT | | USE, THE MINIMUM LOADING WOULD HAVE TO | | BE 125 LBS. | | ******OR******* | | IF THIS AREA IS ENTENDED FOR STORAGE: | | 106.4.2 STORAGE & FACTORY- INDUS- | | TRIAL OCCUPANCIES. IT SHALL BE THE | | RESPONSIBILITY OF THE OWNER, AGENT, | | PROPIETOR OR OCCUPANT OF GROUP S AND | | GROUP F OCCUPANCIES, OR ANY OCCUPANCY | | WHERE EXCESSIVE FLOOR LOADING IS LIKELY | | TO OCCUR, TO EMPLOY A COMPETENT ARCHI- | | TECT OR ENGINEER IN COMPUTING THE SAFE | | FLOOR LOAD CAPACITY. ALL SUCH COMPUTA- | | TIONS SHALL BE ACCOMPANIED BY AN AFFA- | | DAVIT FROM THE ARCHITECT OR ENGINEER | | STATING THE SAFE ALLOWABLE FLOOR LOADS | | ON EACH FLOOR IN POUNDS PER SQ FT.THE | | COMPUTATIONS & AFFADAVIT SHALL BE FILED | | AS A PERMANENT RECORD OF THE BLDG DEPT. | | | | 106.4.3.SIGNS REQUIRED. IN EVERY | | BUILDING OR PART OF A BUILDING USED FOR | | STORAGE, INDUSTRIAL OR HAZARDOUS PUR- | | POSES, THE SAFE FLOOR LOADS, AS REVIEWED | | BY THE BUILDING OFFICIAL ON THE PLAN, | | SHALL BE MARKED ON PLATES OF APPROVED DE | | SIGN WHICH SHALL BE SUPPLIED & SECURELY | | AFFIXED BY THE OWNER OF THE BUILDING IN | | A CONSPICUOUS PLACE IN EACH STORY TO | | WHICH THEY RELATE. SUCH PLATES SHALL NOT | | BE REMOVEDOR DEFACED, & IF LOST, | | REMOVED THE OWNER OF THE BUILDING SHALL | | REPLACE THEM. | | | | JIM WITMER | | BUILDING PLAN REVIEW | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2003-04-29 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2003-04-29 |
Time |
12:51 |
Rev Time |
0.75 |
Received By |
jwitmer |
Date |
2003-04-29 |
Time |
12:29 |
Sent To |
|
|
Notes |
2003-04-29 00:00:00 | | | BUILDING PLAN REVIEW | | PERMIT: 02111907 | | ADD: 1701 OKEECHOBEE RD | | CONT:(PLAN REVIEW) | | GLOBAL CONSTRUCTION ASSOC | | TEL: (954)971-9500 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | 1) 11.4.1.3 ACCESSIBLE BUILDINGS: | | NEW CONSTRUCTION,(9) IN BUILDINGS OR FAC | | ILITIES, OR PORTIONS OF BUILDINGS OR FAC | | ILITIES, REQUIRED TO BE ACCESSIBLE, | | ACCESSIBLE MEANS OF EGRESS SHALL BE PROV | | IDED IN THE SAME NUMBER AS REQUIRED FOR | | EXITS BY THE LOCAL BUILDING / LIFE | | SAFETY REGULATIONS. WHERE A REQUIRED | | EXIT FROM AN OCCUPIABLE LEVEL ABOVE OR B | | ELOW A LEVEL OF ACCESSIBLE EXIT DIS- | | CHARGE IS NOT ACCESSIBLE, AN AREA OF RES | | CUE ASSISTANCE SHALL BE PROVIDED ON EACH | | LEVEL ( IN A NUMBER EQUAL TO THAT OF INA | | CCESSIBLE REQUIRED EXITS). | | 15,500 SF OPEN TO PUBLIC/60 MERCANTILE= | | 258 OCC LOAD. | | | | 1004.1.2 REQUIRES (2) REMOTE MEANS OF | | EGRESS, SINCE THE BACK EGRESS DOORS ARE | | NOT ACCESSIBLE THEY WILL REQUIRE AN AREA | | OF RESCUE ASSISTANCE COMPLYING WITH | | 11-4.3.11 | | 1.LOCATION & CONSTRUCTION (5) | | 2.SIZE | | 3.STAIRWAY WIDTH | | 4.TWO WAY COMMUNICATION | | 5.IDENIFICATION | | | | BUILDING PLAN REVIEW | | JIM WITMER | | (561)659-8096 X 8412 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2003-01-06 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2003-01-06 |
Time |
07:11 |
Rev Time |
3.25 |
Received By |
jwitmer |
Date |
2003-01-03 |
Time |
14:56 |
Sent To |
|
|
Notes |
2003-01-06 00:00:00 | | | BUILDING PLAN REVIEW | | PERMIT: 02111907 | | ADD: 1701 OKEECHOBEE ROAD | | CONT: GLOBAL CONSTRUCTION ASSOC | | TEL: (954)971-9500 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | 1) PERMIT APPLICATION HAS THE ADDRESS | | FOR BUILDING # 2 THAT IS NOT BUILT. | | | | SITE ADDRESS; | | 1801 OKEECHOBEE ROAD | | | | BUILDING # 1; | | 1701 OKEECHOBEE ROAD | | THE TENANT (SUITE #) TO BE BETWEEN 1701 | | AND 1803.THE CITY MASTER STREET GUIDE | | DOES NOT HAVE LISTED A OLD OKEECHOBEE | | ROAD. THE CITY NAME FOR THIS STREET IS | | "OKEECHOBEE ROAD". WHEN YOU CROSS INTO | | THE COUNTY UNINCORPORATED AREAS THE | | STREET NAME IN THE COUNTY IS "OLD OKEE- | | CHOBEE ROAD". | | | | 2)MEANS OF EGRESS: A CONTINUOUS AND | | UNOBSTRUCTED WAY OF TRAVEL FROM ANY | | POINT IN A BUILDING OR STRUCTURE TO A | | PUBLIC WAY, CONSISTING OF THREE SEPERATE | | AND DISTINCT PARTS: (1) THE WAY OF THE | | EXIT ACCESS, (2) THE EXIT, AND (3) THE | | THE WAY OF OF THE EXIT DISCHARGE. | | A MEANS OF EGRESS COMPRISES THE VERTICAL | | AND HORIZONTAL WAYS OF TRAVEL AND | | INCLUDE THE INTERVENING ROOM SPACE,DOORS | | CORRIDORS,PASSAGEWAYS,BALCONIES, STAIRS, | | RAMPS, ENCLOSURES, LOBBIES, HORIZONTAL | | EXITS, COURTS AND YARDS.1001.1.3 | | THE PLAN INDICATES THE BUSINESS OCCUPAN- | | CY HAVING TO EXIT THROUGH THE WAREHOUSE | | CLASSIFIED AS S2 STORAGE. THE CODE DOES | | ALLOW FOR RETAIL TO EXIT THROUGH A STOR- | | AGE ROOM WELL MARKED BUT NOT THROUGH A | | S2 WAREHOSE WITHOUT 2 HR SEPERATION! | | | | 3)BEFORE A PERMIT TO CONSTRUCT, MAY | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | SET OF PLANS MUST BE STAMPED BY THAT | | OFFICE, AND A COPY OF THE PAID RECEIPT | | ATTACHED TO THE PERMIT APPLICATION. | | PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | | | LOOK FOR COMMENTS BY THE OTHER PLAN | | REVIEW DISCIPLINES THAT MAY BE WRITTEN | | ON THE APPLICATION, PLANS, OR ATTACHED | | SEPARATELY. WHEN RESUBMITTING PLANS | | PLEASE CLEARLY INDICATE THE REVISION AND | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | ARY. A TRANSMITTAL LETTER LISTING THE | | ORIGINAL REVIEW COMMENT NUMBER, WITH A | | DESCRIPTION OF THE REVISION MADE, IDEN- | | TIFYING THE SHEET OR SPECIFICATION PAGE | | WHERE THE CHANGES CAN BE FOUND, WILL | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION. | | JIM WITMER | | PLAN REVIEW | | TEL: (561)659-8096 EX.8412 | | FAX: (561)659-8026 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2003-06-09 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-06-09 |
Time |
06:41 |
Rev Time |
0.33 |
Received By |
dpalmer |
Date |
2003-06-09 |
Time |
06:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2003-05-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-05-07 |
Time |
09:50 |
Rev Time |
0.25 |
Received By |
dpalmer |
Date |
2003-05-07 |
Time |
09:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2003-05-06 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-05-06 |
Time |
07:36 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2003-05-06 |
Time |
07:36 |
Sent To |
|
|
Notes |
2003-05-06 00:00:00 | ************ UNSAT ************* | | | | RESUB HAS NO ORIG PACKAGE, PERMIT APPL- | | -CATION ETC. | | | | PLEASE RESUB W. ORIG PACKAGE, TAKE OUT | | OLD SHEETS AND INSERT NEW SHEETS TO | | MAKE TWO COMPLETE SETS FOR REVIEW AND | | STAMPING. | | | | PLEASE SUBMIT FOR REVIEW AT THAT TIME. | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2003-04-28 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-04-28 |
Time |
11:18 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2003-04-28 |
Time |
11:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2002-12-06 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2002-12-05 |
Time |
0546 |
Rev Time |
1.00 |
Received By |
dpalmer |
Date |
2002-12-05 |
Time |
15:07 |
Sent To |
|
|
Notes |
2002-12-05 00:00:00 | ************* UNSAT **************** | | | | 1)NOTE: PLEASE CLARIFY DIRECTION OF | | PANELS. PANELS SEEM TO BE FACING RM | | 112 AND NOT IN THE SAME LOCATION OF | | TRANSFORMER? | | | | 2)NOTE: PLEASE NOTE MISSING EQUIPMENT | | GROUNDING CONDUCTOR BETWEEN PANEL "H1" | | TRANSFORMER AND PANELS "L1 AND "L". | | 250-122/250-24/250-30 | | PLEASE ALSO SHOW EQUIPMENT GROUNDING | | MEANS BETWEEN | | | | 3)NOTE: PLEASE CLARIFY/ NEW OR EXSITNG | | SHOW WINDOW RECEPTS PER 210-62 | | | | 4)NOTE: PLEASE CLARIFY CIRCUITING FOR | | EM LT/ EXT LTS SHOWN PER 700-12E. | | | | PLEASE SUBMIT THE ABOVE INFOMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2003-06-18 |
|
|
Cont ID |
|
Sent By |
nmccray |
Date |
2003-06-18 |
Time |
11:38 |
Rev Time |
0.00 |
Received By |
nmccray |
Date |
2003-06-18 |
Time |
11:38 |
Sent To |
|
|
Notes |
2003-06-18 00:00:00 | ************PROVISO********************* | | SEPARATE "SHOP DRAWING" AND PERMIT | | APPLICATION IS REQUIRED FOR FIRE ALARM | | SYSTEM REMODEL. | | | | NATE MCCRAY, CAPTAIN | | 805-6722 OR 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2003-04-25 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2003-04-25 |
Time |
12:52 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2003-04-25 |
Time |
12:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2002-12-12 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2002-12-12 |
Time |
13:33 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2002-12-12 |
Time |
13:33 |
Sent To |
|
|
Notes |
2002-12-12 00:00:00 | 1) IT APPEARS THAT SOME EXIT ACCESS | | OCCURS WITHIN SPACE 130 FROM THE | | OFFICES. IS IT NOT TRUE THAT SPACE 130 | | CAN BE CONSIDERED MORE HAZARDOUS THAN | | THE OFFICE AREA. PLEASE SEE NFPA 101, | | THE LIFE SAFETY CODE, 2000 EDITION, | | SECTION 7.5.2.1, IMPEDIMENTS TO EXITS. | | | | 2) SEPARATE PLANS AND PERMITS | | REQUIRED FOR THE PLANNED REMODEL OF | | THE FIRE ALARM SYSTEM. | | | | 3) NO FIRE SPRINKLER SYSTEM DRAWINGS | | AS NOTED ON TITLE PAGE. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2003-05-28 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-05-28 |
Time |
13:44 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-05-28 |
Time |
13:44 |
Sent To |
|
|
Notes |
2003-05-28 00:00:00 | COMM BOARD #61 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2003-05-02 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-05-02 |
Time |
17:35 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-05-02 |
Time |
17:35 |
Sent To |
|
|
Notes |
2003-05-02 00:00:00 | COMM BOARD #7 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2003-04-16 |
|
|
Cont ID |
|
Sent By |
shernand |
Date |
2003-04-16 |
Time |
10:21 |
Rev Time |
0.00 |
Received By |
shernand |
Date |
2003-04-16 |
Time |
10:21 |
Sent To |
|
|
Notes |
2003-04-16 00:00:00 | COMM BOARD #27 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2002-12-02 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2002-12-02 |
Time |
08:22 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2002-11-27 |
Time |
08:22 |
Sent To |
|
|
Notes |
2002-12-02 00:00:00 | TO COMM BOARD #5./WRT. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2003-06-18 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-06-18 |
Time |
09:56 |
Rev Time |
0.30 |
Received By |
pkrauss |
Date |
2003-06-18 |
Time |
09:56 |
Sent To |
|
|
Notes |
2003-06-18 00:00:00 | PROVISO: | | | | PROVIDE OUTSIDE AIR CALCS AT ROUGH | | INSPECTION. | | | | AS PER CONVERSATION WITH PETE RUSSO - | | RETURN AIR JUMPERS FROM OFFICE AREAS TO | | BE THE SAME SIZE AS SUPPLY.DUCT IN | | WAREHOUSE AREA DELETED.DUCT IS | | DROPPING OUT OF RTU - NO RUN OUTS AT | | THIS TIME. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2003-04-25 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-04-25 |
Time |
14:16 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2003-04-25 |
Time |
13:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2002-12-27 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2002-12-27 |
Time |
09:10 |
Rev Time |
0.55 |
Received By |
pkrauss |
Date |
2002-12-27 |
Time |
09:02 |
Sent To |
|
|
Notes |
2002-12-27 00:00:00 | DENIED: | | | | PLAN SHEET 3.2 INDICATES OUTSIDE AIR | | CALCULATION (#4) 2437 SQ FT @ .3 CFM PER | | FT.IS THIS CALCULATION FOR THE SPACE | | MARKED 130 OR 129 ON SHEET 1.0?PLEASE | | PROVIDE OUTSIDE AIR CALCULATIONS FOR ALL | | AREAS. | | | | EXHAUST FAN #2 IS NOT LISTED ON THE | | FAN SCHEDULE.PLEASE IDENTIFY. | | | | PROVIDE INFORMATION ON THE CONDENSATE. | | INDICATE TERMINATION LOCATIONS.UNITS | | LARGER THAN 6 TONS SHALL DICHARGE TO | | STORM DRAIN OR DRY WELL. | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | SHALL HAVE: | | ACTIVATION OF ANY AIR DISTRIBUTION | | SYSTEM SMOKE DETECTOR CAUSES A | | SUPERVISORY SIGNAL TO BE INDICATED AT | | A CONSTANTLY ATTENDED LOCATION OR SHALL | | HAVE AN ALARM/STROBE IN NORMALLY | | OCCUPIED AREA.NFPA 90A 4-4.4.2 OR | | 4-4.4.3 (A). | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2003-06-18 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-06-18 |
Time |
09:35 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2003-06-18 |
Time |
09:35 |
Sent To |
|
|
Notes |
2003-06-18 00:00:00 | REVISION OK - CHANGED KITCHEN LAYOUT AND | | LOCATION OF D.F. & WATER COOLER. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2003-05-08 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2003-05-08 |
Time |
14:16 |
Rev Time |
0.50 |
Received By |
bstaples |
Date |
|
Time |
|
Sent To |
B |
|
Notes |
2003-05-08 00:00:00 | PLUMBER SHALL COMPLY WITH REQUIREMENTS | | OF PLAN REVIEW ATTACHED. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2003-04-26 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-04-26 |
Time |
11:30 |
Rev Time |
0.33 |
Received By |
kstevens |
Date |
2003-04-26 |
Time |
11:29 |
Sent To |
|
|
Notes |
2003-04-26 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 11 | | | | 1) SHT 1.0 KITCHEN SINK SHALL COMPLY | | WITH 11-4.24 AND ALL SUBSECTIONS. PLEASE | | PROVIDE DETAILS. | | 2) SHT 3.1 CLEANOUTS SHALL BE INSTALLED | | AT EACH CHANGE OF DIRECTION OF THE BLDG | | DRAIN OR HORIZONTAL WASTE OR SOIL LINES | | GREATER THAN 45 DEGREES. SEC. 708.3.3 | | 3) SHT 3.1 A SECOND DRINKING FOUNTAIN IS | | REQUIRED PER TABLE 403.1. THE HIGH/LOW | | IS CONSIDERED A SINGLE FIXTURE. ALSO SEE | | SECTION 410.1 | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 | | (561) 805-6721 | | FAX (561) 653-2692 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2002-12-26 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2002-12-26 |
Time |
15:47 |
Rev Time |
1.00 |
Received By |
kstevens |
Date |
2002-12-26 |
Time |
15:46 |
Sent To |
|
|
Notes |
2002-12-26 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 11 | | | | 1) PER TABLE 403.1 MINIMUM OF 2 DRINKING | | FOUNTAINS ARE REQUIRED. 1 FOR WAREHOUSE | | AND 1 FOR BUSINESS/SHOWROOM AREA. ALSO | | SEE SECTION 410.1 | | 2) PLEASE PROVIDE A SANITARY RISER DIA- | | GRAM AND A WATER RISER DIAGRAM. | | 3) WILL THERE BE ANY FOOD COOKED OR | | SERVED AT THE DEMO KITCHEN? | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|
|